Radiation monitor RU-140 (#2 Steam Generator Main Steam Line radiation monitor) experienced a communication failure on both ports A and B. The RU-140 monitor is off line and non-functional at this time.
Radiation monitor RU-140 (#2 Steam Generator Main Steam Line radiation monitor) experienced a communication failure on both ports A and B. The RU-140 monitor is off line and non-functional at this time.
At least one channel of RU-140 is required to perform a Steam Generator Tube Rupture (SGTR) dose assessment. This represents an unplanned loss of radiological assessment capability for the inability to perform dose assessments that require the radiation monitor. The ability to make emergency classifications from other radiological data collection methods such as field sampling remains available. Actions have been initiated to restore the radiation monitor.
At least one channel of RU-140 is required to perform a Steam Generator Tube Rupture (SGTR) dose assessment. This represents an unplanned loss of radiological assessment capability for the inability to perform dose assessments that require the radiation monitor. The ability to make emergency classifications from other radiological data collection methods such as field sampling remains available. Actions have been initiated to restore the radiation monitor.
The NRC Resident Inspector has been informed."
The NRC Resident Inspector has been informed.
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2019/20190912en.html#en54272
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2019/20190913en.html#en54272
}}{{unit info
}}{{unit info
| Unit =  3  
| Unit =  3  

Latest revision as of 23:43, 23 February 2020

ENS 54272 +/-
Where
Palo Verde Arizona Public Service icon.png
Arizona (NRC Region 4)
Reporting
10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness
Time - Person (Reporting Time:+2.02 h0.0842 days <br />0.012 weeks <br />0.00277 months <br />)
Opened: Jason Hill
03:25 Sep 12, 2019
NRC Officer: Jeff Herrera
Last Updated: Sep 12, 2019
54272 - NRC Website
Loading map...