| event date = 08/12/2018 00:00 EDT
| event date = 08/12/2018 00:00 EDT
| last update date = 08/12/2018
| last update date = 08/16/2018
| title = Technical Specification Required Shutdown - Loss of 480 Voltage Emergency Bus
| title = En Revision Imported Date  8/17/2018
| event text = On 8-12-18 at 0158 EDT, Beaver Valley Unit 2 experienced a loss of 480 Volt 2P Emergency Bus.  This resulted in a Loss of Safety Function due to the 2-2 Emergency Diesel Generator [EDG] being Inoperable coincident with the Residual Heat Release Valve (2SVS-HCV104).  A Technical Specification shutdown is required per LCO 3.0.3.
| event text = EN Revision Text: TECHNICAL SPECIFICATION REQUIRED SHUTDOWN - LOSS OF 480 VOLTAGE EMERGENCY BUS
On 8-12-18 at 0158 EDT, Beaver Valley Unit 2 experienced a loss of 480 Volt 2P Emergency Bus.  This resulted in a Loss of Safety Function due to the 2-2 Emergency Diesel Generator [EDG] being Inoperable coincident with the Residual Heat Release Valve (2SVS-HCV104).  A Technical Specification shutdown is required per LCO 3.0.3.
The Licensee also stated they were in an unanalyzed condition due to the EDG and Residual Heat Release Valve being inoperable at the same time.
The Licensee also stated they were in an unanalyzed condition due to the EDG and Residual Heat Release Valve being inoperable at the same time.
The Licensee is shutting down to Mode 5 (Cold Shutdown).
The Licensee is shutting down to Mode 5 (Cold Shutdown).
The Licensee is notifying the Resident Inspector.
The Licensee is notifying the Resident Inspector.
The Licensee will be making a Press Release about the unplanned shutdown.
The Licensee will be making a Press Release about the unplanned shutdown.
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20180813en.html#en53548
* * * UPDATE ON 08/16/2018 AT 1424 EDT FROM BLASE BARTKO TO KEN MOTT * * *
On 8-12-18 at 0158 [EDT] Beaver Valley Unit 2 experienced a loss of 480 Volt 2P Emergency Bus.  Per operational guidance, this was determined to be a Loss of Safety Function due to the Unit 2 Emergency Diesel Generator (EDG) being INOPERABLE coincident with the Residual Heat Release Valve (2SVS-HCV104) 10 CFR 50.72(b)(3)(v)(B) and (D).  This was also reported as an Unanalyzed Condition 10 CFR 50.72(b)(3)(ii)(b).
No Press Release was performed for this event.
The NRC Resident Inspector was notified.
At 0410 [EDT] a Technical Specification Shutdown was commenced 10 CFR 50.72(b)(2)(i).
At 2011 [EDT] the 480 Volt 2P Emergency Bus was restored and energized.
Further evaluation of the event has determined that this event was not an Unanalyzed Condition and did not result in a Loss of Safety Function.  The classifications of Unanalyzed Condition and Loss of Safety Function are being retracted.
The accuracy of the existing guidance relative to Safety Function has been entered in the Corrective Action Program and interim actions have been taken to provide accurate guidance.
Notified R1DO (Young) via email.
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20180817en.html#en53548
}}{{unit info
}}{{unit info
| Unit =  2  
| Unit =  2  

Revision as of 07:30, 17 August 2018

ENS 53548 +/-
Where
Beaver Valley
Pennsylvania (NRC Region 1)
Reporting
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown
Time - Person (Reporting Time:+-1.03 h-0.0429 days <br />-0.00613 weeks <br />-0.00141 months <br />)
Opened: Rob Klindworth
02:58 Aug 12, 2018
NRC Officer: Richard Smith
Last Updated: Aug 16, 2018