[ M3Q.,91 L Carolina _ Power & Light Company MD 4'.L__ _ _ ma - w m MI Brunswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461-0429 | |||
-March 28,-1983 FILE: B09-13510C SERIAL: BSEP/83-987 Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Commission Region II, Suite 3100 101 Marietta Street N.W. | |||
Atlanta, GA 30303 4 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NO. 2 DOCATT NO. 50-324 LICENSE NO. DPR-62 SPECIAL REPORT PER TECHNICAL SPECIFICATION 3.7.8 . | |||
==Dear Mr.!O'Reilly:== | |||
During Unit No._2 power operation--two fire barrier LCOs with respective | |||
: issuance dates of March 7 and 8, 1983, were generated on two Control Building fire doors. One of the doors, No. 210, was declared inoperable due to a problem with the door self-closing device. The other door, No. 303, was declared inoperable because of encountered high differential air pressure across the door which prevents automatic self-closure. The door self-closing device of door No. 210 was repaired; however, postmaintenance testing of the r door revealed it would not self-close as a result.of the encountered high r- differential air pressure across the door as. experienced with door No. 303. | |||
As a result of this event,. plant Engineering has been requested to evaluate the subject. differential air pressure problem. Until-the return of the two | |||
~ doors to operability and cancellation of the LCOs, appropriate stationed fire watches at these doors will remain in effect. | |||
Very truly yours, b Wy C. R. Dietz, General Manager Brunswick Steam Electric Plant RMP/dj/LETDJ4 Enclosure L cc: Mr. R. C. DeYoung | |||
! NRC Document Control Desic. . OFFICIAL COPY l-8 9304070145 830328 PDR:ADOCK 05000324 S PDR__ | |||
-. .. _ - .-. - . .}} | |||
Revision as of 13:06, 25 July 2020
| ML20072S370 | |
| Person / Time | |
|---|---|
| Site: | Brunswick |
| Issue date: | 03/28/1983 |
| From: | Dietz C CAROLINA POWER & LIGHT CO. |
| To: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| References | |
| BSEP-83-987, NUDOCS 8304070145 | |
| Download: ML20072S370 (1) | |
Text
.
. :, ;- bW
[ M3Q.,91 L Carolina _ Power & Light Company MD 4'.L__ _ _ ma - w m MI Brunswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461-0429
-March 28,-1983 FILE: B09-13510C SERIAL: BSEP/83-987 Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Commission Region II, Suite 3100 101 Marietta Street N.W.
Atlanta, GA 30303 4 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NO. 2 DOCATT NO. 50-324 LICENSE NO. DPR-62 SPECIAL REPORT PER TECHNICAL SPECIFICATION 3.7.8 .
Dear Mr.!O'Reilly:
During Unit No._2 power operation--two fire barrier LCOs with respective
- issuance dates of March 7 and 8, 1983, were generated on two Control Building fire doors. One of the doors, No. 210, was declared inoperable due to a problem with the door self-closing device. The other door, No. 303, was declared inoperable because of encountered high differential air pressure across the door which prevents automatic self-closure. The door self-closing device of door No. 210 was repaired; however, postmaintenance testing of the r door revealed it would not self-close as a result.of the encountered high r- differential air pressure across the door as. experienced with door No. 303.
As a result of this event,. plant Engineering has been requested to evaluate the subject. differential air pressure problem. Until-the return of the two
~ doors to operability and cancellation of the LCOs, appropriate stationed fire watches at these doors will remain in effect.
Very truly yours, b Wy C. R. Dietz, General Manager Brunswick Steam Electric Plant RMP/dj/LETDJ4 Enclosure L cc: Mr. R. C. DeYoung