ENS 51554: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 11/19/2015 13:00 PST | | event date = 11/19/2015 13:00 PST | ||
| last update date = 11/19/2015 | | last update date = 11/19/2015 | ||
| title = Unanalyzed Condition Due | | title = Unanalyzed Condition Due to Spent Fuel Pool Temperature Outside Limits | ||
| event text = A review of operations log data revealed the Unit 2 Spent Fuel Pool temperature was allowed to drift approximately two degrees below the accepted analyzed temperature of 68 degrees F. The Extent of Condition is under review and the number of instances has not been fully determined. It is possible Unit 3 may have also been affected. | | event text = A review of operations log data revealed the Unit 2 Spent Fuel Pool temperature was allowed to drift approximately two degrees below the accepted analyzed temperature of 68 degrees F. The Extent of Condition is under review and the number of instances has not been fully determined. It is possible Unit 3 may have also been affected. | ||
As described in the San Onofre UFSAR, Section 9.1.2.3 'Design Basis for Fuel Storage and Handling,' one of the conditions assumed in meeting the design basis, is as follows: the most adverse delta-k (reactivity change) was analyzed for a pool temperature range from 68 degree F to 160 degree F. Although the temperature decrease is considered unlikely to have a significant impact on the results of the analysis, it is being reported under 10 CFR 50.72(b)(2) as an unanalyzed condition because there is at this time no analysis of record for the reduced temperature condition. | As described in the San Onofre UFSAR, Section 9.1.2.3 'Design Basis for Fuel Storage and Handling,' one of the conditions assumed in meeting the design basis, is as follows: the most adverse delta-k (reactivity change) was analyzed for a pool temperature range from 68 degree F to 160 degree F. Although the temperature decrease is considered unlikely to have a significant impact on the results of the analysis, it is being reported under 10 CFR 50.72(b)(2) as an unanalyzed condition because there is at this time no analysis of record for the reduced temperature condition. |
Latest revision as of 21:46, 1 March 2018
Where | |
---|---|
San Onofre California (NRC Region 4) | |
Reporting | |
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
Time - Person (Reporting Time:+-1.83 h-0.0763 days <br />-0.0109 weeks <br />-0.00251 months <br />) | |
Opened: | James Vrla 19:10 Nov 19, 2015 |
NRC Officer: | Vince Klco |
Last Updated: | Nov 19, 2015 |
51554 - NRC Website
| |