| event date = 06/10/2009 09:20 CDT
| event date = 06/10/2009 09:20 CDT
| last update date = 06/15/2009
| last update date = 06/15/2009
| title = Unanalyzed Condition - Unknown Cable With Combustible Coating Found In Division I / Division Ii Cable Tray
| title = Unanalyzed Condition - Unknown Cable with Combustible Coating Found in Division I / Division II Cable Tray
| event text = At 0920 on June 10, 2009, technicians [performing] a Halon detection functional surveillance found a No. 10 AWG Tefzel coated conductor that ran in the Division 1, Division 2, and non-divisional cable trough in the Main Control Room subfloor panels.  The conductor is terminated at a ring lug to a bus bar on one end, and the termination point on the other end is unknown.  The Tefzel coating is combustible.
| event text = At 0920 on June 10, 2009, technicians [performing] a Halon detection functional surveillance found a No. 10 AWG Tefzel coated conductor that ran in the Division 1, Division 2, and non-divisional cable trough in the Main Control Room subfloor panels.  The conductor is terminated at a ring lug to a bus bar on one end, and the termination point on the other end is unknown.  The Tefzel coating is combustible.
This is reportable as an 8 hour report in accordance with 10 CFR 50.72(b)(3)(ii)(B) as 'any condition that results in the nuclear power plant being in an unanalyzed condition that significantly degrades plant safety.'
This is reportable as an 8 hour report in accordance with 10 CFR 50.72(b)(3)(ii)(B) as 'any condition that results in the nuclear power plant being in an unanalyzed condition that significantly degrades plant safety.'

Latest revision as of 01:59, 24 February 2020

ENS 45122 +/-
Where
Clinton Constellation icon.png
Illinois (NRC Region 3)
Reporting
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition
Time - Person (Reporting Time:+3.67 h0.153 days <br />0.0218 weeks <br />0.00503 months <br />)
Opened: Michael A. Reandeau
18:00 Jun 10, 2009
NRC Officer: Donald Norwood
Last Updated: Jun 15, 2009
45122 - NRC Website