2018 Joint EPRI/NRC-RES Fire PRA Workshop, Module III - Fire Analysis Page 1 Task Number Task Title Updates Summary Task 1 Plant Boundary Definition and Partitioning No updates since NUREG/CR-6850 Task 6 Fire Ignition Frequencies Supplement 1 to NUREG/CR-6850 (EPRI 1019259):
Published in 2010 FAQ 06-0016-Counting guidance for electrical cabinets FAQ 06-0017-Counting guidance for high energy arcing faults FAQ 06-0018-Counting guidance for main control board FAQ 07-0031-Miscellaneous counting guidance clarifications FAQ 07-0035-Counting guidance for high energy arcing faults on bus ducts FAQ 08-0042-Propagation of fires from electrical cabinets/Well sealed panels FAQ 08-0048-Generic fire ignition frequencies Additional FAQs:
FAQ 13-0005-Counting and modeling of SICF and CFW FAQ 13-0005-Counting and modeling of Junction Boxes FAQ 14-0008-Clarification on counting the main control board FAQ 12-0064-Influence factors for transient and hotwork fires NUREG-2169 / EPRI 3002002936:
Published in 2014 New generic frequencies
2018 Joint EPRI/NRC-RES Fire PRA Workshop, Module III - Fire Analysis Page 2 Task Number Task Title Updates Summary Task 8 Scoping Fire Modeling Supplement 1 to NUREG/CR-6850 (EPRI 1019259):
Published in 2010 FAQ 08-0043-Location of fires within electrical cabinets FAQ 08-0044-Main feed water pump oil spills Additional FAQs:
FAQ 14-0009-Treatment of well-sealed MCCs NRR Closure Memo June 21, 2012, ML12171A583 New severity factors for pump/oil fires NUREG-2178 / EPRI 3002005578 New heat release rate probability distributions for electrical cabinets Obstructed plume NUREG/CR-7102 Kerite Analysis in Thermal Environment of FIRE
2018 Joint EPRI/NRC-RES Fire PRA Workshop, Module III - Fire Analysis Page 3 Task Number Task Title Updates Summary Task 11a Detailed Fire Modeling/Single Compartment Analysis Supplement 1 to NUREG/CR-6850 (EPRI 1019259):
Published in 2010 FAQ 07-0035-Zone of influence for high energy arcing faults on bus ducts FAQ 08-0042-Propagation of fires from electrical cabinets/Well sealed panels FAQ 08-0043-Location of fires within electrical cabinets FAQ 08-0049-Cable tray fire propagation FAQ 08-0046-Incipient fire detection system FAQ 08-0050- Manual suppression probabilities FAQ 08-0050- Transient fire heat release rate growth profile Additional FAQs:
FAQ 13-0004-Modeling treatment for sensitive electronics FAQ 13-0005-Counting and modeling of SICF and CFW FAQ 13-0006-Counting and modeling of Junction Boxes FAQ 14-0009-Treatment of well-sealed MCCs FAQ 14-007-Transient Fire Frequency Likelihood FAQ 16-0011-Cable tray ignition FAQ 17-0013-HEAF non-suppression probabilities NUREG & EPRI Publications NUREG 1805 Supplement 1 (2013)
NUREG/CR-7010 Vol 1, FLASH-CAT Model for cable fire HRR (2012)
NUREG/CR-6931, Vol. 3, THIEF Model for cable heating (2007)
NUREG 1934 / EPRI 1023259 - Fire Modeling Users Guide (2012)
NUREG 1824 / EPRI 1011999 - Fire Modeling Verification and Validation (2007)
NUREG 1824 Supplement 1 / EPRI 3002002182 - Fire Modeling Verification and Validation (2016)
EPRI 3002000830 - FIVE Rev 2 (2014), Updated & new spreadsheets NUREG-2169 / EPRI 3002002936 (2014), New manual suppression probability curves
2018 Joint EPRI/NRC-RES Fire PRA Workshop, Module III - Fire Analysis Page 4 Task Number Task Title Updates Summary NUREG-2178 / EPRI 3002005578, RACHELLE FIRE New heat release rate probability distributions for electrical cabinets and treatment for obstructed fire plumes NUREG/CR-7197, HELEN FIRE, Electrical cabinet heat release rate tests NUREG-2180, DELORES FIRE Treatment of incipient detection systems Task 11b Detailed Fire Modeling/Main Control Room Analysis No updates since NUREG/CR-6850 on the fire modeling guidance.
NUREG 1921 Supplement 1, EPRI 3002009215 EPRI/NRC-RES Fire Human Reliability Analysis Guidelines: Qualitative Analysis for Main Control Room Abandonment Ongoing research on modeling control room abandonment scenarios from human reliability/plant response model perspective.
Task 11c Detailed Fire Modeling/Multi Compartment Analysis No updates since NUREG/CR-6850 Task 13 Seismic Fires Interactions Assessment No updates since NUREG/CR-6850 Tasks 1, 6, 8, 11, 13 ASME/ANS RA-Sa-2009 Fire PRA Standard