| number = ML20211N907
| issue date = 06/25/1986
| title = Insp Rept 50-482/86-14 on 860512-16.Deviation Noted:Failure to Have Qualification Summaries & Environ Evaluation Worksheets for Vulkene Supreme Wiring & Kulka Terminal Blocks Used in Harsh Environ
| author name = Ireland R, Norman D
| author affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
| addressee name =
| addressee affiliation =
| docket = 05000482
| license number =
| contact person =
| document report number = 50-482-86-14, IEIN-83-72, IEIN-86-003, IEIN-86-3, NUDOCS 8607110076
| package number = ML20211N885
| document type = INSPECTION REPORT, NRC-GENERATED, INSPECTION REPORT, UTILITY, TEXT-INSPECTION & AUDIT & I&E CIRCULARS
| page count = 7
}}
See also: [[see also::IR 05000482/1986014]]
 
=Text=
{{#Wiki_filter:.                    - . ,                                      - _ _ - .      .      .    - - - -                              -              .            -      .. - - - . - -
!
                        *
      .
        '
.
f
                                                                                                  APPENDIX B
                                                                                      U.S. NUCLEAR REGULATORY COMMISSION
                                                                                                      REGION IV
'
                          NRC Inspection Report:                                        50-482/86-14                                            License:            NPF-42
:
,
                          Docket:                      50-482
'
                          Licensee:                          Kansas Gas and Electric Company
,
                                                              P. O. Box 208
3
                                                            Wichita, Kansas 67201
!
!                        Facility Name: Wolf Creek Generating Station                                                                                                                        !
                          Inspection At:                                      Burlington, Kansas
                          Inspection Conducted: May 12-16, 1986
  i
i
                          Inspector                                              A 24 m ?~ A
                                                                                          _
                                                                                                                                                                      4/-2f/fd                i
j                                                                          D. E. Norman, React'or Inspector, Engineering                                              Date
                                                                                Section, Reactor Safety Branch
                                                              '
i
j                                                                                                                                                                                          l
i
!
  I
f
'
                          Approved:                                        M2Y M- - ~'- #                                                                            4/-P.r/N
:                                                                          R. E. Ireland, Chief Engineering Section,                                                  Date
j                                                                          Reactor Safety Branch
.
l                        Inspection Summary
j                        Inspection Conducted May 12-16, 1986 (Report 50-482/86-14)
.
                          Areas Inspected:                                        Special, announced inspection to determine what wiring is                                                i
  i
  '
                          installed in Limitorque operators and to review licensee's environmental
                          documentation to ensure that qualification of wiring is adequately established.                                                                                  i
i                        The inspection also included a review of the licensee's actions relative to                                                                                      ;
                          Information Notices (IN) 83-72 and 86-03.
!                        Results: The inspection determined that Limitorque operators, which had                                                                                          ;
i
                          previously been reported to be qualified by Limitorque or Westinghouse,
1                        contained internal wiring and/or terminal blocks which could not be shown to be
-
.                        qualified-to the requirements of 10 CFR 50.49. The licensee had inspected most                                                                                    !
I                        of the Limitorque operators, and in response to IN 83-72 and IN 86-03 had
i                        replaced unqualified wiring and terminal blocks in several operators. However,                                                                                    l
                          44 operators qualified by the NSSS had apparently not been inspected. Wiring
  '
                                                                                                                                                                                            i
  i                                                                                                                                                                                        ,
                                                                                      '
l
,  8607110076 860708                                                                                                                                                                      [
  1  PDR              ADOCK 05000482
    G                                                        PDR
      _ , . , , . _ _ _ _ . _ . _ . . _ _ _ _ _ _ , _ _ _ _ , _ _ . _ _ _ .                                . - _ _ _ _ _ . _ _ _ _ . _ , _ _ _ _ . ~ . _ . _ . - _ -
 
                                                                                                      . _ - -
    *
  .
                                                2
      which appears to be unqualified was found in one of those operators during this
      inspection. Also, the licensee had identified several operators with
      unidentified wire or terminal blocks, and no apparent corrective action had
      been taken to assure that these items were qualified.
!
!
l
I
:
!
1
'
                                                                                                                l
,
                          , - - - ---w -- .. , -  -      - - - .  - - - . - - - - - - - , - - , - - ,    -  -
 
