ML071370638: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 18: Line 18:


=Text=
=Text=
{{#Wiki_filter:June 6, 2007Mr. Gene F. St. Pierre, Site Vice Presidentc/o James M. Peschel Seabrook Station P. O. Box 300 Seabrook, NH 03874
{{#Wiki_filter:June 6, 2007 Mr. Gene F. St. Pierre, Site Vice President c/o James M. Peschel Seabrook Station P. O. Box 300 Seabrook, NH 03874


==SUBJECT:==
==SUBJECT:==
SEABROOK STATION, UNIT NO. 1 - RESPONSE TO GENERIC LETTER 2006-02"GRID RELIABILITY AND THE IMPACT ON PLANT RISK AND THE OPERABILITY OFOFFSITE POWER" (TAC NO. MD1032)
SEABROOK STATION, UNIT NO. 1 - RESPONSE TO GENERIC LETTER 2006-02 GRID RELIABILITY AND THE IMPACT ON PLANT RISK AND THE OPERABILITY OF OFFSITE POWER (TAC NO. MD1032)


==Dear Mr. St. Pierre:==
==Dear Mr. St. Pierre:==


On February 1, 2006, the U.S. Nuclear Regulatory Commission (NRC) issued GL 2006-02,"Grid Reliability and the Impact on Plant Risk and the Operability of Offsite Power" (Agencywide Document Access and Management System (ADAMS) Accession No.
On February 1, 2006, the U.S. Nuclear Regulatory Commission (NRC) issued GL 2006-02, Grid Reliability and the Impact on Plant Risk and the Operability of Offsite Power (Agencywide Document Access and Management System (ADAMS) Accession No.
ML060180352), to all holders of operating licenses for nuclear power reactors except those who have permanently ceased operation and have certified that fuel has been removed from the reactor vessel.GL 2006-02 notified licensees of the NRC staff's need for information in four areas as follows:
ML060180352), to all holders of operating licenses for nuclear power reactors except those who have permanently ceased operation and have certified that fuel has been removed from the reactor vessel.
(1)Use of protocols between the nuclear power plant (NPP) and the transmission systemoperator (TSO), independent system operator (ISO), or reliability coordinator/authority (RC/RA) and the use of transmission load flow analysis tools (analysis tools) by TSOs to assist NPPs in monitoring grid conditions to determine the operability of offsite power systems under plant technical specifications (TSs). (The TSO, ISO, or RC/RA is responsible for preserving the reliability of the local transmission system. In this GL the term TSO is used to denote these entities);(2)Use of NPP/TSO protocols and analysis tools by TSOs to assist NPPs in monitoring gridconditions for consideration in maintenance risk assessments;(3)Offsite power restoration procedures in accordance with Section 2 of NRC RegulatoryGuide (RG) 1.155, "Station Blackout;" and(4)Losses of offsite power caused by grid failures at a frequency equal to or greater thanonce in 20 site-years in accordance with RG 1.155.Subsequent to the GL, the NRC issued a Request For Additional Information (RAI) (ADAMSAccession No. ML063380308) regarding the resolution of GL 2006-02 to 63 of 65 holders of operating licenses for nuclear power reactors. The RAI requested licensees respond to questions in the following areas:(1)Switchyard Minimum Voltage, G. St. Pierre- 2 -(2)Loss of Real-Time Contingency Analysis (RTCA) Capability,(3)Verification of RTCA Predicted Post-Trip Voltage, (4)Identification of Applicable Single Contingencies, (5)Seasonal Variation in Grid Stress (reliability and Loss-of-offsite power (LOOP)Probability,(6)Interface With Transmission System Operator During Extended Plant Maintenance.By letters dated April 3, 2006 (ADAMS Accession No.ML060950462), and January 31, 2007(ADAMS Accession No.ML070430281), you responded to the information request of GL 2006-02 and the subsequent RAI. Based on the information you provided, the staff has concluded that compliance is being maintained with NRC regulatory requirements governing electric power sources and associated personnel training and considers your response to GL 2006-02 complete.If you have any questions, please contact me 301-415-2481Sincerely,/ra/G. Edward Miller, Project ManagerPlant Licensing Branch I-2 Division of Operating Reactor Licensing Office of Nuclear Reactor RegulationDocket No. 50-443 cc:  See next page
GL 2006-02 notified licensees of the NRC staffs need for information in four areas as follows:
(1)     Use of protocols between the nuclear power plant (NPP) and the transmission system operator (TSO), independent system operator (ISO), or reliability coordinator/authority (RC/RA) and the use of transmission load flow analysis tools (analysis tools) by TSOs to assist NPPs in monitoring grid conditions to determine the operability of offsite power systems under plant technical specifications (TSs). (The TSO, ISO, or RC/RA is responsible for preserving the reliability of the local transmission system. In this GL the term TSO is used to denote these entities);
(2)     Use of NPP/TSO protocols and analysis tools by TSOs to assist NPPs in monitoring grid conditions for consideration in maintenance risk assessments; (3)     Offsite power restoration procedures in accordance with Section 2 of NRC Regulatory Guide (RG) 1.155, Station Blackout; and (4)     Losses of offsite power caused by grid failures at a frequency equal to or greater than once in 20 site-years in accordance with RG 1.155.
Subsequent to the GL, the NRC issued a Request For Additional Information (RAI) (ADAMS Accession No. ML063380308) regarding the resolution of GL 2006-02 to 63 of 65 holders of operating licenses for nuclear power reactors. The RAI requested licensees respond to questions in the following areas:
(1)     Switchyard Minimum Voltage,


