{{#Wiki_filter:Module III - Fire Analysis Appendix H: Damage Criteria and Damage Time Joint EPRI/NRC-RES Fire PRA Workshop August 6-10, 2018 A Collaboration of the Electric Power Research Institute (EPRI) & U.S. NRC Office of Nuclear Regulatory Research (RES)
{{#Wiki_filter:Joint EPRI/NRC-RES Fire PRA Workshop August 6-10, 2018 Module III - Fire Analysis Appendix H: Damage Criteria and Damage Time A Collaboration of the Electric Power Research Institute (EPRI) & U.S. NRC Office of Nuclear Regulatory Research (RES)


Damage Criteria Characterizing targets A target is something other than the fire ignition source that may become involved in the fire
2 Damage Criteria Characterizing targets A target is something other than the fire ignition source that may become involved in the fire
    - Defined as a part of the fire scenario Generally there are two target types:
- Defined as a part of the fire scenario Generally there are two target types:
    - Damage target: A component (or cable) that is important to plant operations that may be damaged by an exposing fire
- Damage target: A component (or cable) that is important to plant operations that may be damaged by an exposing fire
    - Secondary ignition target: Any object that is combustible and that may be ignited by an exposing fire thereby spreading the fire One object can actually be both
- Secondary ignition target: Any object that is combustible and that may be ignited by an exposing fire thereby spreading the fire One object can actually be both
    - e.g., the first cable tray above a fire ignition source This presentation is mainly about damage targets, but the same general approach applies to ignition targets as well 2
- e.g., the first cable tray above a fire ignition source This presentation is mainly about damage targets, but the same general approach applies to ignition targets as well


Damage Criteria Damage Thresholds Damage (or Failure) Threshold: the minimum value of an exposure environment parameter that can lead to the failure of the damage target of interest within the time scale of the fire
3 Damage Criteria Damage Thresholds Damage (or Failure) Threshold: the minimum value of an exposure environment parameter that can lead to the failure of the damage target of interest within the time scale of the fire
    - Can be a temperature - exposure to high temperatures such as in a hot gas layer or fire plume
- Can be a temperature - exposure to high temperatures such as in a hot gas layer or fire plume
    - Can be a radiant heat flux - generally due to direct radiant heating from the luminous flame zone of a fire
- Can be a radiant heat flux - generally due to direct radiant heating from the luminous flame zone of a fire
    - In theory, it could be a minimum smoke density, but we arent that smart (more on smoke shortly)
- In theory, it could be a minimum smoke density, but we arent that smart (more on smoke shortly)
Corresponding PRA Standard SRs: FSS-C5, C6 and D9 3
Corresponding PRA Standard SRs: FSS-C5, C6 and D9


Damage Criteria Damage Thresholds Damage thresholds are of primary interest to Task 8 - Scoping Fire Modeling, but also play a role in Task 11 - Detailed Fire Modeling Zone-of-Influence (ZOI) - The area around a fire where radiative and convective heat transfer is sufficiently strong to damage equipment or cables and/or heat other materials to the point of ignition.
4 Damage Criteria Damage Thresholds Damage thresholds are of primary interest to Task 8 - Scoping Fire Modeling, but also play a role in Task 11 - Detailed Fire Modeling Zone-of-Influence (ZOI) - The area around a fire where radiative and convective heat transfer is sufficiently strong to damage equipment or cables and/or heat other materials to the point of ignition.
    - Damage thresholds are most useful when screening out specific fire ignition sources in Task 8:
- Damage thresholds are most useful when screening out specific fire ignition sources in Task 8:
If the closest target is outside the ZOI (no damage) and fire cannot ignite any secondary combustibles, then we screen that source out of the analysis as non-threatening (more later)
If the closest target is outside the ZOI (no damage) and fire cannot ignite any secondary combustibles, then we screen that source out of the analysis as non-threatening (more later)
    - When we get to Task 11, well need damage time (more later)
- When we get to Task 11, well need damage time (more later)
Also Note: If an electrical cable is damaged, we assume that it will also be ignited. FAQ 16-0011 offers a clarification on cable tray ignition, damage and fire propagation through cable trays Based on testing experience - arcing causes piloted ignition. FAQ 16-0011 clarifies the conditions for fire propagation after ignition.
Also Note: If an electrical cable is damaged, we assume that it will also be ignited. FAQ 16-0011 offers a clarification on cable tray ignition, damage and fire propagation through cable trays Based on testing experience - arcing causes piloted ignition. FAQ 16-0011 clarifies the conditions for fire propagation after ignition.
4


