ENS 47920: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 05/12/2012 20:15 CDT | | event date = 05/12/2012 20:15 CDT | ||
| last update date = 05/13/2012 | | last update date = 05/13/2012 | ||
| title = Hvac | | title = Hvac for Technical Support Center Out of Service | ||
| event text = The facility Technical Support Center (TSC) was rendered non-functional due to the TSC HVAC Air Handling Unit (AHU) ventilation system being out of service. Investigation into the cause of the failure of the TSC ventilation AHU found a tripped supply breaker. The supply breaker was subsequently reset and the TSC HVAC unit placed back in service. | | event text = The facility Technical Support Center (TSC) was rendered non-functional due to the TSC HVAC Air Handling Unit (AHU) ventilation system being out of service. Investigation into the cause of the failure of the TSC ventilation AHU found a tripped supply breaker. The supply breaker was subsequently reset and the TSC HVAC unit placed back in service. | ||
This report is being generated per TRM bases 13.13.1 condition B for the TSC emergency response facility being out of service for greater than 30 minutes. The total out of service time was 44 minutes. | This report is being generated per TRM bases 13.13.1 condition B for the TSC emergency response facility being out of service for greater than 30 minutes. The total out of service time was 44 minutes. |
Latest revision as of 21:04, 1 March 2018
Where | |
---|---|
Farley Alabama (NRC Region 2) | |
Reporting | |
10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness | |
Time - Person (Reporting Time:+-0.25 h-0.0104 days <br />-0.00149 weeks <br />-3.4245e-4 months <br />) | |
Opened: | Blake Mitchell 01:00 May 13, 2012 |
NRC Officer: | John Knoke |
Last Updated: | May 13, 2012 |
47920 - NRC Website
| |