ML060950462), and January 31, 2007(ADAMS Accession No.ML070430281), you responded to the information request of GL 2006-02 and the subsequent RAI. Based on the information you provided, the staff has concluded that compliance is being maintained with NRC regulatory requirements governing electric power sources and associated personnel training and considers your response to GL 2006-02 complete.If you have any questions, please contact me 301-415-2481Sincerely,/ra/G. Edward Miller, Project ManagerPlant Licensing Branch I-2 Division of Operating Reactor Licensing Office of Nuclear Reactor RegulationDocket No. 50-443 cc: See next pageDISTRIBUTIONPUBLICGWilson, NRRRidsRgn1MailCenter(GMatakas)LPL1-2R/FRidsNrrRMGMillerRidsNrrDorlLplI-2(HChernoff)
G. St. Pierre                                  (2)    Loss of Real-Time Contingency Analysis (RTCA) Capability, (3)    Verification of RTCA Predicted Post-Trip Voltage, (4)    Identification of Applicable Single Contingencies, (5)    Seasonal Variation in Grid Stress (reliability and Loss-of-offsite power (LOOP)
RidsOgcRpRidsNrrLAMOBrienCJackson, NRR RidsNrrDorlDprMMcConnell, NRRRidsAcrsAcnwMailCenterAccession Number:  ML071370638OFFICELPL1-2/PMLPL1-2/LADE/EEEB/BCLPL1-2/BCNAMEGEMillerMO'BrienGWilsonHChernoffDATE5/22/075/30/076/6/076/6/07 Seabrook Station, Unit No. 1 cc:
Probability, (6)    Interface With Transmission System Operator During Extended Plant Maintenance.
Mr. J. A. StallSenior Vice President, Nuclear and Chief Nuclear Officer Florida Power & Light Company P.O. Box 14000 Juno Beach, FL  33408-0420Mr. Peter BrannAssistant Attorney General State House, Station #6 Augusta, ME  04333Resident InspectorU.S. Nuclear Regulatory Commission Seabrook Nuclear Power Station P.O. Box 1149 Seabrook, NH  03874Town of Exeter10 Front Street Exeter, NH  03823Regional Administrator, Region IU.S. Nuclear Regulatory Commission
By letters dated April 3, 2006 (ADAMS Accession No.ML060950462), and January 31, 2007 (ADAMS Accession No.ML070430281), you responded to the information request of GL 2006-02 and the subsequent RAI. Based on the information you provided, the staff has concluded that compliance is being maintained with NRC regulatory requirements governing electric power sources and associated personnel training and considers your response to GL 2006-02 complete.
If you have any questions, please contact me 301-415-2481 Sincerely,
                                              /ra/
G. Edward Miller, Project Manager Plant Licensing Branch I-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-443 cc: See next page


