ENS 57327: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot insert)
 
(StriderTol Bot change)
 
Line 19: Line 19:
| event text = The following information was provided by the South Carolina Department of Health and Environmental Control (the Department) via email:
| event text = The following information was provided by the South Carolina Department of Health and Environmental Control (the Department) via email:
On September 16, 2024, at 1415 EDT, the Department was notified by Alpek Polyester (the licensee) that while performing semi-annual shutter checks the licensee discovered that two gauges (model: Berthold LB 300 IRL) had cables that were malfunctioning, and that the sources were unable to be retracted to the shielded and locked position. One gauge contains a 6 mCi (original activity) cobalt-60 source and the other contains a 2.5 mCi (original activity) cobalt-60 source. Currently the cobalt sources are 1.07 mCi and 0.044 mCi, respectively. These sources were placed into service on September 17, 2011. On September 17, 2024, the department on-call duty officer met the licensee's radiation safety officer at 0900 EDT to perform a visual inspection and radiation survey of the gauge. The highest radiation measured was 0.5 microR/hr.  The licensee has contacted a licensed vendor to schedule the repair of the drive cables.
On September 16, 2024, at 1415 EDT, the Department was notified by Alpek Polyester (the licensee) that while performing semi-annual shutter checks the licensee discovered that two gauges (model: Berthold LB 300 IRL) had cables that were malfunctioning, and that the sources were unable to be retracted to the shielded and locked position. One gauge contains a 6 mCi (original activity) cobalt-60 source and the other contains a 2.5 mCi (original activity) cobalt-60 source. Currently the cobalt sources are 1.07 mCi and 0.044 mCi, respectively. These sources were placed into service on September 17, 2011. On September 17, 2024, the department on-call duty officer met the licensee's radiation safety officer at 0900 EDT to perform a visual inspection and radiation survey of the gauge. The highest radiation measured was 0.5 microR/hr.  The licensee has contacted a licensed vendor to schedule the repair of the drive cables.
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2024/20240924en.html#en57327
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2024/20240925en.html#en57327
}}
}}


{{ENS-Nav}}
{{ENS-Nav}}

Latest revision as of 06:20, 25 September 2024

ENS 57327 +/-
Where
Alpek Polyester Usa, Llc
Gaston, South Carolina (NRC Region 1)
License number: 189
Organization: Sc Dept Of Environmental Services
Reporting
Agreement State
Time - Person (Reporting Time:+21.55 h0.898 days <br />0.128 weeks <br />0.0295 months <br />)
Opened: Andrew Roxburgh
12:03 Sep 17, 2024
NRC Officer: Robert A. Thompson
Last Updated: Sep 17, 2024
57327 - NRC Website