Damage Criteria Damage Thresholds The damage threshold is specific to the damage target based on target type and target characteristics
5 Damage Criteria Damage Thresholds The damage threshold is specific to the damage target based on target type and target characteristics
    - What type of component?
- What type of component?
    - What are its vulnerabilities (e.g., heat, smoke, water)?
- What are its vulnerabilities (e.g., heat, smoke, water)?
    - What is the weak link relative to damage and the fire scenario?
- What is the weak link relative to damage and the fire scenario?
Most fire scenarios focus on:
Most fire scenarios focus on:
    - Electrical cables (power, control, and instrumentation)
- Electrical cables (power, control, and instrumentation)
    - Electronics and integrated circuit devices 5
- Electronics and integrated circuit devices


Cables Classification of cables by insulation type Cable insulations fall into one of two major categories:
6 Cables Classification of cables by insulation type Cable insulations fall into one of two major categories:
Thermoplastic (TP): capable of softening or fusing when heated and of hardening again when cooled (Merriam-Webster)
Thermoplastic (TP): capable of softening or fusing when heated and of hardening again when cooled (Merriam-Webster)
    - TP materials melt when heated and solidify when cooled Thermoset (TS): capable of becoming permanently rigid when heated or cured (Marriam-Webster)
- TP materials melt when heated and solidify when cooled Thermoset (TS): capable of becoming permanently rigid when heated or cured (Marriam-Webster)
    - On heating TS materials may soften, swell, blister, crack, smolder and/or burn but they wont melt Both types are used in U.S. NPPs
- On heating TS materials may soften, swell, blister, crack, smolder and/or burn but they wont melt Both types are used in U.S. NPPs
    - Thermoplastic is more common in older plants, also used in non-vital applications such as lighting and communications
- Thermoplastic is more common in older plants, also used in non-vital applications such as lighting and communications
    - Thermoset is more common in newer plants
- Thermoset is more common in newer plants
    - Practices also vary based on utility preference at the time of construction 6
- Practices also vary based on utility preference at the time of construction


Damage Criteria Cable damage thresholds The following are defined as generic damage thresholds for the most common damage targets - cables:
7 The following are defined as generic damage thresholds for the most common damage targets - cables:
Radiant Heating Criteria Temperature Criteria Cable Type NUREG/CR-6850 Thermoplastic         6 kW/m2 (0.5 BTU/ft2s)     205°C (400°F)
*if you have case specific information, you may use alternate values if you can establish a technical basis - many specific cable types will have much higher damage thresholds if you can establish a more specific insulation type for target cables Damage Criteria Cable damage thresholds Cable Type Radiant Heating Criteria Temperature Criteria Thermoplastic 6 kW/m2 (0.5 BTU/ft2s) 205°C (400°F)
Appendix H Thermoset             11 kW/m2 (1.0 BTU/ft2s)   330°C (625°F)
Thermoset 11 kW/m2 (1.0 BTU/ft2s) 330°C (625°F)
FAQ 16-0011
NUREG/CR-6850 Appendix H FAQ 16-0011
  *if you have case specific information, you may use alternate values if you can establish a technical basis - many specific cable types will have much higher damage thresholds if you can establish a more specific insulation type for target cables 7


Damage Criteria Sensitive Electronics Electronic devices refers mainly to control components that are based on integrated circuit type devices
8 Damage Criteria Sensitive Electronics Electronic devices refers mainly to control components that are based on integrated circuit type devices
    - Circuit cards, amplifiers, D/A and A/D converters, signal conditioning devices, communications equipment, computers, instrument transmitters, etc.
- Circuit cards, amplifiers, D/A and A/D converters, signal conditioning devices, communications equipment, computers, instrument transmitters, etc.
Does not include electro-mechanical devices that lack integrated circuit elements
Does not include electro-mechanical devices that lack integrated circuit elements
    - Relays, switches, indicating lights, breakers, etc.
- Relays, switches, indicating lights, breakers, etc.
Typical damage thresholds for electronics are much lower than cables:
Typical damage thresholds for electronics are much lower than cables:
    - 3 kW/m2 (0.25 BTU/ft2) and 65oC (150°F)
- 3 kW/m2 (0.25 BTU/ft2) and 65oC (150°F)
    - FAQ 13-004 Treatment of Sensitive Electronics 8
- FAQ 13-004 Treatment of Sensitive Electronics