  *
.
                                            3
                                        DETAILS
                              '
    1.  Persons Contacted
        Kansas' Gas and Electric
      *C.  J. Hoch, Q.A. Technician
        W. M. Lindsay, Supervisor, Quality Systems
      *M. G. Williams, Superintendent, Reg. and Adm.
        N. Hoadley, Lead Engineer, NPE
        D. Walsh, Supervisor, Maintenance Services
        D. Glogowski, Maintenance Engineer
      *C. J. Pendergrass, Licensing Engineer
      *K. Petersen, Lead Engineer, Licensing
        J. A. Zell, Manager, Nuclear Training
      *F. T. Rhodes, Plant Manager
      *J. Goode, Licensing Engineer
        D. Rich, Superintendent, Maintenance
        R. L. Hoyt, Senior Engineering Specialist
        J. L. Houghton, Operations Coordinator
      *R. M. Grant, Director, Quality
      *A. A. Freitag, Manager, NPE
      *W. J. Rudolph, Manager, QA
      *0. L. Maynard, Manager, Licensing
      *D. R. Prichard, Engineer, NPC
      *J. A. Bailey, Director, Engineering and Tech Services
      *G.  D. Boyer, Superintendent, Technical Support
        Bechtel
        C. E. Jeniks, Acting Lead, Electrical
        NRC
        J. E. Gagliardo, Chief, Reactor Projects Branch
      *J. E. Cummins, Senior Resident Inspector
      *B. L. Bartlett, Resident Inspector
      *D. E. Norman, Reactor Inspector
      * Denotes those present during exit interview on May 16, 1986.
    2.  Purpose
        The purpose of this inspection was to identify wiring used in Limitorque
        valve operators installed in a harsh environment, to review the licensee's
        environmental qualification documentation to ensure that qualification of
        wiring was adequately established, and to review the licensee's actions
        relative to IN 83-72 and IN 86-03.
 
                                                                            --      - _ _ _ _ _ - _ _ _ _ _ _ _ _ _ -
    .
      *
  .
                                              4
      3. Inspection Summary
          a.  Review of Previous Licensee Actions
              Approximately 114 Limitorque operators are installed in a harsh
              environment at Wolf Creek. Because of reported qualification
              problems concerning the operators, the licensee performed inspections
,
              in July 1984, which identified problems in wiring, terminal blocks,
              limit switches and mounting orientation for the operators. During
              the licensee's inspection, all 11 operators covered by M-225
              specification were found to have unidentified wires. The wires were
                                                        w
              subsequently)      replaced
              Requests (WR 90306-85        with90316-85.
                                        through    qualifiedThe
                                                              ' ires in accordance
                                                                  operators  were model with Work
              number SMB with serial numbers ranging from 238481 to 290374.
              Unidentified wires were also found in operator KAHV-0030 (S/N 321295,
              Spec. No. 231C, Model SMB.) and there was no documentation to show
';
              that the wires were changed or determined to be qualified. This is a
              potential violation of 10 CFR 50.49. (482/8614-01)
              The licensee inspection also revealed that several types of terminal
              blocks were being used in Limitorque operators. In addition to the
              terminal blocks, for which qualification data was available (Marathon
              300/1600, Buchanan 0222/0524, GE EB-5 and Curtis Type "L"), Kulka
              blocks were found and some others were not identif;able. There was
              no documentation to show that the unidentified terminal blocks were
              changed or determined to be qualified. This is a potential violation
              of 10 CFR 50.49.    (482/8614-02.) The Kulka tenninal blocks are
              discussed later in this report.
              The licensee had also identified unqualified limit switches found
              during their inspection. This information will be reviewed by NRC
              during a subsequent inspection (open item 482/8614-03).
          b.  Hardware Inspection
              (1) Sample Selection
                    The master list of safety-related equipment located in a harsh
                    environment was reviewed and a sample of 10 operators was
                    selected to be inspected. Selection of the sample was based on
                    the 1ollowing criteria:    (a) operators from several safety
                    systems, (b) range of Limitorque serial numbers, (c) at least
                    one operator previously inspected by the licensee, (d) operators
                    qualified by both Limitorque and the NSSS contractor, and
                      (e) operators located outside high radiation areas.
                          -    -
 
