| event date = 01/23/2004 12:20 CST
| event date = 01/23/2004 12:20 CST
| last update date = 01/23/2004
| last update date = 01/23/2004
| title = Plant Shutdown Required By Technical Specifications
| title = Plant Shutdown Required by Technical Specifications
| event text = Dresden Unit 2 is performing a Technical Specification required shutdown due to the loss of the [120 VAC] Essential Service Bus normal electrical feed.  This is reportable per 10CFR 50.72(b)(2)(i), SAF 1.2 "Plant Shutdown Required by Technical Specification". The loss of the feed occurred at 02:10 [CST] on 01/23/04 and power swapped to the backup feed.  Technical Specification 3.8.7. A. was entered and repairs began on the uninterruptible power supply.  Repairs were unsuccessful and Unit 2 shut down began at 12:20 [CST] with unit required to be hot shutdown by 22:10 [CST] 01/23/04 and cold shutdown by 22:10 [CST] 01/24/04.  Repairs will continue in parallel will unit shutdown.
| event text = Dresden Unit 2 is performing a Technical Specification required shutdown due to the loss of the [120 VAC] Essential Service Bus normal electrical feed.  This is reportable per 10CFR 50.72(b)(2)(i), SAF 1.2 "Plant Shutdown Required by Technical Specification". The loss of the feed occurred at 02:10 [CST] on 01/23/04 and power swapped to the backup feed.  Technical Specification 3.8.7. A. was entered and repairs began on the uninterruptible power supply.  Repairs were unsuccessful and Unit 2 shut down began at 12:20 [CST] with unit required to be hot shutdown by 22:10 [CST] 01/23/04 and cold shutdown by 22:10 [CST] 01/24/04.  Repairs will continue in parallel will unit shutdown.
The licensee notified the NRC Resident Inspector.
The licensee notified the NRC Resident Inspector.

Latest revision as of 21:24, 1 March 2018

ENS 40468 +/-
Where
Dresden Constellation icon.png
Illinois (NRC Region 3)
Reporting
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown
Time - Person (Reporting Time:+-4.45 h-0.185 days <br />-0.0265 weeks <br />-0.0061 months <br />)
Opened: Glen Morrow
13:53 Jan 23, 2004
NRC Officer: Mike Ripley
Last Updated: Jan 23, 2004
40468 - NRC Website