ENS 50083: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
| Line 16: | Line 16: | ||
| event date = 05/02/2014 EDT | | event date = 05/02/2014 EDT | ||
| last update date = 05/02/2014 | | last update date = 05/02/2014 | ||
| title = Part 21 Report - Check Valves | | title = Part 21 Report - Check Valves with Missing Jam Nuts | ||
| event text = The following is a synopsis of information received via facsimile from Flowserve: | | event text = The following is a synopsis of information received via facsimile from Flowserve: | ||
Jam nuts were found to be missing on size 4, pressure class 600, normally open, in-line check valves per Flowserve drawing no. 07-45546-01. The valves are used in saturated steam service and must close with a reverse flow of less than 7000 lbs/hr steam at 95 and 1085 psig. The valve operating parts are identified as safety related. | Jam nuts were found to be missing on size 4, pressure class 600, normally open, in-line check valves per Flowserve drawing no. 07-45546-01. The valves are used in saturated steam service and must close with a reverse flow of less than 7000 lbs/hr steam at 95 and 1085 psig. The valve operating parts are identified as safety related. | ||
Latest revision as of 20:50, 1 March 2018
| Where | |
|---|---|
| Flowserve Us Inc., Flow Control Division Raleigh, North Carolina (NRC Region 1) | |
| Organization: | Flowserve Us Inc. |
| Reporting | |
| 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect | |
| Time - Person (Reporting Time:+12.8 h0.533 days <br />0.0762 weeks <br />0.0175 months <br />) | |
| Opened: | James Mcgeehin 16:48 May 2, 2014 |
| NRC Officer: | Donald Norwood |
| Last Updated: | May 2, 2014 |
| 50083 - NRC Website | |