475 Allendale Road King of Prussia, PA  19406Office of the Attorney GeneralOne Ashburton Place, 20th Floor Boston, MA  02108Board of SelectmenTown of Amesbury Town Hall Amesbury, MA  01913Mr. Robert PooleFederal Emergency Management Agency Region I 99 High Street, 6 th FloorBoston, MA  02110Mr. Tom CrimminsPolestar Applied Technology One First Street, Suite 4 Los Altos, CA 94019John GiarrussoMassachusetts Emergency ManagementAgency400 Worcester Road Framingham, MA 01702-5399Ms. Kelly Ayotte, Attorney GeneralMr. Orvil Fitch, Deputy Attorney General 33 Capitol Street Concord, NH 03301Mr. Christopher M. Pope, DirectorHomeland Security & Emergency Mgmt.
ML060950462), and January 31, 2007 (ADAMS Accession No.ML070430281), you responded to the information request of GL 2006-02 and the subsequent RAI. Based on the information you provided, the staff has concluded that compliance is being maintained with NRC regulatory requirements governing electric power sources and associated personnel training and considers your response to GL 2006-02 complete.
New Hampshire Department of Safety Bureau of Emergency Management 33 Hazen Drive Concord, NH 03301Mr. M. S. Ross, Managing AttorneyFlorida Power & Light Company P.O. Box 14000 Juno Beach, FL 33408-0420Mr. Rajiv S. KundalkarVice President - Nuclear Engineering Florida Power & Light Company P.O. Box 14000 Juno Beach, FL 33408-0420James M. PeschelRegulatory Programs Manager FPL Energy Seabrook, LLC PO Box 300 Seabrook, NH 03874Ms. Marjan MashhadiSenior Attorney Florida Power & Light Company 801 Pennsylvania Ave., NW Suite 220 Washington, DC 20004 Seabrook Station, Unit No. 1 cc:
If you have any questions, please contact me 301-415-2481 Sincerely,
Mr. Mark E. WarnerVice President, Nuclear Operations Support Florida Power & Light Company P.O. Box 14000 Juno Beach, FL 33408-0420}}
                                                  /ra/
G. Edward Miller, Project Manager Plant Licensing Branch I-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-443 cc: See next page DISTRIBUTION PUBLIC                  GWilson, NRR        RidsRgn1MailCenter(GMatakas)
LPL1-2R/F                RidsNrrRMGMiller    RidsNrrDorlLplI-2(HChernoff)
RidsOgcRp                RidsNrrLAMOBrien    CJackson, NRR RidsNrrDorlDpr          MMcConnell, NRR      RidsAcrsAcnwMailCenter Accession Number: ML071370638 OFFICE LPL1-2/PM          LPL1-2/LA    DE/EEEB/BC          LPL1-2/BC NAME GEMiller            MOBrien      GWilson              HChernoff DATE    5/22/07          5/30/07      6/6/07              6/6/07
 
