{{#Wiki_filter:Module III - Fire Analysis Appendix H: Damage Criteria and Damage Time Joint EPRI/NRC-RES Fire PRA Workshop August 6-10, 2018 A Collaboration of the Electric Power Research Institute (EPRI) & U.S. NRC Office of Nuclear Regulatory Research (RES)
-RES Fire PRA WorkshopAugust 6-10, 2018Module III
 
-Fire AnalysisAppendix H: Damage Criteria and Damage TimeA Collaboration of the Electric Power Research Institute (EPRI) & U.S. NRC Office of Nuclear Regulatory Research (RES) 2Damage CriteriaCharacterizing targetsA targetis something otherthan the fire ignition source that may become involved in the fire
Damage Criteria Characterizing targets A target is something other than the fire ignition source that may become involved in the fire
-Defined as a part of the fire scenarioGenerally there are two target types:
    - Defined as a part of the fire scenario Generally there are two target types:
-Damage target: A component (or cable) that is important to plant operations that may be damaged by an exposing fire
    - Damage target: A component (or cable) that is important to plant operations that may be damaged by an exposing fire
-Secondary ignition target: Any object that is combustible and that may be ignited by an exposing fire thereby spreading the fireOne object can actually be both
    - Secondary ignition target: Any object that is combustible and that may be ignited by an exposing fire thereby spreading the fire One object can actually be both
-e.g., the first cable tray above a fire ignition source-This presentation is mainly about damage targets, but the same general approach applies to ignition targets as well 3Damage CriteriaDamage ThresholdsDamage (or Failure) Threshold: the minimum value of an exposure environment parameter that canlead to the failure of the damage target of interest within the time scale of the fire-Can be a temperature  
    - e.g., the first cable tray above a fire ignition source This presentation is mainly about damage targets, but the same general approach applies to ignition targets as well 2
-exposure to high temperatures such as in a hot gas layer or fire plume
 
-Can be a radiant heat flux  
Damage Criteria Damage Thresholds Damage (or Failure) Threshold: the minimum value of an exposure environment parameter that can lead to the failure of the damage target of interest within the time scale of the fire
-generally due to direct radiant heating from the luminous flame zone of a fire
    - Can be a temperature - exposure to high temperatures such as in a hot gas layer or fire plume
-In theory, it could be a minimum smoke density, but we aren't that smart (more on smoke shortly)Corresponding PRA Standard SRs: FSS
    - Can be a radiant heat flux - generally due to direct radiant heating from the luminous flame zone of a fire
-C5, C6 and D9 4Damage CriteriaDamage ThresholdsDamage thresholds are of primary interest to Task 8  
    - In theory, it could be a minimum smoke density, but we arent that smart (more on smoke shortly)
-Scoping Fire Modeling, but also play a role in Task 11  
Corresponding PRA Standard SRs: FSS-C5, C6 and D9 3
-Detailed Fire ModelingZone-of-Influence (ZOI)  
 
-The area around a fire where radiative and convective heat transfer is sufficiently strong to damage equipment or cables and/or heat other materials to the point of ignition.
Damage Criteria Damage Thresholds Damage thresholds are of primary interest to Task 8 - Scoping Fire Modeling, but also play a role in Task 11 - Detailed Fire Modeling Zone-of-Influence (ZOI) - The area around a fire where radiative and convective heat transfer is sufficiently strong to damage equipment or cables and/or heat other materials to the point of ignition.
-Damage thresholds are most useful when screening out specific fire ignition sources in Task 8:If the closest target is outside the ZOI (no damage) andfire cannot ignite any secondary combustibles, then we screen that source out of the analysis as non
    - Damage thresholds are most useful when screening out specific fire ignition sources in Task 8:
-threatening (more later)
If the closest target is outside the ZOI (no damage) and fire cannot ignite any secondary combustibles, then we screen that source out of the analysis as non-threatening (more later)
-When we get to Task 11, we'll need damage time (more later)Also Note:If an electrical cable is damaged, we assume that it will also be ignited. FAQ 16
    - When we get to Task 11, well need damage time (more later)
-0011 offers a clarification on cable tray ignition, damage and fire propagation through cable traysBased on testing experience  
Also Note: If an electrical cable is damaged, we assume that it will also be ignited. FAQ 16-0011 offers a clarification on cable tray ignition, damage and fire propagation through cable trays Based on testing experience - arcing causes piloted ignition. FAQ 16-0011 clarifies the conditions for fire propagation after ignition.
-arcing causes piloted ignition. FAQ 16-0011 clarifies the conditions for fire propagation after ignition.
4
5Damage CriteriaDamage ThresholdsThe damage threshold is specific to the damage target based on target type and target characteristics
 
