ML19280A002: Difference between revisions
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
| Line 2: | Line 2: | ||
| number = ML19280A002 | | number = ML19280A002 | ||
| issue date = 10/03/2019 | | issue date = 10/03/2019 | ||
| title = Emergency Amendment Public Conference Call Discussion Points - 3 | | title = NRR E-mail Capture - FitzPatrick Emergency Amendment Public Conference Call Discussion Points - 3 | ||
| author name = Lee S | | author name = Lee S | ||
| author affiliation = NRC/NRR/DORL/LPL1 | | author affiliation = NRC/NRR/DORL/LPL1 | ||
Revision as of 05:23, 1 December 2019
| ML19280A002 | |
| Person / Time | |
|---|---|
| Site: | FitzPatrick |
| Issue date: | 10/03/2019 |
| From: | Samson Lee NRC/NRR/DORL/LPL1 |
| To: | Williams C Exelon Generation Co |
| References | |
| Download: ML19280A002 (2) | |
Text
NRR-DRMAPEm Resource From: Lee, Samson Sent: Thursday, October 3, 2019 3:58 PM To: Williams, Christian D:(Exelon Nuclear)
Subject:
FitzPatrick Emergency amendment public conference call discussion points - 3 On-Load Tap Changer In the draft LAR dated October 2, 2019, Attachment 1, Section 2.0, the following is stated: Loss or degradation of normal AC power at the 4 KV level results in an automatic fast transfer or automatic residual transfer to the offsite AC power sources through the RSSTs 71T-2 and 71T-3. These transformers contain an On-Load Tap Changer to maintain the 4KV Bus voltages under various analyzed scenarios.
The licensee stated today in case the existing RSST 71T-3 cannot be repaired, the alternative will be to replace RSST 71T-3 with an old spare transformer. Does the old spare transformer has an On-Load Tap Changer? If not, will it impact the degraded voltage setpoints specified in JAFNPP TS Table 3.3.8.1-1.
- Thanks, Sam 1
Hearing Identifier: NRR_DRMA Email Number: 240 Mail Envelope Properties (BL0PR0901MB3185597138AF01AEA40CC7E99A9F0)
Subject:
FitzPatrick Emergency amendment public conference call discussion points - 3 Sent Date: 10/3/2019 3:57:50 PM Received Date: 10/3/2019 3:57:00 PM From: Lee, Samson Created By: Samson.Lee@nrc.gov Recipients:
"Williams, Christian D:(Exelon Nuclear)" <Christian.Williams@exeloncorp.com>
Tracking Status: None Post Office: BL0PR0901MB3185.namprd09.prod.outlook.com Files Size Date & Time MESSAGE 757 10/3/2019 3:57:00 PM Options Priority: Standard Return Notification: No Reply Requested: No Sensitivity: Normal Expiration Date:
Recipients Received: