ML20085D077: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot change)
(StriderTol Bot change)
 
Line 17: Line 17:


=Text=
=Text=
{{#Wiki_filter:I fnarosr4       3 MGMWSHB ' VSH                     Wg Q                 4                           *
{{#Wiki_filter:I fnarosr4 3
        $$$*SShE''ES's SUSPECTED DUPLICATE "7'   73 mestern union u v C U 2-OF0F87E191 ICS IPMMTZZ CSP Q IM             i -.x j   *******
MGMWSHB ' VSH Wg Q 4
9
$$$*SShE''ES's "7'
    . 8'033321351 MGM TDMT HARTSVILLE S 152 07-10 0340P EST l
mestern union u v C UQ IM i -.x j 73 9
ZIP 20545                                                                                             0 50-261 C                                                                       c}                       'b       3 7           ,
SUSPECTED DUPLICATE 2-OF0F87E191 ICS IPMMTZZ CSP 8'033321351 MGM TDMT HARTSVILLE S 152 07-10 0340P EST ZIP 20545 0
JOHN F OLEARY                                                           I DIRECTORATE OF LICENSING USAEC                                 ll   gJ-              -
l 50-261 C
                                                                                                  ')   .A C     WASHINGTON DC 20545                                           -
c}
JUL131973>                   -
'b 3
                                                                                                              )
7 JOHN F OLEARY I
h    E.S. AT07.*.1C EllIR"Y
DIRECTORATE OF LICENSING USAEC ll gJ-
                                                                                                        }
')
('                                                                               $la$                       3 g      Nd se:uca CD         -4 IN ACCORDANCE WITH SECTION 6.6.2 0F THE TECHNICAL SPECIFICATIONS THE FOLLOVING ABNORMAL OCCURRENCE IS REPORTED AT 0830 ON JULY C     10 WHILE ROUTINELY PUTTING' CONTAINMENT FOR COOLER NUMBER TWO                                         O IN SERVICE, THE CIRCUIT BREAKER FOR THIS FAN TRIPPED. I NVESTIGATI ON
.A C
: t.      REVEALED THAT THE TRIP WAS INITIATED BY INSTANTANEOUSLY OVER I b     OCCURRENCE CAUSED BY THE MISALIGNMENT OF THE INSTANTANEOUSLY                                         O CALIBRATION SPRING IN THE OVER CURRENT TRIP DEVICE. THE DEVICE WAS REMOVED, THE SPRING REALIGNED AND THE COOLING UNIT PUT IN                                         '
WASHINGTON DC 20545
L. SERVICE SATISFACTORILY AT 1007. TO PREVENT THE RECURRENCE OF THIS TRIP, ALL NEWLY INSTALLED TRIP DEVICES ARE BEING VISUALLY
)
  -.. INSPECTED FOR PROPER SPRING ALIGNMENT. THIS UNIT HAD OPERATED L     SATISFACTORILY FOLLOWING THE INSTALLATION OF THE NEY TRIP DEVICE.                                       '
h JUL131973>
}
E.S. AT07.*.1C EllIR"Y
('
$la$
3 Nd se:uca g
CD
-4 IN ACCORDANCE WITH SECTION 6.6.2 0F THE TECHNICAL SPECIFICATIONS THE FOLLOVING ABNORMAL OCCURRENCE IS REPORTED AT 0830 ON JULY C
10 WHILE ROUTINELY PUTTING' CONTAINMENT FOR COOLER NUMBER TWO O
IN SERVICE, THE CIRCUIT BREAKER FOR THIS FAN TRIPPED. I NVESTIGATI ON REVEALED THAT THE TRIP WAS INITIATED BY INSTANTANEOUSLY OVER t.b OCCURRENCE CAUSED BY THE MISALIGNMENT OF THE INSTANTANEOUSLY O
I CALIBRATION SPRING IN THE OVER CURRENT TRIP DEVICE. THE DEVICE L.
WAS REMOVED, THE SPRING REALIGNED AND THE COOLING UNIT PUT IN SERVICE SATISFACTORILY AT 1007. TO PREVENT THE RECURRENCE OF THIS TRIP, ALL NEWLY INSTALLED TRIP DEVICES ARE BEING VISUALLY INSPECTED FOR PROPER SPRING ALIGNMENT. THIS UNIT HAD OPERATED L
SATISFACTORILY FOLLOWING THE INSTALLATION OF THE NEY TRIP DEVICE.
THIS WAS REPORTED TO MR HERB WHITTNER IN PERSON ON JULY 10, 1973.
THIS WAS REPORTED TO MR HERB WHITTNER IN PERSON ON JULY 10, 1973.
: l.       BENNY J FURR MANAGER H B ROBIt130N SEG PLANT PO BOX 790 HARTSVILLE                                 O SC 29550 l     2041 EST                                                                                             O MGMVSHB WSH lC                                                                                                           e lC                                                                                                           O C                                                                                                          O 2 p.lf (ri 1                                                                   -
l.
lc
BENNY J FURR MANAGER H B ROBIt130N SEG PLANT PO BOX 790 HARTSVILLE O
                                                                                                            -o
SC 29550 l
:D lC
2041 EST O
                                                      >                    5438                             a 8307200324 730717 PDR ADDCK 05000261 PDR g       S
MGMVSHB WSH lC e
                                                                                      -4 COPY SENT RPGTON                       ~
lC O
t                                                                                                             O}}
p.lf (ri C
O 1
2 lc
-o
:D lC 5438 a
8307200324 730717 PDR ADDCK 05000261 S
PDR g
-4 COPY SENT RPGTON
~
t O}}