-What type of component?
Damage Criteria Damage Thresholds The damage threshold is specific to the damage target based on target type and target characteristics
-What are it's vulnerabilities (e.g., heat, smoke, water-)?
    - What type of component?
-What is the weak link relative to damage and the fire scenario?Most fire scenarios focus on:
    - What are its vulnerabilities (e.g., heat, smoke, water)?
-Electrical cables (power, control, and instrumentation)
    - What is the weak link relative to damage and the fire scenario?
-Electronics and integrated circuit devices 6CablesClassification of cables by insulation typeCable insulations fall into one of two major categories:Thermoplastic (TP):capable of softening or fusing when heated and of hardening again when cooled (Merriam
Most fire scenarios focus on:
-Webster)-TP materials melt when heated and solidify when cooledThermoset (TS): capable of becoming permanently rigid when heated or cured (Marriam-Webster)-On heating TS materials may soften, swell, blister, crack, smolder and/or burn but they won't meltBoth types are used in U.S. NPPs
    - Electrical cables (power, control, and instrumentation)
-Thermoplastic is more common in older plants, also used in non
    - Electronics and integrated circuit devices 5
-vital applications such as lighting and communications
 
-Thermoset is more common in newer plants
Cables Classification of cables by insulation type Cable insulations fall into one of two major categories:
-Practices also vary based on utility preference at the time of construction 7The following are defined as generic damage thresholds for the most common damage targets  
Thermoplastic (TP): capable of softening or fusing when heated and of hardening again when cooled (Merriam-Webster)
-cables:*if you have case specific information, you may use alternate values if you can establish a technical basis
    - TP materials melt when heated and solidify when cooled Thermoset (TS): capable of becoming permanently rigid when heated or cured (Marriam-Webster)
-many specific cable types will have much higher damage thresholds if you can establish a more specific insulation type for target cablesDamage CriteriaCable damage thresholdsCable TypeRadiant Heating CriteriaTemperature CriteriaThermoplastic6 kW/m 2(0.5 BTU/ft2s)205°C (400°F)Thermoset11 kW/m 2(1.0 BTU/ft2s)330°C (625°F)NUREG/CR-6850 Appendix HFAQ 16-0011 8Damage CriteriaSensitive ElectronicsElectronic devices refers mainly to control components that are based on integrated circuit type devices
    - On heating TS materials may soften, swell, blister, crack, smolder and/or burn but they wont melt Both types are used in U.S. NPPs
-Circuit cards, amplifiers, D/A and A/D converters, signal conditioning devices, communications equipment, computers, instrument transmitters, etc. Does not include electro
    - Thermoplastic is more common in older plants, also used in non-vital applications such as lighting and communications
-mechanical devices that lack integrated circuit elements-Relays, switches, indicating lights, breakers, etc.Typical damage thresholds for electronics are much lower than cables:
    - Thermoset is more common in newer plants
-3 kW/m 2(0.25 BTU/ft
    - Practices also vary based on utility preference at the time of construction 6
: 2) and 65 oC (150°F)-FAQ 13-004 Treatment of Sensitive Electronics 9Damage CriteriaSensitive ElectronicsFAQ 13-004 discusses an approach for treating "sensitive electronics" targets in fire scenarios
 
-Points out that there is no clear definition of what constitute "sensitive electronics" in NUREG/CR
Damage Criteria Cable damage thresholds The following are defined as generic damage thresholds for the most common damage targets - cables:
-6850-Proposed treatment assumes that equipment that is sensitive to increased temperatures will be located inside electrical enclosures
Radiant Heating Criteria Temperature Criteria Cable Type NUREG/CR-6850 Thermoplastic        6 kW/m2 (0.5 BTU/ft2s)     205°C (400°F)
-Guidance is based on FDS fire simulations317kW transient fire located 1 m from a cabinetRadiometer located inside the cabinet to measure internal heat fluxes-In order to reach damaging heat fluxes inside the cabinet, conditions outside the cabinet are consistent with the damage criteria for Themoset cables 10Damage CriteriaSome other specific casesSome items are considered invulnerable to fire
Appendix H Thermoset            11 kW/m2 (1.0 BTU/ft2s)   330°C (625°F)
-induced damage:
FAQ 16-0011
-Ferrous metal pipes and tanks
  *if you have case specific information, you may use alternate values if you can establish a technical basis - many specific cable types will have much higher damage thresholds if you can establish a more specific insulation type for target cables 7
-Passive components such as flow check valves
 