                                    -        -.                  .
      *
  .
                                                5
.
,
                    The following operators were included in the sample:
                    *a.  EMHV-8802A(S/N216087)
                    *b.  EJHV-8809A (S/N 200677)
                      c.  ENHV-0006 (S/N 238482
:                      d.  LFHV-106    (S/N 256091
                      e.  EGHV-127    (S/N260401
                      f.  EGHV-061    (S/N 271908
-
                      9  EFliV-31    (S/N286123)
                      h.  EFHV-47    (S/N315153)
4                      1.  EGHV-133    (S/N321898)
                    *j.  BGHV-8105 (S/N 247314)
                    *apparently not inspected by licensee.
                (2) Findings
                    Each operator was inspected to establish the type of internal
                    wiring. Most longer wires could be identified by wiring
,                    manufacturer markings; however, many short wires did not have
i                    markings and were identified by visual comparison to previously
;                    identified wires. Nine of the operators had a combination of
                    Rockbestos Firewall III, Raychem Flamtrol, or Vulkene Supreme
                    wiring. Most of the wires in operator EJHV-8809A were colored
                    blue and were marked "Techbestos."
                    Field wiring which interfaced with the operators was also
                    inspected. All wires appeared to be of the same type; however,
                    specific identification could not be made at this interface,
                    since the jariet material which contained the markings was not
,
                    visible.
!
            c. Documentation Review
                (1) Equipment Qualification Cover Sheet
                    Each operator specification numba h.s an EQ cover sheet,
                    Equipment Evaluation Workshent (~E9) and a summary of
                    qualification details, such ar; 100 . iption of equipment-
                    qualified, specified and 'quah rleu u,vironment, qualification
                    method, qualified life, and reports used to establish-
                    qualification. The description of qualified equipment includes
                    such items as motor type, and terminal block type. During the
                    licensee walkdown inspections, certain wiring and terminal
                    blocks were identified (i.e., Vulkene Supreme wiring and Kukla
                    terminal blocks) which were neither' discussed nor referenced in
                    the qualification documentation. Therefore, no trail exists for
                    making a' determination of the qualification status of these
                    items. This is an apparent deviation from the EQ program plan
    -  . -    .      -                -          -            -              - - - -
 
            . .                .                .                            .        . .                -                                      - - -
                                          . ,
    . .'    *
    .
                                                                              6
                                                                                                                ;
'
                            described in the " Environmental Description of Safety Related
                            Electrical Equipment" submitted by letter dated January 17,
                            1986.      (482/8614-04)
                    (2) Cable Pull Cards
                            Cable pull cards for field cable interfacing with operators
                            EMHV-8802A and EGHV-127 were reviewed to establish cable
I                          identity.          Cables _ identified were Rockbestos 600V control cable,
                            and Anaconda low voltage power cable. Qualification of these
                            cables is reported in test reports E-057-020-03 and
                            E058-005-030, respectively.
                    (3) Vendor Qualification Reports
                            Vendor and/or test lab qualification test reports for wiring and
                            terminal blocks included in the operators were reviewed.                                                  The
                            following discrepancies were identified as a result of this                                                                          -
1
                            review:
                            (a) There was no qualification test report available for G.E.
                                    Vulkene Supreme wire which was installed in some operators.
                                    The basis for qualification was a G.E. Product Data
                                    Pamphlet dated June 30, 1977, which states that the wiring
                                    is qualified to IEEE Stds. 323-74 and 383-74 and which
                                    presents certain qualification data.                                    The data presented is
                                    stated to be subject to change without notice. Therefore,
                                    there is no basis for demonstrating qualification of the
                                    Vulkene wiring to the requirements of 10 CFR 50.49. This.
                                    is a potential violation of110 CFR 50.49. (482/8614-05)
                            (b) There was no qualification test report or basis for
'
                                    determining qualification of Techbestos wire which was
                                    identified during this inspection. This failure te
                                    demonstrate qualification is a potential violation of
                                    10 CFR 50.49.                (482/8614-06)                ;
                            (c)      It was stated previously in this report that there was no
                                    audit trail for Kulka terminal blocks in the Limitorque
                                    operator qualification documentation, even though these
'
i                                  terminal blocks had been identified by the licensee. The
                                    basis of qualification of the terminal blocks was stated by
                                    the licensee to be the " Design Qualification Report for
                                    Feedthrough/ Adapters Model assemblies ISP-719," dated
                          ,        October 4, 1983. In'this report, Kukla 602 series terminal
                                  . blocks _were qualified as a part of the electrical
                              '
                                  . penetrations.              There was no documentation to show that the
                                    terminal blocks were' identical to or~ similar to those
  l                                  identified in Limitorque operators, nor had an analysis
  I                                  been performed to predict qualified life in the operator
I
                      .,
                                            .
T
      - - -    -- --        .-,          ,        _ , . , _ _ _ . . - - , ,    ,,,,.,y .,  -,,,._,.,.,,o          e ,,,,,,,,~.,..__.-4,.--yy..,.      - . -
 
                    -                                  .      .
  *
.                                                                          .
                                            7                                        ,
                      environment.    This failure to demonstrate qualification is
                      a potential violation of 10 CFR 50.49.    (482/8614-07)
    4. Exit Meeting
      An exit meeting was held on May 16, 1986, with the persons identified in
      paragraph 1 during which time results of the inspection were discussed.
            .
                  -                          -                          .--    -  -
}}