Damage Criteria Sensitive Electronics FAQ 13-004 discusses an approach for treating sensitive electronics targets in fire scenarios
9 Damage Criteria Sensitive Electronics FAQ 13-004 discusses an approach for treating sensitive electronics targets in fire scenarios
    - Points out that there is no clear definition of what constitute sensitive electronics in NUREG/CR-6850
- Points out that there is no clear definition of what constitute sensitive electronics in NUREG/CR-6850
    - Proposed treatment assumes that equipment that is sensitive to increased temperatures will be located inside electrical enclosures
- Proposed treatment assumes that equipment that is sensitive to increased temperatures will be located inside electrical enclosures
    - Guidance is based on FDS fire simulations 317kW transient fire located 1 m from a cabinet Radiometer located inside the cabinet to measure internal heat fluxes
- Guidance is based on FDS fire simulations 317kW transient fire located 1 m from a cabinet Radiometer located inside the cabinet to measure internal heat fluxes
    - In order to reach damaging heat fluxes inside the cabinet, conditions outside the cabinet are consistent with the damage criteria for Themoset cables 9
- In order to reach damaging heat fluxes inside the cabinet, conditions outside the cabinet are consistent with the damage criteria for Themoset cables


Damage Criteria Some other specific cases Some items are considered invulnerable to fire-induced damage:
10 Damage Criteria Some other specific cases Some items are considered invulnerable to fire-induced damage:
    - Ferrous metal pipes and tanks
- Ferrous metal pipes and tanks
    - Passive components such as flow check valves
- Passive components such as flow check valves
    - Concrete structural or partitioning elements except when considering random failure likelihood in multi-compartment scenarios i.e., we do not consider fire-induced structural failure of concrete Things you still need to watch for:
- Concrete structural or partitioning elements except when considering random failure likelihood in multi-compartment scenarios i.e., we do not consider fire-induced structural failure of concrete Things you still need to watch for:
    - Soldered piping (e.g., air/gas lines that are soldered copper)
- Soldered piping (e.g., air/gas lines that are soldered copper)
    - Flexible boots/joints/sleeves on piping (e.g., the Vandellos scenario)
- Flexible boots/joints/sleeves on piping (e.g., the Vandellos scenario)
    - Exposed structural steel given a very large fire source (e.g.,
- Exposed structural steel given a very large fire source (e.g.,
catastrophic loss of the main TG set - more later) 10
catastrophic loss of the main TG set - more later)


Damage Criteria Everything else For other devices (e.g., motors, switchgear, etc.) we typically look to either the supporting cables or controls
11 Damage Criteria Everything else For other devices (e.g., motors, switchgear, etc.) we typically look to either the supporting cables or controls
    - A electric motor driven pump is fed by power cables, and those cables are generally more vulnerable to fire damage than the pump itself
- A electric motor driven pump is fed by power cables, and those cables are generally more vulnerable to fire damage than the pump itself
    - A switchgear is supported by both power and control cables - typically loss of the control cables means loss of functionality (no control power means breaker will not auto-cycle and cannot be remotely cycled)
- A switchgear is supported by both power and control cables - typically loss of the control cables means loss of functionality (no control power means breaker will not auto-cycle and cannot be remotely cycled)
    - A battery charger usually contains some integrated circuit cards that control charging rate and monitor battery status
- A battery charger usually contains some integrated circuit cards that control charging rate and monitor battery status
    - A motor operated valve again, look at the cables 11
- A motor operated valve again, look at the cables


Damage Criteria Damage Thresholds For additional rules related to damage criteria, see H.1.1; e.g.:
12 Damage Criteria Damage Thresholds For additional rules related to damage criteria, see H.1.1; e.g.:
    - Cables in conduit: potential damage targets, but will not contribute to fire growth and spread - no credit to conduit for delaying the onset of thermal damage.
- Cables in conduit: potential damage targets, but will not contribute to fire growth and spread - no credit to conduit for delaying the onset of thermal damage.
    - Cables coated by a fire-retardant coating: treat as exposed cables for damage purposes - coating may slow the subsequent spread of fire, but we are NOT specific here.
- Cables coated by a fire-retardant coating: treat as exposed cables for damage purposes - coating may slow the subsequent spread of fire, but we are NOT specific here.
12


Damage Criteria Damage Thresholds Plant-specific or product-specific damage thresholds may be used if appropriate basis is established
13 Damage Criteria Damage Thresholds Plant-specific or product-specific damage thresholds may be used if appropriate basis is established
    - NUREG/CR-6850 provides some references for information specific to many popular types and brands of cables
- NUREG/CR-6850 provides some references for information specific to many popular types and brands of cables
    - Example:
- Example:
13