-Concrete structural or partitioning elements except when considering random failure likelihood in multi
Damage Criteria Sensitive Electronics Electronic devices refers mainly to control components that are based on integrated circuit type devices
-compartment scenariosi.e., we do notconsider fire
    - Circuit cards, amplifiers, D/A and A/D converters, signal conditioning devices, communications equipment, computers, instrument transmitters, etc.
-induced structural failure of concreteThings you still need to watch for:
Does not include electro-mechanical devices that lack integrated circuit elements
-Soldered piping (e.g., air/gas lines that are soldered copper)
    - Relays, switches, indicating lights, breakers, etc.
-Flexible boots/joints/sleeves on piping (e.g., the Vandellosscenario)-Exposed structural steel given a very large fire source (e.g., catastrophic loss of the main TG set  
Typical damage thresholds for electronics are much lower than cables:
-more later) 11Damage CriteriaEverything else-For other devices (e.g., motors, switchgear, etc.) we typically look to either the supporting cables or controls
    - 3 kW/m2 (0.25 BTU/ft2) and 65oC (150°F)
-A electric motor driven pump is fed by power cables, and those cables are generally more vulnerable to fire damage than the pump itself
    - FAQ 13-004 Treatment of Sensitive Electronics 8
-A switchgear is supported by both power and control cables  
 
-typically loss of the control cables means loss of functionality (no control power means breaker will not auto
Damage Criteria Sensitive Electronics FAQ 13-004 discusses an approach for treating sensitive electronics targets in fire scenarios
-cycle and cannot be remotely cycled)
    - Points out that there is no clear definition of what constitute sensitive electronics in NUREG/CR-6850
-A battery charger usually contains some integrated circuit cards that control charging rate and monitor battery status
    - Proposed treatment assumes that equipment that is sensitive to increased temperatures will be located inside electrical enclosures
-A motor operated valve- again, look at the cables 12Damage CriteriaDamage ThresholdsFor additional rules related to damage criteria, see H.1.1; e.g.:
    - Guidance is based on FDS fire simulations 317kW transient fire located 1 m from a cabinet Radiometer located inside the cabinet to measure internal heat fluxes
-Cables in conduit: potential damage targets, but will not contribute to fire growth and spread  
    - In order to reach damaging heat fluxes inside the cabinet, conditions outside the cabinet are consistent with the damage criteria for Themoset cables 9
-no credit to conduit for delaying the onset of thermal damage.
 
-Cables coated by a fire
Damage Criteria Some other specific cases Some items are considered invulnerable to fire-induced damage:
-retardant coating: treat as exposed cables for damage purposes  
    - Ferrous metal pipes and tanks
-coating may slow the subsequent spread of fire, but we are NOT specific here.
    - Passive components such as flow check valves
13Damage CriteriaDamage ThresholdsPlant-specific or product
    - Concrete structural or partitioning elements except when considering random failure likelihood in multi-compartment scenarios i.e., we do not consider fire-induced structural failure of concrete Things you still need to watch for:
-specific damage thresholds may be usedif appropriate basisis established
    - Soldered piping (e.g., air/gas lines that are soldered copper)
-NUREG/CR-6850 provides some references for information specific to many popular types and brands of cables
    - Flexible boots/joints/sleeves on piping (e.g., the Vandellos scenario)
-Example:
    - Exposed structural steel given a very large fire source (e.g.,
14Damage CriteriaDamage TimeIt is both appropriate and desirable to consider, not just the possibility of damage, but also the time before damage occurs
catastrophic loss of the main TG set - more later) 10
-This is part of Task 11  
 
-Detailed Fire ModelingIt takes time to heat a target to its damage temperature
Damage Criteria Everything else For other devices (e.g., motors, switchgear, etc.) we typically look to either the supporting cables or controls
-If the air temperature (or heat flux) equals the damage threshold, damage times may be prolonged (e.g., 30
    - A electric motor driven pump is fed by power cables, and those cables are generally more vulnerable to fire damage than the pump itself
-60 minutes or more)
    - A switchgear is supported by both power and control cables - typically loss of the control cables means loss of functionality (no control power means breaker will not auto-cycle and cannot be remotely cycled)
-As exposure conditions become more severe, time to damage decreases (e.g., if immersed in flames, may be a few seconds)A damage time gives us a "hook" to credit fire intervention:
    - A battery charger usually contains some integrated circuit cards that control charging rate and monitor battery status
-It tells you how long you have to put the fire and prevent damage
    - A motor operated valve again, look at the cables 11
-We can then ask "what is the probability that given the fire, it will be put out before damage occurs?"
 
