ENS 54885: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot insert)
 
(StriderTol Bot change)
 
Line 9: Line 9:
| unit = 2
| unit = 2
| utype = W-4-LP, W-4-LP
| utype = W-4-LP, W-4-LP
| cfr = 10 CFR 50.72(b)(2)(iv)(A), 10 CFR 50.72(b)(2)(iv)(B), 10 CFR 50.72(b)(3)(iv)(A)
| cfr = 10 CFR 50.72(b)(2)(iv)(A)
| emergency class = Non Emergency  
| emergency class = Non Emergency
| notification date = 09/05/2020 02:27
| notification date = 09/05/2020 02:27
| notification by = Perry Graham
| notification by = Perry Graham
Line 17: Line 17:
| last update date = 09/05/2020
| last update date = 09/05/2020
| title = Manual Reactor Trip and Automatic Safety Injection
| title = Manual Reactor Trip and Automatic Safety Injection
| event text = On September 4, 2020, DC Cook Unit 2 experienced a lowering Reactor Coolant System (RCS) pressure caused by a failed open Reactor Coolant Pressurizer Spray valve. At approximately 2242 [EDT], a manual Reactor Trip was performed due to the lowering RCS pressure. Following the manual reactor trip, an automatic Safety Injection was actuated due to the lowering RCS pressure. RCS pressure has recovered to normal and is stable.
| event text = On September 4, 2020, DC Cook Unit 2 experienced a lowering Reactor Coolant System (RCS) pressure caused by a failed open Reactor Coolant Pressurizer Spray valve. At approximately 2242 [EDT], a manual Reactor Trip was performed due to the lowering RCS pressure. Following the manual reactor trip, an automatic Safety Injection was actuated due to the lowering RCS pressure. RCS pressure has recovered to normal and is stable.
This notification is being made in accordance with 10 CFR 50.72(b)(2)(iv)(B), Reactor Protection System (RPS) actuation, and 10 CFR 50.72(b)(2)(iv)(A), ECCS Discharge to RCS, as a four (4) hour report. Notification is also being made as an 8 hour report under 10 CFR 50.72(b)(3)(iv)(A), Reactor Protection System (RPS), Containment Isolation, Emergency Core Cooling (ECCS), Auxiliary Feedwater System (AFW), and Emergency AC Electrical Power actuations. The DC Cook Resident NRC Inspector has been notified.
This notification is being made in accordance with 10 CFR 50.72(b)(2)(iv)(B), Reactor Protection System (RPS) actuation, and 10 CFR 50.72(b)(2)(iv)(A), ECCS Discharge to RCS, as a four (4) hour report. Notification is also being made as an 8 hour report under 10 CFR 50.72(b)(3)(iv)(A), Reactor Protection System (RPS), Containment Isolation, Emergency Core Cooling (ECCS), Auxiliary Feedwater System (AFW), and Emergency AC Electrical Power actuations. The DC Cook Resident NRC Inspector has been notified.
Unit 2 is being supplied by offsite power. All control rods fully inserted. Aux Feedwater Pumps started as required and are operating properly. All ECCS components operated as required including Containment Isolation. Decay heat is being removed via the Condenser Steam Dumps and ECCS has been secured. Three of four Reactor Coolant Pumps were secured and RCS pressure has recovered to normal pressure and is stable. Preliminary evaluation indicates all plant systems functioned normally following the Reactor Trip and Safety Injection. DC Cook Unit 2 remains stable in Mode 3. No radioactive release is in progress as a result of this event.
Unit 2 is being supplied by offsite power. All control rods fully inserted. Aux Feedwater Pumps started as required and are operating properly. All ECCS components operated as required including Containment Isolation. Decay heat is being removed via the Condenser Steam Dumps and ECCS has been secured. Three of four Reactor Coolant Pumps were secured and RCS pressure has recovered to normal pressure and is stable. Preliminary evaluation indicates all plant systems functioned normally following the Reactor Trip and Safety Injection. DC Cook Unit 2 remains stable in Mode 3. No radioactive release is in progress as a result of this event.
Unit 1 was not affected and remains in Mode 1, 100 % power.
Unit 1 was not affected and remains in Mode 1, 100 % power.
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2020/20200907en.html#en54885
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2020/20200907en.html#en54885
}}{{unit info
| Unit =  2
| type =
| Scram code =  M/R
| Reactor critical =  Y
| Initial power =  92
| Initial reactor mode =  Power Operation
| Current power =  0
| Current reactor mode =  Hot Standby
}}
}}


{{ENS-Nav}}[[Category:Power Reactor]]
{{ENS-Nav}}[[Category:Power Reactor]]

Latest revision as of 11:23, 15 January 2021

ENS 54885 +/-
Where
Cook American Electric Power icon.png
Michigan (NRC Region 3)
Reporting
10 CFR 50.72(b)(2)(iv)(A), System Actuation - ECCS Discharge
Time - Person (Reporting Time:+-0.25 h-0.0104 days <br />-0.00149 weeks <br />-3.4245e-4 months <br />)
Opened: Perry Graham
02:27 Sep 5, 2020
NRC Officer: Bethany Cecere
Last Updated: Sep 5, 2020
54885 - NRC Website