Latest revision as of 03:45, 14 December 2024

Telecopy Ao:On 730710,circuit Breaker for Containment Cooler Fan 2 Tripped.Caused by Overcurrent Due to Misalignment of Calibr Spring in Overcurrent Trip Device.Spring Realigned
ML20085D077
Person / Time
Site: Robinson Duke Energy icon.png
Issue date: 07/10/1973
From: Furr B
CAROLINA POWER & LIGHT CO.
To: Oleary J
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML20085D064 List:
References
NUDOCS 8307200324
Download: ML20085D077 (1)


Text

I fnarosr4 3

MGMWSHB ' VSH Wg Q 4

$$$*SShEES's "7'

mestern union u v C UQ IM i -.x j 73 9

SUSPECTED DUPLICATE 2-OF0F87E191 ICS IPMMTZZ CSP 8'033321351 MGM TDMT HARTSVILLE S 152 07-10 0340P EST ZIP 20545 0

l 50-261 C

c}

'b 3

7 JOHN F OLEARY I

DIRECTORATE OF LICENSING USAEC ll gJ-

')

.A C

WASHINGTON DC 20545

)

h JUL131973>

}

E.S. AT07.*.1C EllIR"Y

('

$la$

3 Nd se:uca g

CD

-4 IN ACCORDANCE WITH SECTION 6.6.2 0F THE TECHNICAL SPECIFICATIONS THE FOLLOVING ABNORMAL OCCURRENCE IS REPORTED AT 0830 ON JULY C

10 WHILE ROUTINELY PUTTING' CONTAINMENT FOR COOLER NUMBER TWO O

IN SERVICE, THE CIRCUIT BREAKER FOR THIS FAN TRIPPED. I NVESTIGATI ON REVEALED THAT THE TRIP WAS INITIATED BY INSTANTANEOUSLY OVER t.b OCCURRENCE CAUSED BY THE MISALIGNMENT OF THE INSTANTANEOUSLY O

I CALIBRATION SPRING IN THE OVER CURRENT TRIP DEVICE. THE DEVICE L.

WAS REMOVED, THE SPRING REALIGNED AND THE COOLING UNIT PUT IN SERVICE SATISFACTORILY AT 1007. TO PREVENT THE RECURRENCE OF THIS TRIP, ALL NEWLY INSTALLED TRIP DEVICES ARE BEING VISUALLY INSPECTED FOR PROPER SPRING ALIGNMENT. THIS UNIT HAD OPERATED L

SATISFACTORILY FOLLOWING THE INSTALLATION OF THE NEY TRIP DEVICE.

THIS WAS REPORTED TO MR HERB WHITTNER IN PERSON ON JULY 10, 1973.

l.

BENNY J FURR MANAGER H B ROBIt130N SEG PLANT PO BOX 790 HARTSVILLE O

SC 29550 l

2041 EST O

MGMVSHB WSH lC e

lC O

p.lf (ri C

O 1

2 lc

-o

D lC 5438 a

8307200324 730717 PDR ADDCK 05000261 S

PDR g

-4 COPY SENT RPGTON

~

t O