Damage Criteria Damage Time It is both appropriate and desirable to consider, not just the possibility of damage, but also the time before damage occurs
14 Damage Criteria Damage Time It is both appropriate and desirable to consider, not just the possibility of damage, but also the time before damage occurs
      - This is part of Task 11 - Detailed Fire Modeling It takes time to heat a target to its damage temperature
- This is part of Task 11 - Detailed Fire Modeling It takes time to heat a target to its damage temperature
      - If the air temperature (or heat flux) equals the damage threshold, damage times may be prolonged (e.g., 30-60 minutes or more)
- If the air temperature (or heat flux) equals the damage threshold, damage times may be prolonged (e.g., 30-60 minutes or more)
      - As exposure conditions become more severe, time to damage decreases (e.g., if immersed in flames, may be a few seconds)
- As exposure conditions become more severe, time to damage decreases (e.g., if immersed in flames, may be a few seconds)
A damage time gives us a hook to credit fire intervention:
A damage time gives us a hook to credit fire intervention:
      - It tells you how long you have to put the fire and prevent damage
- It tells you how long you have to put the fire and prevent damage
      - We can then ask what is the probability that given the fire, it will be put out before damage occurs?
- We can then ask what is the probability that given the fire, it will be put out before damage occurs?
      - More details on that process later in the week, but for now well talk a little about estimating damage time 14
- More details on that process later in the week, but for now well talk a little about estimating damage time


Damage Criteria Damage time - three common approaches Predict when a fire grows large enough to create damaging environment at the target location (generally most conservative)
15 Damage Criteria Damage time - three common approaches Predict when a fire grows large enough to create damaging environment at the target location (generally most conservative)
Empirical approach (intermediate approach, e.g., SDP*)
Empirical approach (intermediate approach, e.g., SDP*)
    - Predict the peak exposure condition (temperature or heat flux)
- Predict the peak exposure condition (temperature or heat flux)
    - Use a look-up table to estimate time to damage
- Use a look-up table to estimate time to damage
    - Catch: look-up tables currently only available for generic thermoset and thermoplastic cables Direct modeling of target thermal response based on fire environment (generally most realistic)
- Catch: look-up tables currently only available for generic thermoset and thermoplastic cables Direct modeling of target thermal response based on fire environment (generally most realistic)
    - Use a fire model to predict the temperature response of the target
- Use a fire model to predict the temperature response of the target
    - When the predicted temperature of the target reaches the damage threshold, assume target failure
- When the predicted temperature of the target reaches the damage threshold, assume target failure
    - Catch: need fire model that does target response calculation
- Catch: need fire model that does target response calculation
    - Simplest example: THIEF model for cables (more later)
- Simplest example: THIEF model for cables (more later)
* Significance Determination Process 15
* Significance Determination Process


Damage Criteria Damage time - time to threshold One simple approach is to assume damage occurs when the conditions at the target location first reach the damage threshold
16 Damage Criteria Damage time - time to threshold One simple approach is to assume damage occurs when the conditions at the target location first reach the damage threshold  
      - Generally gives the most conservative answer of the three approaches
- Generally gives the most conservative answer of the three approaches
* If you can characterize fire growth versus time, then you can use that to predict the fire environment over time even using simple correlations that are based on fire heat release rate
* If you can characterize fire growth versus time, then you can use that to predict the fire environment over time even using simple correlations that are based on fire heat release rate
      - Plume temperature correlation
- Plume temperature correlation  
      - Radiant heating correlation
- Radiant heating correlation  
      - Steady state hot gas layer temperature correlation If you are in a hot gas layer situation, you can predict transient temperature profile using a fire model like CFAST or MAGIC
- Steady state hot gas layer temperature correlation If you are in a hot gas layer situation, you can predict transient temperature profile using a fire model like CFAST or MAGIC
      - Wont help much unless you have a transient fire growth profile because HGL develops to steady state very quickly in these models 16
- Wont help much unless you have a transient fire growth profile because HGL develops to steady state very quickly in these models


Damage Criteria Damage time - the look-up tables Table H-5: Failure Time-Temperature Relationship for The empirical          Thermoset cables (Table A.7.1 from reference H.6).
17 Damage Criteria Damage time - the look-up tables The empirical time to damage tables are an intermediate approach
time to damage                  Exposure Temperature           Time to Failure tables are an                  oC                    oF          (minutes) intermediate                  330                 625               28 approach 350                 660               13
- Still very simple but somewhat conservative Given exposure temperature, look-up tables give estimated time to damage Table H-5: Failure Time-Temperature Relationship for Thermoset cables (Table A.7.1 from reference H.6).
      - Still very simple but somewhat              370                 700               9 conservative              390                 735               7 Given exposure                410                 770               5 temperature, 430                 805               4 look-up tables give estimated                450                 840               3 time to damage                470                 880               2 490 (or greater)     915 (or greater)         1 17
Exposure Temperature Time to Failure (minutes) oC oF 330 625 28 350 660 13 370 700 9
390 735 7
410 770 5
430 805 4
450 840 3
470 880 2
490 (or greater) 915 (or greater) 1


