05000456/FIN-2000006-06: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 12: | Line 12: | ||
| identified by = NRC | | identified by = NRC | ||
| Inspection procedure = IP 71111.05 | | Inspection procedure = IP 71111.05 | ||
| Inspector = D | | Inspector = D Chyug Hausman, K Sullivan, P Qualls, R Deem, R Gardner, | ||
| CCA = N/A for ROP | | CCA = N/A for ROP | ||
| INPO aspect = | | INPO aspect = | ||
| description = The licensee did not provide any objective evidence that the molded case circuit breakers at the 120Vac and 125Vdc voltage levels had been periodically manually exercised, inspected, and tested as required by the Braidwood Stations Fire Protection Report (FPR), Chapter 2.4, Safe Shutdown Analysis, Section 2.4.1.5, Assumptions, paragraph 5.a. The licenses failure to periodically manually exercise, inspect, and test molded case circuit breakers to ensure proper operation as assumed by the FPR is a violation of the Braidwood Stations Facility Operating License. | | description = The licensee did not provide any objective evidence that the molded case circuit breakers at the 120Vac and 125Vdc voltage levels had been periodically manually exercised, inspected, and tested as required by the Braidwood Stations Fire Protection Report (FPR), Chapter 2.4, Safe Shutdown Analysis, Section 2.4.1.5, Assumptions, paragraph 5.a. The licenses failure to periodically manually exercise, inspect, and test molded case circuit breakers to ensure proper operation as assumed by the FPR is a violation of the Braidwood Stations Facility Operating License. | ||
}} | }} |
Revision as of 19:20, 20 February 2018
Site: | Braidwood |
---|---|
Report | IR 05000456/2000006 Section 1R05 |
Date counted | Jun 30, 2000 (2000Q2) |
Type: | NCV: |
cornerstone | Initiating Events |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | D Chyug Hausman K Sullivan P Qualls R Deem R Gardner |
INPO aspect | |
' | |