-More details on that process later in the week, but for now we'll talk a little about estimating damage time 15Damage CriteriaDamage time  
Damage Criteria Damage Thresholds For additional rules related to damage criteria, see H.1.1; e.g.:
-three common approachesPredict when a fire grows large enough to create damaging environment at the target location (generally most conservative)Empirical approach (intermediate approach, e.g., SDP*)
    - Cables in conduit: potential damage targets, but will not contribute to fire growth and spread - no credit to conduit for delaying the onset of thermal damage.
-Predict the peak exposure condition (temperature or heat flux)
    - Cables coated by a fire-retardant coating: treat as exposed cables for damage purposes - coating may slow the subsequent spread of fire, but we are NOT specific here.
-Use a look
12
-up table to estimate time to damage
 
-Catch: look
Damage Criteria Damage Thresholds Plant-specific or product-specific damage thresholds may be used if appropriate basis is established
-up tables currently only available for generic thermoset and thermoplastic cablesDirect modeling of target thermal response based on fire environment (generally most realistic)
    - NUREG/CR-6850 provides some references for information specific to many popular types and brands of cables
-Use a fire model to predict the temperature response of the target
    - Example:
-When the predicted temperature of the target reaches the damage threshold, assume target failure
13
-Catch: need fire model that does target response calculation
 
-Simplest example: THIEF model for cables (more later)
Damage Criteria Damage Time It is both appropriate and desirable to consider, not just the possibility of damage, but also the time before damage occurs
* Significance Determination Process 16Damage CriteriaDamage time  
      - This is part of Task 11 - Detailed Fire Modeling It takes time to heat a target to its damage temperature
-time to thresholdOne simple approach is to assume damage occurs when the conditions at the target location first reach the damage threshold  
      - If the air temperature (or heat flux) equals the damage threshold, damage times may be prolonged (e.g., 30-60 minutes or more)
-Generally gives the most conservative answer of the three approaches
      - As exposure conditions become more severe, time to damage decreases (e.g., if immersed in flames, may be a few seconds)
*If you can characterize fire growth versus time, then you can use that to predict the fire environment over time even using simple correlationsthat are based on fire heat release rate
A damage time gives us a hook to credit fire intervention:
-Plume temperature correlation  
      - It tells you how long you have to put the fire and prevent damage
-Radiant heating correlation  
      - We can then ask what is the probability that given the fire, it will be put out before damage occurs?
-Steady state hot gas layer temperature correlationIf you are in a hot gas layer situation, you can predict transient temperature profile using a fire model like CFAST or MAGIC
      - More details on that process later in the week, but for now well talk a little about estimating damage time 14
-Won't help much unless you have a transient fire growth profile because HGL develops to steady state very quickly in these models 17Damage CriteriaDamage time  
 
-the look-up tablesThe empirical time to damage tables are an intermediate approach-Still very simple but somewhat conservativeGiven exposure temperature, look-up tables give estimated time to damageTable H-5: Failure Time
Damage Criteria Damage time - three common approaches Predict when a fire grows large enough to create damaging environment at the target location (generally most conservative)
-Temperature Relationship for Thermosetcables (Table A.7.1 from reference H.6).Exposure TemperatureTime to Failure (minutes)o C o F 330 625 28 350 660 13 370 700 9 390 735 7 410 770 5 430 805 4 450 840 3 470 880 2490 (or greater)915 (or greater) 1 18Damage CriteriaDamage time  
Empirical approach (intermediate approach, e.g., SDP*)
-direct response modeling (e.g., THIEF)Assumes a single cable in air (or in a conduit in air)Input is an air temperature profileOutput is cable temperature vs timeAssume damage when cable temperature exceeds thresholdNow part of CFAST and FDS; FDTs
    - Predict the peak exposure condition (temperature or heat flux)
*See:  NUREG/CR
    - Use a look-up table to estimate time to damage
-6931 V3*Simple one
    - Catch: look-up tables currently only available for generic thermoset and thermoplastic cables Direct modeling of target thermal response based on fire environment (generally most realistic)
-dimensional homogeneous heat transfer model 19Thermally-Induced Electrical Failure (THIEF)ExampleCable diam 20 mmMass per length0.3kg/mJacket thickness1.6 mmConduit diameter 14 mmConduit thickness 0 mmDamage temp 205 CAmbient temp 20 C 050100150200250 0500100015002000Temperature [C]Time [C]THIEF ResultsConduitExposureSurfaceConductorCable diam 20 mmMass per length0.3kg/mJacket thickness1.6 mmConduit diameter 14 mmConduit thickness 5 mmDamage temp 205 CAmbient temp 20 C 050100150200250 0500100015002000Temperature [C]Time [C]THIEF ResultsConduitExposureSurfaceConductorNo ConduitCable Inside Conduit 20Damage CriteriaSmoke DamageAppendix T provides an extended discussion of current knowledge regarding smoke damage
    - Use a fire model to predict the temperature response of the target
-This is about smoke and the failure of equipment  
    - When the predicted temperature of the target reaches the damage threshold, assume target failure
-It is not about the impact of smoke on peopleWe are interested in short
    - Catch: need fire model that does target response calculation
-term damage
    - Simplest example: THIEF model for cables (more later)
-Within the time scale of the fire scenario including plant shutdown
* Significance Determination Process 15
-We do not consider longer term issues such as corrosion leading to failure some days or weeks after a fireCorresponding PRA Standard SR: FSS
 
