ML20072S370: Difference between revisions
StriderTol (talk | contribs) (StriderTol Bot change) |
StriderTol (talk | contribs) (StriderTol Bot change) |
||
| Line 17: | Line 17: | ||
=Text= | =Text= | ||
{{#Wiki_filter:. | {{#Wiki_filter:. | ||
bW | |||
[ M3Q.,91 L Carolina _ Power & Light Company MD | [ M3Q | ||
.,91 L Carolina _ Power & Light Company MD 4'.L__ _ _ ma - w m MI Brunswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461-0429 | |||
Atlanta, GA | -March 28,-1983 FILE: B09-13510C SERIAL: BSEP/83-987 Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Commission Region II, Suite 3100 101 Marietta Street N.W. | ||
Atlanta, GA 30303 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NO. 2 4 | |||
DOCATT NO. 50-324 LICENSE NO. DPR-62 SPECIAL REPORT PER TECHNICAL SPECIFICATION 3.7.8 | |||
==Dear Mr.!O'Reilly:== | ==Dear Mr.!O'Reilly:== | ||
During Unit No._2 power operation--two fire barrier LCOs with respective | During Unit No._2 power operation--two fire barrier LCOs with respective | ||
: issuance dates of March 7 and 8, 1983, were generated on two Control Building fire doors. One of the doors, No. 210, was declared inoperable due to a problem with the door self-closing device. The other door, No. 303, was declared inoperable because of encountered high differential air pressure across the door which prevents automatic self-closure. The door self-closing device of door No. 210 was repaired; however, postmaintenance testing of the | : issuance dates of March 7 and 8, 1983, were generated on two Control Building fire doors. One of the doors, No. 210, was declared inoperable due to a problem with the door self-closing device. The other door, No. 303, was declared inoperable because of encountered high differential air pressure across the door which prevents automatic self-closure. The door self-closing device of door No. 210 was repaired; however, postmaintenance testing of the r | ||
As a result of this event,. plant Engineering has been requested to evaluate the subject. differential air pressure problem. Until-the return of the two | door revealed it would not self-close as a result.of the encountered high differential air pressure across the door as. experienced with door No. 303. | ||
r-As a result of this event,. plant Engineering has been requested to evaluate the subject. differential air pressure problem. | |||
Very truly yours, b Wy C. R. Dietz, General Manager Brunswick Steam Electric Plant RMP/dj/LETDJ4 Enclosure L | Until-the return of the two | ||
~ doors to operability and cancellation of the LCOs, appropriate stationed fire watches at these doors will remain in effect. | |||
Very truly yours, b Wy C. R. Dietz, General Manager Brunswick Steam Electric Plant RMP/dj/LETDJ4 Enclosure L | |||
cc: | |||
Mr. R. C. DeYoung NRC Document Control Desic. | |||
. OFFICIAL COPY l-8 9304070145 830328 PDR:ADOCK 05000324 S | |||
PDR__ | |||
.}} | |||
Latest revision as of 04:22, 15 December 2024
| ML20072S370 | |
| Person / Time | |
|---|---|
| Site: | Brunswick |
| Issue date: | 03/28/1983 |
| From: | Dietz C CAROLINA POWER & LIGHT CO. |
| To: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| References | |
| BSEP-83-987, NUDOCS 8304070145 | |
| Download: ML20072S370 (1) | |
Text
.
bW
[ M3Q
.,91 L Carolina _ Power & Light Company MD 4'.L__ _ _ ma - w m MI Brunswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461-0429
-March 28,-1983 FILE: B09-13510C SERIAL: BSEP/83-987 Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Commission Region II, Suite 3100 101 Marietta Street N.W.
Atlanta, GA 30303 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NO. 2 4
DOCATT NO. 50-324 LICENSE NO. DPR-62 SPECIAL REPORT PER TECHNICAL SPECIFICATION 3.7.8
Dear Mr.!O'Reilly:
During Unit No._2 power operation--two fire barrier LCOs with respective
- issuance dates of March 7 and 8, 1983, were generated on two Control Building fire doors. One of the doors, No. 210, was declared inoperable due to a problem with the door self-closing device. The other door, No. 303, was declared inoperable because of encountered high differential air pressure across the door which prevents automatic self-closure. The door self-closing device of door No. 210 was repaired; however, postmaintenance testing of the r
door revealed it would not self-close as a result.of the encountered high differential air pressure across the door as. experienced with door No. 303.
r-As a result of this event,. plant Engineering has been requested to evaluate the subject. differential air pressure problem.
Until-the return of the two
~ doors to operability and cancellation of the LCOs, appropriate stationed fire watches at these doors will remain in effect.
Very truly yours, b Wy C. R. Dietz, General Manager Brunswick Steam Electric Plant RMP/dj/LETDJ4 Enclosure L
cc:
Mr. R. C. DeYoung NRC Document Control Desic.
. OFFICIAL COPY l-8 9304070145 830328 PDR:ADOCK 05000324 S
PDR__
.