Line 16: Line 16:
| event date = 07/29/2004 09:42 EDT
| event date = 07/29/2004 09:42 EDT
| last update date = 07/29/2004
| last update date = 07/29/2004
| title = Plant Entered Lco Action Statement Due To Malfunction Of A Suppression Chamber-To-Drywell Vacuum Breaker.
| title = Plant Entered Lco Action Statement Due to Malfunction of a Suppression Chamber-To-Drywell Vacuum Breaker.
| event text = On July 29, 2004, at approximately 0351 hours, testing of Suppression Chamber-to-Drywell vacuum breakers commenced in accordance with Periodic Test 0PT02.3.1, "Suppression Chamber-to-Drywell Vacuum Breaker Operability Test."  At 0357 hours, it was determined that vacuum breaker 2-CAC-X18D had an open indication.  Technical Specifications (TS) Limiting Condition for Operation (LCO) 3.6.1.6, "Suppression Chamber-to-Drywell Vacuum Breakers," Condition B was entered for one suppression chamber-to-drywell vacuum breaker (2-CAC-X18D) not indicating closed.  Required Action B.1 of TS LCO 3.6.1.6 provides 4 hours to verify the vacuum breaker closed.  Attempts to confirm the vacuum breaker closed were unsuccessful and at 0757 hours, TS LCO 3.6.1.6 Condition C was entered.  Required Action C.1 is to be in Mode 3 (Hot Shutdown) in 12 hours and Required Action C.2 is to be in Mode 4 (Cold Shutdown) in 36 hours.  Initiation of the plant shutdown required by TS LCO 3.6.1.6 commenced at 0942 hours.
| event text = On July 29, 2004, at approximately 0351 hours, testing of Suppression Chamber-to-Drywell vacuum breakers commenced in accordance with Periodic Test 0PT02.3.1, "Suppression Chamber-to-Drywell Vacuum Breaker Operability Test."  At 0357 hours, it was determined that vacuum breaker 2-CAC-X18D had an open indication.  Technical Specifications (TS) Limiting Condition for Operation (LCO) 3.6.1.6, "Suppression Chamber-to-Drywell Vacuum Breakers," Condition B was entered for one suppression chamber-to-drywell vacuum breaker (2-CAC-X18D) not indicating closed.  Required Action B.1 of TS LCO 3.6.1.6 provides 4 hours to verify the vacuum breaker closed.  Attempts to confirm the vacuum breaker closed were unsuccessful and at 0757 hours, TS LCO 3.6.1.6 Condition C was entered.  Required Action C.1 is to be in Mode 3 (Hot Shutdown) in 12 hours and Required Action C.2 is to be in Mode 4 (Cold Shutdown) in 36 hours.  Initiation of the plant shutdown required by TS LCO 3.6.1.6 commenced at 0942 hours.
This condition is being reported in accordance with 10 CFR 50.72(b)(2)(i) as the initiation of any nuclear plant shutdown required by the plant's TS.  
This condition is being reported in accordance with 10 CFR 50.72(b)(2)(i) as the initiation of any nuclear plant shutdown required by the plant's TS.  

Latest revision as of 21:23, 1 March 2018

ENS 40905 +/-
Where
Brunswick Duke Energy icon.png
North Carolina (NRC Region 2)
Reporting
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown
Time - Person (Reporting Time:+-1.47 h-0.0613 days <br />-0.00875 weeks <br />-0.00201 months <br />)
Opened: Ken Chism
12:14 Jul 29, 2004
NRC Officer: Chauncey Gould
Last Updated: Jul 29, 2004
40905 - NRC Website