-D9 21Damage CriteriaSmoke DamageBottom Line: Some components are known to be vulnerable to smoke damage, but it takes a dense exposure to cause short term damage So what are the vulnerable components
Damage Criteria Damage time - time to threshold One simple approach is to assume damage occurs when the conditions at the target location first reach the damage threshold
?-High voltage switching equipment (arcing)
      - Generally gives the most conservative answer of the three approaches
-High voltage transmission lines (arcing)
* If you can characterize fire growth versus time, then you can use that to predict the fire environment over time even using simple correlations that are based on fire heat release rate
-Devices such as strip chart recorders that are dependent on fine mechanical motion (binding)
      - Plume temperature correlation
-Un-protected printed circuit cards (deposition and shorting)e.g., exposed within a panel and not provided with a protective coating 22Damage CriteriaSmoke DamageSmoke damage is assessed on an empirical basis:
      - Radiant heating correlation
-We don't set quantitative thresholds
      - Steady state hot gas layer temperature correlation If you are in a hot gas layer situation, you can predict transient temperature profile using a fire model like CFAST or MAGIC
-We don't try to use fire models
      - Wont help much unless you have a transient fire growth profile because HGL develops to steady state very quickly in these models 16
-You should consider the potential failure of vulnerable componentsdue to smoke as a part of your damage target set 23Damage CriteriaSmoke DamageAssume that vulnerable components adjacent to or connected to the fire source will be damaged by smoke:
 
-Within the same electrical cabinet or housing as a fire sourcee.g. given a panel fire, the whole panel is lost due to smoke and/or heat
Damage Criteria Damage time - the look-up tables Table H-5: Failure Time-Temperature Relationship for The empirical          Thermoset cables (Table A.7.1 from reference H.6).
-In an adjacent cabinet if the cabinet
time to damage                  Exposure Temperature          Time to Failure tables are an                  oC                    oF          (minutes) intermediate                  330                 625               28 approach 350                 660               13
-to-cabinet partitions are not well
      - Still very simple but somewhat              370                  700               9 conservative              390                 735               7 Given exposure                410                 770               5 temperature, 430                 805               4 look-up tables give estimated                450                 840               3 time to damage                470                 880               2 490 (or greater)     915 (or greater)         1 17
-sealed-In a common stackof electrical cubicles
 
-In a nearby cabinet with a direct connection to the fire sourcee.g., a shared or common bus
Damage Criteria Damage time - direct response modeling (e.g., THIEF)
-duct 24Questions?}}
* See: NUREG/CR-6931 V3
* Simple one-dimensional homogeneous heat transfer model Assumes a single cable in air (or in a conduit in air)
Input is an air temperature profile Output is cable temperature vs time Assume damage when cable temperature exceeds threshold Now part of CFAST and FDS; FDTs 18
 
Thermally-Induced Electrical Failure (THIEF)
Example Cable diam                20    mm                                                            Cable diam               20     mm Mass per length          0.3    kg/m                No Conduit                                Mass per length        0.3    kg/m Jacket thickness        1.6     mm                                                            Jacket thickness       1.6    mm Conduit diameter          14    mm                                                            Conduit diameter        14    mm Conduit thickness        0      mm                        Cable Inside                        Conduit thickness        5      mm Damage temp              205      C                                                            Damage temp             205     C Ambient temp             20     C Conduit                          Ambient temp            20      C THIEF Results                                                                                THIEF Results 250                                                                                            250 200                                                                                            200 Temperature [C]
150 Temperature [C]
150 100                                                                                            100 Conduit                                                                                      Conduit Exposure                                                                                      Exposure 50                                            Surface                                        50                                            Surface Conductor                                                                                    Conductor 0                                                                                              0 0      500          1000          1500              2000                                    0      500        1000          1500              2000 Time [C]                                                                                     Time [C]
19
 