Damage Criteria Damage time - direct response modeling (e.g., THIEF)
18 Damage Criteria Damage time - direct response modeling (e.g., THIEF)
Assumes a single cable in air (or in a conduit in air)
Input is an air temperature profile Output is cable temperature vs time Assume damage when cable temperature exceeds threshold Now part of CFAST and FDS; FDTs
* See: NUREG/CR-6931 V3
* See: NUREG/CR-6931 V3
* Simple one-dimensional homogeneous heat transfer model Assumes a single cable in air (or in a conduit in air)
* Simple one-dimensional homogeneous heat transfer model
Input is an air temperature profile Output is cable temperature vs time Assume damage when cable temperature exceeds threshold Now part of CFAST and FDS; FDTs 18


Thermally-Induced Electrical Failure (THIEF)
19 Thermally-Induced Electrical Failure (THIEF)
Example Cable diam               20     mm                                                           Cable diam              20    mm Mass per length          0.3    kg/m                No Conduit                                Mass per length         0.3   kg/m Jacket thickness         1.6     mm                                                            Jacket thickness        1.6    mm Conduit diameter         14     mm                                                            Conduit diameter        14    mm Conduit thickness         0     mm                        Cable Inside                        Conduit thickness        5      mm Damage temp             205     C                                                            Damage temp            205      C Ambient temp             20     C Conduit                          Ambient temp            20      C THIEF Results                                                                                THIEF Results 250                                                                                           250 200                                                                                            200 Temperature [C]
Example Cable diam 20 mm Mass per length 0.3 kg/m Jacket thickness 1.6 mm Conduit diameter 14 mm Conduit thickness 0
150 Temperature [C]
mm Damage temp 205 C
150 100                                                                                            100 Conduit                                                                                      Conduit Exposure                                                                                     Exposure 50                                            Surface                                        50                                            Surface Conductor                                                                                     Conductor 0                                                                                             0 0     500         1000           1500               2000                                     0      500        1000          1500              2000 Time [C]                                                                                     Time [C]
Ambient temp 20 C
19
0 50 100 150 200 250 0
500 1000 1500 2000 Temperature [C]
Time [C]
THIEF Results Conduit Exposure Surface Conductor Cable diam 20 mm Mass per length 0.3 kg/m Jacket thickness 1.6 mm Conduit diameter 14 mm Conduit thickness 5
mm Damage temp 205 C
Ambient temp 20 C
0 50 100 150 200 250 0
500 1000 1500 2000 Temperature [C]
Time [C]
THIEF Results Conduit Exposure Surface Conductor No Conduit Cable Inside Conduit


Damage Criteria Smoke Damage Appendix T provides an extended discussion of current knowledge regarding smoke damage
20 Damage Criteria Smoke Damage Appendix T provides an extended discussion of current knowledge regarding smoke damage
    - This is about smoke and the failure of equipment
- This is about smoke and the failure of equipment  
    - It is not about the impact of smoke on people We are interested in short-term damage
- It is not about the impact of smoke on people We are interested in short-term damage
    - Within the time scale of the fire scenario including plant shutdown
- Within the time scale of the fire scenario including plant shutdown
    - We do not consider longer term issues such as corrosion leading to failure some days or weeks after a fire Corresponding PRA Standard SR: FSS-D9 20
- We do not consider longer term issues such as corrosion leading to failure some days or weeks after a fire Corresponding PRA Standard SR: FSS-D9


Damage Criteria Smoke Damage Bottom Line: Some components are known to be vulnerable to smoke damage, but it takes a dense exposure to cause short term damage So what are the vulnerable components?
21 Damage Criteria Smoke Damage Bottom Line: Some components are known to be vulnerable to smoke damage, but it takes a dense exposure to cause short term damage So what are the vulnerable components?
    - High voltage switching equipment (arcing)
- High voltage switching equipment (arcing)
    - High voltage transmission lines (arcing)
- High voltage transmission lines (arcing)
    - Devices such as strip chart recorders that are dependent on fine mechanical motion (binding)
- Devices such as strip chart recorders that are dependent on fine mechanical motion (binding)
    - Un-protected printed circuit cards (deposition and shorting) e.g., exposed within a panel and not provided with a protective coating 21
- Un-protected printed circuit cards (deposition and shorting) e.g., exposed within a panel and not provided with a protective coating


