{{#Wiki_filter:BFN-17 | {{#Wiki_filter:BFN-17 TABLE 11.9-1 QUALITY REQUIREMENTS FOR CONDENSATE IN STORAGE Specific Conductivity mho/cm 1.0 Silica (as SiO2), ppm 0.05 Chloride (as Cl), ppm 0.05 Filterable Iron ppm, 0.2}} | ||
}} | |||
Latest revision as of 04:37, 7 January 2025
Text
BFN-17 TABLE 11.9-1 QUALITY REQUIREMENTS FOR CONDENSATE IN STORAGE Specific Conductivity mho/cm 1.0 Silica (as SiO2), ppm 0.05 Chloride (as Cl), ppm 0.05 Filterable Iron ppm, 0.2