Damage Criteria Smoke Damage Appendix T provides an extended discussion of current knowledge regarding smoke damage
    - This is about smoke and the failure of equipment
    - It is not about the impact of smoke on people We are interested in short-term damage
    - Within the time scale of the fire scenario including plant shutdown
    - We do not consider longer term issues such as corrosion leading to failure some days or weeks after a fire Corresponding PRA Standard SR: FSS-D9 20
 
Damage Criteria Smoke Damage Bottom Line: Some components are known to be vulnerable to smoke damage, but it takes a dense exposure to cause short term damage So what are the vulnerable components?
    - High voltage switching equipment (arcing)
    - High voltage transmission lines (arcing)
    - Devices such as strip chart recorders that are dependent on fine mechanical motion (binding)
    - Un-protected printed circuit cards (deposition and shorting) e.g., exposed within a panel and not provided with a protective coating 21
 
Damage Criteria Smoke Damage Smoke damage is assessed on an empirical basis:
    - We dont set quantitative thresholds
    - We dont try to use fire models
    - You should consider the potential failure of vulnerable components due to smoke as a part of your damage target set 22
 
Damage Criteria Smoke Damage Assume that vulnerable components adjacent to or connected to the fire source will be damaged by smoke:
    - Within the same electrical cabinet or housing as a fire source e.g. given a panel fire, the whole panel is lost due to smoke and/or heat
    - In an adjacent cabinet if the cabinet-to-cabinet partitions are not well-sealed
    - In a common stack of electrical cubicles
    - In a nearby cabinet with a direct connection to the fire source e.g., a shared or common bus-duct 23
 
Questions?
24}}

Revision as of 19:23, 20 October 2019

Joint EPRI/NRC-RES Fire PRA Workshop - Module III - Fire Analysis -Appendix H: Damage Criteria and Damage Time
ML18213A084
Person / Time
Issue date: 07/31/2018
From: Tammie Rivera
NRC/RES/DRA/FRB, Electric Power Research Institute
To:
Shared Package
ML18213A072 List:
References
Download: ML18213A084 (24)


Text

Module III - Fire Analysis Appendix H: Damage Criteria and Damage Time Joint EPRI/NRC-RES Fire PRA Workshop August 6-10, 2018 A Collaboration of the Electric Power Research Institute (EPRI) & U.S. NRC Office of Nuclear Regulatory Research (RES)

Damage Criteria Characterizing targets A target is something other than the fire ignition source that may become involved in the fire

- Defined as a part of the fire scenario Generally there are two target types:

- Damage target: A component (or cable) that is important to plant operations that may be damaged by an exposing fire

- Secondary ignition target: Any object that is combustible and that may be ignited by an exposing fire thereby spreading the fire One object can actually be both

- e.g., the first cable tray above a fire ignition source This presentation is mainly about damage targets, but the same general approach applies to ignition targets as well 2

Damage Criteria Damage Thresholds Damage (or Failure) Threshold: the minimum value of an exposure environment parameter that can lead to the failure of the damage target of interest within the time scale of the fire

- Can be a temperature - exposure to high temperatures such as in a hot gas layer or fire plume

- Can be a radiant heat flux - generally due to direct radiant heating from the luminous flame zone of a fire

- In theory, it could be a minimum smoke density, but we arent that smart (more on smoke shortly)

Corresponding PRA Standard SRs: FSS-C5, C6 and D9 3

Damage Criteria Damage Thresholds Damage thresholds are of primary interest to Task 8 - Scoping Fire Modeling, but also play a role in Task 11 - Detailed Fire Modeling Zone-of-Influence (ZOI) - The area around a fire where radiative and convective heat transfer is sufficiently strong to damage equipment or cables and/or heat other materials to the point of ignition.

- Damage thresholds are most useful when screening out specific fire ignition sources in Task 8:

If the closest target is outside the ZOI (no damage) and fire cannot ignite any secondary combustibles, then we screen that source out of the analysis as non-threatening (more later)

- When we get to Task 11, well need damage time (more later)

Also Note: If an electrical cable is damaged, we assume that it will also be ignited. FAQ 16-0011 offers a clarification on cable tray ignition, damage and fire propagation through cable trays Based on testing experience - arcing causes piloted ignition. FAQ 16-0011 clarifies the conditions for fire propagation after ignition.

4

Damage Criteria Damage Thresholds The damage threshold is specific to the damage target based on target type and target characteristics

- What type of component?

- What are its vulnerabilities (e.g., heat, smoke, water)?

- What is the weak link relative to damage and the fire scenario?

