- ...__ ___-.__- _ - - - -- - _ _ -- -.-.---- _ _ --.----_-. _ _-..__ _ _ - - -____---- ---.-___ --__.___.---._--- -_- -.-_-_._.-_-__ _-___-- - -_._..-_..__-__a}} | - ...__ ___-.__- _ - - - -- - _ _ -- -.-.---- _ _ --.----_-. _ _-..__ _ _ - - -____---- ---.-___ --__.___.---._--- -_- -.-_-_._.-_-__ _-___-- - -_._..-_..__-__a}} | ||
Revision as of 17:51, 17 February 2020
| ML20004E483 | |
| Person / Time | |
|---|---|
| Site: | Palisades |
| Issue date: | 06/02/1981 |
| From: | Peterson D CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.) |
| To: | |
| Shared Package | |
| ML20004E479 | List: |
| References | |
| NUDOCS 8106120249 | |
| Download: ML20004E483 (4) | |
Text
.
OPERATING DATA REPORT DOCKET NO. 50-255 DATE e-2-01 COMPLETED BY DAPeterson TELEPHONE c16 764-8913 OPERATING STATUS
- 1. Unit Name: Pslisades N tes
- 2. Reporting Period: 810501-810531
- 3. Licensed Thermal Power (MWt): 2530
- 4. Nameplate Rating (Gross MWe): 011*I S. Design Electrical Rating (Net MWe): 805
- 6. Maximum Dependable Capacity (Gross MWe): *675
- 7. Maximum Dependsble Capacity (Net MWe): *635
- 8. If Changes Occer in Capacity Ratings (!! ems Number 3 Through 7) Since Last Report,Give Reasons:
- 9. Power Level To Which Restricted,If Any (Net MWe):
- 10. Reasons For Restrictions.If Any:
(
This Month Yr..to Date Cumulative
- 11. Hours in Reporting Period Thh 3623 82.838
- 12. Number Of Hours Reactor Was Critical Thh 3602.h h7,124.8
- ~
- 13. Reactor Reserve Shutdown Hours ~
- 14. Houis Generator On.Line _
74h 3594.9 hh,788.h
- 15. Unit Reserve Shutdo. n Hours - - -
- 16. Gross Thermal Energy ver-sted (MWH) 1,% 1,384 8,720,712 88,424,h8 _
- 17. Gross Electrical Energy Generated (MWF) 521,010 _, 2,733,530 27,297,9ho i 18. Net Electrical Energy Generated (MWH) 491,609 . 2,590,813 25,6hl,117 l 19. Unit Service factor 100 99 2 sh.1
- 20. Unit Availability Factor 100 99.2 Sh.1 -
- 21. Unit Capacity Factor (Using MDC Net) 10h.1 112.6 h8.8 l 22. Unit Capacity Factor (Using DER Net) 82 1 88.8 38 h I
- 23. Unit Forced Outage Rate 0 0.78 33.1
- 24. Shutdowns Scheduled Over Next 6 Months (Type. Dste.and Duration of Each):
ReNeline. Auemt 8. antroxirtately 100 day duration.
l
- 25. If Shut Down At End Of Report Period. Estimated Date of Startup:
- 26. Units in Test Status (Prior to Commercial Operation): Forecast Achieved INITIA L CRITICALITY INITIA L ELECTRIClTY COMMERCIA L OPERATION
- Based on Condenser Back Pressure. -
(9/77) 8106120)
AVER AGE DAILY UNIT POWER LEVEL 50-255 h DOCKET NO.
Palisades UNIT DATE 6-3-81 COMPLETED BY DAPeterson
. TELEPHONE (616176h-8913 MONTH Mw 1061 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net) (gw,,g ,)
1 Th2 37 675 2 Th6 is h52 3
731 g, 255 4 708 20 268 5 690 21 537 6 "# 22 4-A Th6 i{ 7 731 23 657 628 g 3 9
739 6%
10 7U 26 662
.Thi gg, 12 7'8 23 668 13 Th2 637 29 14 30 ,
4hn 15 Tho y 681 a 737 l
l INS 1RUC110NS 1
On this format. fist the average daGy unit power level in MWe-Net for each day in the reporting month. Compute to the nearest whole megawatt.
i
-( (9/77) l 1
. . _ _ _ _ _ . , _ _ . _ _ _ . . . . . _ _ , . . . _ . _ . - , _ . . , . _ . . . _ _ _ _ _ . ~ . _ , . . . . _ , . _ . _ _ . _ , . _ . _ , . , _ _ - - _ . . _ _ _ _ _ _ _ . _ _ , _ _ _ _ _ , _
UNITSilUIDOWNS AND FOWER REDUCTIONS DOCKET NO. 50-255
. UNIT NAME Palisades DATE 6-7-81 .
REPORT MONTil Mmr . lo81 COMi*LETED ilY D Va"DenBerg TELEPilONE (616) 761_8913 4 a
1 m II QM
) ' C No. Date j 5
} ,fid Ed Causc & Cosrective A' lion du
$3 c2 2U dj =j!
Repos a 6 Psevent Recutscuce 6
2 810517 y 0 11 N/A - - -
Condenser vacuurn problems 3 810518 y 0 !! N/A - - -
Condenser vacuum problem reoccurred 4
l O
O ,
- c3 s I suf*
I 2 3 4 17: Foiced Reason: Method: Exhibit G Insisus-sions "g" S: Scheduled A-Eiguipmens Failuse(Explain) 1 Manual for Psepasation of Data
, ll Maintenance of Test 2-Manual Scra m. linesy Sheets (os 1.icensee C Refueling 3- Automatic Scram. Event Repost (LERI File INURI Cr I D Regulatory Resteietion 4-Othes (Explain) 0161) 1: Opesator Tsaining & license Examination F Adudnistrative 5 G Opesational I.isor (limplain) Esinbu I- Same Sousce 19/77) Il-Othes (lixplaiu)
.d
't
SUMMARY
OF OPERATING EXPERIENCE FOR MAY 1981 -
I Power reduction occurred on May 17 and again on May 18 as a result of unexplained loeses in condenser vacuta. Problems with the inner con-denser loop seal were corrected and the plant returned to approximately 90% power.