Seabrook Station, Unit No. 1 cc:
Mr. J. A. Stall                    Agency Senior Vice President, Nuclear and 400 Worcester Road Chief Nuclear Officer              Framingham, MA 01702-5399 Florida Power & Light Company P.O. Box 14000                      Ms. Kelly Ayotte, Attorney General Juno Beach, FL 33408-0420          Mr. Orvil Fitch, Deputy Attorney General 33 Capitol Street Mr. Peter Brann                    Concord, NH 03301 Assistant Attorney General State House, Station #6            Mr. Christopher M. Pope, Director Augusta, ME 04333                  Homeland Security & Emergency Mgmt.
New Hampshire Department of Safety Resident Inspector                  Bureau of Emergency Management U.S. Nuclear Regulatory Commission  33 Hazen Drive Seabrook Nuclear Power Station      Concord, NH 03301 P.O. Box 1149 Seabrook, NH 03874                  Mr. M. S. Ross, Managing Attorney Florida Power & Light Company Town of Exeter                      P.O. Box 14000 10 Front Street                    Juno Beach, FL 33408-0420 Exeter, NH 03823 Mr. Rajiv S. Kundalkar Regional Administrator, Region I    Vice President - Nuclear Engineering U.S. Nuclear Regulatory Commission  Florida Power & Light Company 475 Allendale Road                  P.O. Box 14000 King of Prussia, PA 19406          Juno Beach, FL 33408-0420 Office of the Attorney General      James M. Peschel One Ashburton Place, 20th Floor    Regulatory Programs Manager Boston, MA 02108                    FPL Energy Seabrook, LLC PO Box 300 Board of Selectmen                  Seabrook, NH 03874 Town of Amesbury Town Hall                          Ms. Marjan Mashhadi Amesbury, MA 01913                  Senior Attorney Florida Power & Light Company Mr. Robert Poole                    801 Pennsylvania Ave., NW Suite 220 Federal Emergency Management Agency Washington, DC 20004 Region I 99 High Street, 6th Floor Boston, MA 02110 Mr. Tom Crimmins Polestar Applied Technology One First Street, Suite 4 Los Altos, CA 94019 John Giarrusso Massachusetts Emergency Management
 
Seabrook Station, Unit No. 1 cc:
Mr. Mark E. Warner Vice President, Nuclear Operations Support Florida Power & Light Company P.O. Box 14000 Juno Beach, FL 33408-0420}}

Revision as of 07:05, 23 November 2019

Response to Generic Letter 2006-02 Grid Reliability and the Impact on Plant Risk and the Operability of Offsite Power
ML071370638
Person / Time
Site: Seabrook NextEra Energy icon.png
Issue date: 06/06/2007
From: Geoffrey Miller
NRC/NRR/ADRO/DORL/LPLI-2
To: St.Pierre G
Florida Power & Light Energy Seabrook
Miller G, NRR/DORL, 415-2481
References
GL-06-002, TAC MD1032
Download: ML071370638 (5)


Text

June 6, 2007 Mr. Gene F. St. Pierre, Site Vice President c/o James M. Peschel Seabrook Station P. O. Box 300 Seabrook, NH 03874

SUBJECT:

SEABROOK STATION, UNIT NO. 1 - RESPONSE TO GENERIC LETTER 2006-02 GRID RELIABILITY AND THE IMPACT ON PLANT RISK AND THE OPERABILITY OF OFFSITE POWER (TAC NO. MD1032)

Dear Mr. St. Pierre:

On February 1, 2006, the U.S. Nuclear Regulatory Commission (NRC) issued GL 2006-02, Grid Reliability and the Impact on Plant Risk and the Operability of Offsite Power (Agencywide Document Access and Management System (ADAMS) Accession No.

ML060180352), to all holders of operating licenses for nuclear power reactors except those who have permanently ceased operation and have certified that fuel has been removed from the reactor vessel.

GL 2006-02 notified licensees of the NRC staffs need for information in four areas as follows:

(1) Use of protocols between the nuclear power plant (NPP) and the transmission system operator (TSO), independent system operator (ISO), or reliability coordinator/authority (RC/RA) and the use of transmission load flow analysis tools (analysis tools) by TSOs to assist NPPs in monitoring grid conditions to determine the operability of offsite power systems under plant technical specifications (TSs). (The TSO, ISO, or RC/RA is responsible for preserving the reliability of the local transmission system. In this GL the term TSO is used to denote these entities);

(2) Use of NPP/TSO protocols and analysis tools by TSOs to assist NPPs in monitoring grid conditions for consideration in maintenance risk assessments; (3) Offsite power restoration procedures in accordance with Section 2 of NRC Regulatory Guide (RG) 1.155, Station Blackout; and (4) Losses of offsite power caused by grid failures at a frequency equal to or greater than once in 20 site-years in accordance with RG 1.155.