Damage Criteria Smoke Damage Smoke damage is assessed on an empirical basis:
22 Damage Criteria Smoke Damage Smoke damage is assessed on an empirical basis:
    - We dont set quantitative thresholds
- We dont set quantitative thresholds
    - We dont try to use fire models
- We dont try to use fire models
    - You should consider the potential failure of vulnerable components due to smoke as a part of your damage target set 22
- You should consider the potential failure of vulnerable components due to smoke as a part of your damage target set


Damage Criteria Smoke Damage Assume that vulnerable components adjacent to or connected to the fire source will be damaged by smoke:
23 Damage Criteria Smoke Damage Assume that vulnerable components adjacent to or connected to the fire source will be damaged by smoke:
    - Within the same electrical cabinet or housing as a fire source e.g. given a panel fire, the whole panel is lost due to smoke and/or heat
- Within the same electrical cabinet or housing as a fire source e.g. given a panel fire, the whole panel is lost due to smoke and/or heat
    - In an adjacent cabinet if the cabinet-to-cabinet partitions are not well-sealed
- In an adjacent cabinet if the cabinet-to-cabinet partitions are not well-sealed
    - In a common stack of electrical cubicles
- In a common stack of electrical cubicles
    - In a nearby cabinet with a direct connection to the fire source e.g., a shared or common bus-duct 23
- In a nearby cabinet with a direct connection to the fire source e.g., a shared or common bus-duct


Questions?
24 Questions?}}
24}}

Latest revision as of 16:05, 5 January 2025

Joint EPRI/NRC-RES Fire PRA Workshop - Module III - Fire Analysis -Appendix H: Damage Criteria and Damage Time
ML18213A084
Person / Time
Issue date: 07/31/2018
From: Tammie Rivera
NRC/RES/DRA/FRB, Electric Power Research Institute
To:
Shared Package
ML18213A072 List:
References
Download: ML18213A084 (24)


Text

Joint EPRI/NRC-RES Fire PRA Workshop August 6-10, 2018 Module III - Fire Analysis Appendix H: Damage Criteria and Damage Time A Collaboration of the Electric Power Research Institute (EPRI) & U.S. NRC Office of Nuclear Regulatory Research (RES)

2 Damage Criteria Characterizing targets A target is something other than the fire ignition source that may become involved in the fire

- Defined as a part of the fire scenario Generally there are two target types:

- Damage target: A component (or cable) that is important to plant operations that may be damaged by an exposing fire

- Secondary ignition target: Any object that is combustible and that may be ignited by an exposing fire thereby spreading the fire One object can actually be both

- e.g., the first cable tray above a fire ignition source This presentation is mainly about damage targets, but the same general approach applies to ignition targets as well

3 Damage Criteria Damage Thresholds Damage (or Failure) Threshold: the minimum value of an exposure environment parameter that can lead to the failure of the damage target of interest within the time scale of the fire

- Can be a temperature - exposure to high temperatures such as in a hot gas layer or fire plume

- Can be a radiant heat flux - generally due to direct radiant heating from the luminous flame zone of a fire

- In theory, it could be a minimum smoke density, but we arent that smart (more on smoke shortly)

Corresponding PRA Standard SRs: FSS-C5, C6 and D9

4 Damage Criteria Damage Thresholds Damage thresholds are of primary interest to Task 8 - Scoping Fire Modeling, but also play a role in Task 11 - Detailed Fire Modeling Zone-of-Influence (ZOI) - The area around a fire where radiative and convective heat transfer is sufficiently strong to damage equipment or cables and/or heat other materials to the point of ignition.

- Damage thresholds are most useful when screening out specific fire ignition sources in Task 8:

If the closest target is outside the ZOI (no damage) and fire cannot ignite any secondary combustibles, then we screen that source out of the analysis as non-threatening (more later)

- When we get to Task 11, well need damage time (more later)

Also Note: If an electrical cable is damaged, we assume that it will also be ignited. FAQ 16-0011 offers a clarification on cable tray ignition, damage and fire propagation through cable trays Based on testing experience - arcing causes piloted ignition. FAQ 16-0011 clarifies the conditions for fire propagation after ignition.

5 Damage Criteria Damage Thresholds The damage threshold is specific to the damage target based on target type and target characteristics

- What type of component?

- What are its vulnerabilities (e.g., heat, smoke, water)?

- What is the weak link relative to damage and the fire scenario?