Most fire scenarios focus on:

- Electrical cables (power, control, and instrumentation)

- Electronics and integrated circuit devices 5

Cables Classification of cables by insulation type Cable insulations fall into one of two major categories:

Thermoplastic (TP): capable of softening or fusing when heated and of hardening again when cooled (Merriam-Webster)

- TP materials melt when heated and solidify when cooled Thermoset (TS): capable of becoming permanently rigid when heated or cured (Marriam-Webster)

- On heating TS materials may soften, swell, blister, crack, smolder and/or burn but they wont melt Both types are used in U.S. NPPs

- Thermoplastic is more common in older plants, also used in non-vital applications such as lighting and communications

- Thermoset is more common in newer plants

- Practices also vary based on utility preference at the time of construction 6

Damage Criteria Cable damage thresholds The following are defined as generic damage thresholds for the most common damage targets - cables:

Radiant Heating Criteria Temperature Criteria Cable Type NUREG/CR-6850 Thermoplastic 6 kW/m2 (0.5 BTU/ft2s) 205°C (400°F)

Appendix H Thermoset 11 kW/m2 (1.0 BTU/ft2s) 330°C (625°F)

FAQ 16-0011

  • if you have case specific information, you may use alternate values if you can establish a technical basis - many specific cable types will have much higher damage thresholds if you can establish a more specific insulation type for target cables 7

Damage Criteria Sensitive Electronics Electronic devices refers mainly to control components that are based on integrated circuit type devices

- Circuit cards, amplifiers, D/A and A/D converters, signal conditioning devices, communications equipment, computers, instrument transmitters, etc.

Does not include electro-mechanical devices that lack integrated circuit elements

- Relays, switches, indicating lights, breakers, etc.

Typical damage thresholds for electronics are much lower than cables:

- 3 kW/m2 (0.25 BTU/ft2) and 65oC (150°F)

- FAQ 13-004 Treatment of Sensitive Electronics 8

Damage Criteria Sensitive Electronics FAQ 13-004 discusses an approach for treating sensitive electronics targets in fire scenarios

- Points out that there is no clear definition of what constitute sensitive electronics in NUREG/CR-6850

- Proposed treatment assumes that equipment that is sensitive to increased temperatures will be located inside electrical enclosures

- Guidance is based on FDS fire simulations 317kW transient fire located 1 m from a cabinet Radiometer located inside the cabinet to measure internal heat fluxes

- In order to reach damaging heat fluxes inside the cabinet, conditions outside the cabinet are consistent with the damage criteria for Themoset cables 9

Damage Criteria Some other specific cases Some items are considered invulnerable to fire-induced damage:

- Ferrous metal pipes and tanks

- Passive components such as flow check valves

- Concrete structural or partitioning elements except when considering random failure likelihood in multi-compartment scenarios i.e., we do not consider fire-induced structural failure of concrete Things you still need to watch for:

- Soldered piping (e.g., air/gas lines that are soldered copper)

- Flexible boots/joints/sleeves on piping (e.g., the Vandellos scenario)

- Exposed structural steel given a very large fire source (e.g.,

catastrophic loss of the main TG set - more later) 10

Damage Criteria Everything else For other devices (e.g., motors, switchgear, etc.) we typically look to either the supporting cables or controls

- A electric motor driven pump is fed by power cables, and those cables are generally more vulnerable to fire damage than the pump itself

- A switchgear is supported by both power and control cables - typically loss of the control cables means loss of functionality (no control power means breaker will not auto-cycle and cannot be remotely cycled)

- A battery charger usually contains some integrated circuit cards that control charging rate and monitor battery status

- A motor operated valve again, look at the cables 11

Damage Criteria Damage Thresholds For additional rules related to damage criteria, see H.1.1; e.g.:

- Cables in conduit: potential damage targets, but will not contribute to fire growth and spread - no credit to conduit for delaying the onset of thermal damage.

- Cables coated by a fire-retardant coating: treat as exposed cables for damage purposes - coating may slow the subsequent spread of fire, but we are NOT specific here.

12

Damage Criteria Damage Thresholds Plant-specific or product-specific damage thresholds may be used if appropriate basis is established

- NUREG/CR-6850 provides some references for information specific to many popular types and brands of cables

- Example:

13

Damage Criteria Damage Time It is both appropriate and desirable to consider, not just the possibility of damage, but also the time before damage occurs

- This is part of Task 11 - Detailed Fire Modeling It takes time to heat a target to its damage temperature

- If the air temperature (or heat flux) equals the damage threshold, damage times may be prolonged (e.g., 30-60 minutes or more)

- As exposure conditions become more severe, time to damage decreases (e.g., if immersed in flames, may be a few seconds)

A damage time gives us a hook to credit fire intervention:

- It tells you how long you have to put the fire and prevent damage

- We can then ask what is the probability that given the fire, it will be put out before damage occurs?

