| event date = 07/29/2004 09:42 EDT | | event date = 07/29/2004 09:42 EDT | ||
| last update date = 07/29/2004 | | last update date = 07/29/2004 | ||
| title = Plant Entered Lco Action Statement Due | | title = Plant Entered Lco Action Statement Due to Malfunction of a Suppression Chamber-To-Drywell Vacuum Breaker. | ||
| event text = On July 29, 2004, at approximately 0351 hours, testing of Suppression Chamber-to-Drywell vacuum breakers commenced in accordance with Periodic Test 0PT02.3.1, "Suppression Chamber-to-Drywell Vacuum Breaker Operability Test." At 0357 hours, it was determined that vacuum breaker 2-CAC-X18D had an open indication. Technical Specifications (TS) Limiting Condition for Operation (LCO) 3.6.1.6, "Suppression Chamber-to-Drywell Vacuum Breakers," Condition B was entered for one suppression chamber-to-drywell vacuum breaker (2-CAC-X18D) not indicating closed. Required Action B.1 of TS LCO 3.6.1.6 provides 4 hours to verify the vacuum breaker closed. Attempts to confirm the vacuum breaker closed were unsuccessful and at 0757 hours, TS LCO 3.6.1.6 Condition C was entered. Required Action C.1 is to be in Mode 3 (Hot Shutdown) in 12 hours and Required Action C.2 is to be in Mode 4 (Cold Shutdown) in 36 hours. Initiation of the plant shutdown required by TS LCO 3.6.1.6 commenced at 0942 hours. | | event text = On July 29, 2004, at approximately 0351 hours, testing of Suppression Chamber-to-Drywell vacuum breakers commenced in accordance with Periodic Test 0PT02.3.1, "Suppression Chamber-to-Drywell Vacuum Breaker Operability Test." At 0357 hours, it was determined that vacuum breaker 2-CAC-X18D had an open indication. Technical Specifications (TS) Limiting Condition for Operation (LCO) 3.6.1.6, "Suppression Chamber-to-Drywell Vacuum Breakers," Condition B was entered for one suppression chamber-to-drywell vacuum breaker (2-CAC-X18D) not indicating closed. Required Action B.1 of TS LCO 3.6.1.6 provides 4 hours to verify the vacuum breaker closed. Attempts to confirm the vacuum breaker closed were unsuccessful and at 0757 hours, TS LCO 3.6.1.6 Condition C was entered. Required Action C.1 is to be in Mode 3 (Hot Shutdown) in 12 hours and Required Action C.2 is to be in Mode 4 (Cold Shutdown) in 36 hours. Initiation of the plant shutdown required by TS LCO 3.6.1.6 commenced at 0942 hours. | ||
This condition is being reported in accordance with 10 CFR 50.72(b)(2)(i) as the initiation of any nuclear plant shutdown required by the plant's TS. | This condition is being reported in accordance with 10 CFR 50.72(b)(2)(i) as the initiation of any nuclear plant shutdown required by the plant's TS. |
Latest revision as of 21:23, 1 March 2018
Where | |
---|---|
Brunswick North Carolina (NRC Region 2) | |
Reporting | |
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown | |
Time - Person (Reporting Time:+-1.47 h-0.0613 days <br />-0.00875 weeks <br />-0.00201 months <br />) | |
Opened: | Ken Chism 12:14 Jul 29, 2004 |
NRC Officer: | Chauncey Gould |