Most fire scenarios focus on:

- Electrical cables (power, control, and instrumentation)

- Electronics and integrated circuit devices

6 Cables Classification of cables by insulation type Cable insulations fall into one of two major categories:

Thermoplastic (TP): capable of softening or fusing when heated and of hardening again when cooled (Merriam-Webster)

- TP materials melt when heated and solidify when cooled Thermoset (TS): capable of becoming permanently rigid when heated or cured (Marriam-Webster)

- On heating TS materials may soften, swell, blister, crack, smolder and/or burn but they wont melt Both types are used in U.S. NPPs

- Thermoplastic is more common in older plants, also used in non-vital applications such as lighting and communications

- Thermoset is more common in newer plants

- Practices also vary based on utility preference at the time of construction

7 The following are defined as generic damage thresholds for the most common damage targets - cables:

  • if you have case specific information, you may use alternate values if you can establish a technical basis - many specific cable types will have much higher damage thresholds if you can establish a more specific insulation type for target cables Damage Criteria Cable damage thresholds Cable Type Radiant Heating Criteria Temperature Criteria Thermoplastic 6 kW/m2 (0.5 BTU/ft2s) 205°C (400°F)

Thermoset 11 kW/m2 (1.0 BTU/ft2s) 330°C (625°F)

NUREG/CR-6850 Appendix H FAQ 16-0011

8 Damage Criteria Sensitive Electronics Electronic devices refers mainly to control components that are based on integrated circuit type devices

- Circuit cards, amplifiers, D/A and A/D converters, signal conditioning devices, communications equipment, computers, instrument transmitters, etc.

Does not include electro-mechanical devices that lack integrated circuit elements

- Relays, switches, indicating lights, breakers, etc.

Typical damage thresholds for electronics are much lower than cables:

- 3 kW/m2 (0.25 BTU/ft2) and 65oC (150°F)

- FAQ 13-004 Treatment of Sensitive Electronics

9 Damage Criteria Sensitive Electronics FAQ 13-004 discusses an approach for treating sensitive electronics targets in fire scenarios

- Points out that there is no clear definition of what constitute sensitive electronics in NUREG/CR-6850

- Proposed treatment assumes that equipment that is sensitive to increased temperatures will be located inside electrical enclosures

- Guidance is based on FDS fire simulations 317kW transient fire located 1 m from a cabinet Radiometer located inside the cabinet to measure internal heat fluxes

- In order to reach damaging heat fluxes inside the cabinet, conditions outside the cabinet are consistent with the damage criteria for Themoset cables

10 Damage Criteria Some other specific cases Some items are considered invulnerable to fire-induced damage:

- Ferrous metal pipes and tanks

- Passive components such as flow check valves

- Concrete structural or partitioning elements except when considering random failure likelihood in multi-compartment scenarios i.e., we do not consider fire-induced structural failure of concrete Things you still need to watch for:

- Soldered piping (e.g., air/gas lines that are soldered copper)

- Flexible boots/joints/sleeves on piping (e.g., the Vandellos scenario)

- Exposed structural steel given a very large fire source (e.g.,

catastrophic loss of the main TG set - more later)

11 Damage Criteria Everything else For other devices (e.g., motors, switchgear, etc.) we typically look to either the supporting cables or controls

- A electric motor driven pump is fed by power cables, and those cables are generally more vulnerable to fire damage than the pump itself

- A switchgear is supported by both power and control cables - typically loss of the control cables means loss of functionality (no control power means breaker will not auto-cycle and cannot be remotely cycled)

- A battery charger usually contains some integrated circuit cards that control charging rate and monitor battery status

- A motor operated valve again, look at the cables

12 Damage Criteria Damage Thresholds For additional rules related to damage criteria, see H.1.1; e.g.:

- Cables in conduit: potential damage targets, but will not contribute to fire growth and spread - no credit to conduit for delaying the onset of thermal damage.

- Cables coated by a fire-retardant coating: treat as exposed cables for damage purposes - coating may slow the subsequent spread of fire, but we are NOT specific here.

13 Damage Criteria Damage Thresholds Plant-specific or product-specific damage thresholds may be used if appropriate basis is established

- NUREG/CR-6850 provides some references for information specific to many popular types and brands of cables

- Example:

14 Damage Criteria Damage Time It is both appropriate and desirable to consider, not just the possibility of damage, but also the time before damage occurs

- This is part of Task 11 - Detailed Fire Modeling It takes time to heat a target to its damage temperature

- If the air temperature (or heat flux) equals the damage threshold, damage times may be prolonged (e.g., 30-60 minutes or more)

- As exposure conditions become more severe, time to damage decreases (e.g., if immersed in flames, may be a few seconds)

A damage time gives us a hook to credit fire intervention:

- It tells you how long you have to put the fire and prevent damage

- We can then ask what is the probability that given the fire, it will be put out before damage occurs?