- More details on that process later in the week, but for now well talk a little about estimating damage time 14

Damage Criteria Damage time - three common approaches Predict when a fire grows large enough to create damaging environment at the target location (generally most conservative)

Empirical approach (intermediate approach, e.g., SDP*)

- Predict the peak exposure condition (temperature or heat flux)

- Use a look-up table to estimate time to damage

- Catch: look-up tables currently only available for generic thermoset and thermoplastic cables Direct modeling of target thermal response based on fire environment (generally most realistic)

- Use a fire model to predict the temperature response of the target

- When the predicted temperature of the target reaches the damage threshold, assume target failure

- Catch: need fire model that does target response calculation

- Simplest example: THIEF model for cables (more later)

Damage Criteria Damage time - time to threshold One simple approach is to assume damage occurs when the conditions at the target location first reach the damage threshold

- Generally gives the most conservative answer of the three approaches

  • If you can characterize fire growth versus time, then you can use that to predict the fire environment over time even using simple correlations that are based on fire heat release rate

- Plume temperature correlation

- Radiant heating correlation

- Steady state hot gas layer temperature correlation If you are in a hot gas layer situation, you can predict transient temperature profile using a fire model like CFAST or MAGIC

- Wont help much unless you have a transient fire growth profile because HGL develops to steady state very quickly in these models 16

Damage Criteria Damage time - the look-up tables Table H-5: Failure Time-Temperature Relationship for The empirical Thermoset cables (Table A.7.1 from reference H.6).

time to damage Exposure Temperature Time to Failure tables are an oC oF (minutes) intermediate 330 625 28 approach 350 660 13

- Still very simple but somewhat 370 700 9 conservative 390 735 7 Given exposure 410 770 5 temperature, 430 805 4 look-up tables give estimated 450 840 3 time to damage 470 880 2 490 (or greater) 915 (or greater) 1 17

Damage Criteria Damage time - direct response modeling (e.g., THIEF)

  • Simple one-dimensional homogeneous heat transfer model Assumes a single cable in air (or in a conduit in air)

Input is an air temperature profile Output is cable temperature vs time Assume damage when cable temperature exceeds threshold Now part of CFAST and FDS; FDTs 18

Thermally-Induced Electrical Failure (THIEF)

Example Cable diam 20 mm Cable diam 20 mm Mass per length 0.3 kg/m No Conduit Mass per length 0.3 kg/m Jacket thickness 1.6 mm Jacket thickness 1.6 mm Conduit diameter 14 mm Conduit diameter 14 mm Conduit thickness 0 mm Cable Inside Conduit thickness 5 mm Damage temp 205 C Damage temp 205 C Ambient temp 20 C Conduit Ambient temp 20 C THIEF Results THIEF Results 250 250 200 200 Temperature [C]

150 Temperature [C]

150 100 100 Conduit Conduit Exposure Exposure 50 Surface 50 Surface Conductor Conductor 0 0 0 500 1000 1500 2000 0 500 1000 1500 2000 Time [C] Time [C]

19

Damage Criteria Smoke Damage Appendix T provides an extended discussion of current knowledge regarding smoke damage

- This is about smoke and the failure of equipment

- It is not about the impact of smoke on people We are interested in short-term damage

- Within the time scale of the fire scenario including plant shutdown

- We do not consider longer term issues such as corrosion leading to failure some days or weeks after a fire Corresponding PRA Standard SR: FSS-D9 20

Damage Criteria Smoke Damage Bottom Line: Some components are known to be vulnerable to smoke damage, but it takes a dense exposure to cause short term damage So what are the vulnerable components?

- High voltage switching equipment (arcing)

- High voltage transmission lines (arcing)

- Devices such as strip chart recorders that are dependent on fine mechanical motion (binding)

- Un-protected printed circuit cards (deposition and shorting) e.g., exposed within a panel and not provided with a protective coating 21

Damage Criteria Smoke Damage Smoke damage is assessed on an empirical basis:

- We dont set quantitative thresholds

- We dont try to use fire models

- You should consider the potential failure of vulnerable components due to smoke as a part of your damage target set 22

Damage Criteria Smoke Damage Assume that vulnerable components adjacent to or connected to the fire source will be damaged by smoke:

- Within the same electrical cabinet or housing as a fire source e.g. given a panel fire, the whole panel is lost due to smoke and/or heat

- In an adjacent cabinet if the cabinet-to-cabinet partitions are not well-sealed

- In a common stack of electrical cubicles

- In a nearby cabinet with a direct connection to the fire source e.g., a shared or common bus-duct 23

Questions?