- More details on that process later in the week, but for now well talk a little about estimating damage time

15 Damage Criteria Damage time - three common approaches Predict when a fire grows large enough to create damaging environment at the target location (generally most conservative)

Empirical approach (intermediate approach, e.g., SDP*)

- Predict the peak exposure condition (temperature or heat flux)

- Use a look-up table to estimate time to damage

- Catch: look-up tables currently only available for generic thermoset and thermoplastic cables Direct modeling of target thermal response based on fire environment (generally most realistic)

- Use a fire model to predict the temperature response of the target

- When the predicted temperature of the target reaches the damage threshold, assume target failure

- Catch: need fire model that does target response calculation

- Simplest example: THIEF model for cables (more later)

16 Damage Criteria Damage time - time to threshold One simple approach is to assume damage occurs when the conditions at the target location first reach the damage threshold

- Generally gives the most conservative answer of the three approaches

  • If you can characterize fire growth versus time, then you can use that to predict the fire environment over time even using simple correlations that are based on fire heat release rate

- Plume temperature correlation

- Radiant heating correlation

- Steady state hot gas layer temperature correlation If you are in a hot gas layer situation, you can predict transient temperature profile using a fire model like CFAST or MAGIC

- Wont help much unless you have a transient fire growth profile because HGL develops to steady state very quickly in these models

17 Damage Criteria Damage time - the look-up tables The empirical time to damage tables are an intermediate approach

- Still very simple but somewhat conservative Given exposure temperature, look-up tables give estimated time to damage Table H-5: Failure Time-Temperature Relationship for Thermoset cables (Table A.7.1 from reference H.6).

Exposure Temperature Time to Failure (minutes) oC oF 330 625 28 350 660 13 370 700 9

390 735 7

410 770 5

430 805 4

450 840 3

470 880 2

490 (or greater) 915 (or greater) 1

18 Damage Criteria Damage time - direct response modeling (e.g., THIEF)

Assumes a single cable in air (or in a conduit in air)

Input is an air temperature profile Output is cable temperature vs time Assume damage when cable temperature exceeds threshold Now part of CFAST and FDS; FDTs

  • Simple one-dimensional homogeneous heat transfer model

19 Thermally-Induced Electrical Failure (THIEF)

Example Cable diam 20 mm Mass per length 0.3 kg/m Jacket thickness 1.6 mm Conduit diameter 14 mm Conduit thickness 0

mm Damage temp 205 C

Ambient temp 20 C

0 50 100 150 200 250 0

500 1000 1500 2000 Temperature [C]

Time [C]

THIEF Results Conduit Exposure Surface Conductor Cable diam 20 mm Mass per length 0.3 kg/m Jacket thickness 1.6 mm Conduit diameter 14 mm Conduit thickness 5

mm Damage temp 205 C

Ambient temp 20 C

0 50 100 150 200 250 0

500 1000 1500 2000 Temperature [C]

Time [C]

THIEF Results Conduit Exposure Surface Conductor No Conduit Cable Inside Conduit

20 Damage Criteria Smoke Damage Appendix T provides an extended discussion of current knowledge regarding smoke damage

- This is about smoke and the failure of equipment

- It is not about the impact of smoke on people We are interested in short-term damage

- Within the time scale of the fire scenario including plant shutdown

- We do not consider longer term issues such as corrosion leading to failure some days or weeks after a fire Corresponding PRA Standard SR: FSS-D9

21 Damage Criteria Smoke Damage Bottom Line: Some components are known to be vulnerable to smoke damage, but it takes a dense exposure to cause short term damage So what are the vulnerable components?

- High voltage switching equipment (arcing)

- High voltage transmission lines (arcing)

- Devices such as strip chart recorders that are dependent on fine mechanical motion (binding)

- Un-protected printed circuit cards (deposition and shorting) e.g., exposed within a panel and not provided with a protective coating

22 Damage Criteria Smoke Damage Smoke damage is assessed on an empirical basis:

- We dont set quantitative thresholds

- We dont try to use fire models

- You should consider the potential failure of vulnerable components due to smoke as a part of your damage target set

23 Damage Criteria Smoke Damage Assume that vulnerable components adjacent to or connected to the fire source will be damaged by smoke:

- Within the same electrical cabinet or housing as a fire source e.g. given a panel fire, the whole panel is lost due to smoke and/or heat

- In an adjacent cabinet if the cabinet-to-cabinet partitions are not well-sealed

- In a common stack of electrical cubicles

- In a nearby cabinet with a direct connection to the fire source e.g., a shared or common bus-duct

24 Questions?