Subsequent to the GL, the NRC issued a Request For Additional Information (RAI) (ADAMS Accession No. ML063380308) regarding the resolution of GL 2006-02 to 63 of 65 holders of operating licenses for nuclear power reactors. The RAI requested licensees respond to questions in the following areas:

(1) Switchyard Minimum Voltage,

G. St. Pierre (2) Loss of Real-Time Contingency Analysis (RTCA) Capability, (3) Verification of RTCA Predicted Post-Trip Voltage, (4) Identification of Applicable Single Contingencies, (5) Seasonal Variation in Grid Stress (reliability and Loss-of-offsite power (LOOP)

Probability, (6) Interface With Transmission System Operator During Extended Plant Maintenance.

By letters dated April 3, 2006 (ADAMS Accession No.ML060950462), and January 31, 2007 (ADAMS Accession No.ML070430281), you responded to the information request of GL 2006-02 and the subsequent RAI. Based on the information you provided, the staff has concluded that compliance is being maintained with NRC regulatory requirements governing electric power sources and associated personnel training and considers your response to GL 2006-02 complete.

If you have any questions, please contact me 301-415-2481 Sincerely,

/ra/

G. Edward Miller, Project Manager Plant Licensing Branch I-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-443 cc: See next page

ML060950462), and January 31, 2007 (ADAMS Accession No.ML070430281), you responded to the information request of GL 2006-02 and the subsequent RAI. Based on the information you provided, the staff has concluded that compliance is being maintained with NRC regulatory requirements governing electric power sources and associated personnel training and considers your response to GL 2006-02 complete.

If you have any questions, please contact me 301-415-2481 Sincerely,

/ra/

G. Edward Miller, Project Manager Plant Licensing Branch I-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-443 cc: See next page DISTRIBUTION PUBLIC GWilson, NRR RidsRgn1MailCenter(GMatakas)

LPL1-2R/F RidsNrrRMGMiller RidsNrrDorlLplI-2(HChernoff)

RidsOgcRp RidsNrrLAMOBrien CJackson, NRR RidsNrrDorlDpr MMcConnell, NRR RidsAcrsAcnwMailCenter Accession Number: ML071370638 OFFICE LPL1-2/PM LPL1-2/LA DE/EEEB/BC LPL1-2/BC NAME GEMiller MOBrien GWilson HChernoff DATE 5/22/07 5/30/07 6/6/07 6/6/07

Seabrook Station, Unit No. 1 cc:

Mr. J. A. Stall Agency Senior Vice President, Nuclear and 400 Worcester Road Chief Nuclear Officer Framingham, MA 01702-5399 Florida Power & Light Company P.O. Box 14000 Ms. Kelly Ayotte, Attorney General Juno Beach, FL 33408-0420 Mr. Orvil Fitch, Deputy Attorney General 33 Capitol Street Mr. Peter Brann Concord, NH 03301 Assistant Attorney General State House, Station #6 Mr. Christopher M. Pope, Director Augusta, ME 04333 Homeland Security & Emergency Mgmt.

New Hampshire Department of Safety Resident Inspector Bureau of Emergency Management U.S. Nuclear Regulatory Commission 33 Hazen Drive Seabrook Nuclear Power Station Concord, NH 03301 P.O. Box 1149 Seabrook, NH 03874 Mr. M. S. Ross, Managing Attorney Florida Power & Light Company Town of Exeter P.O. Box 14000 10 Front Street Juno Beach, FL 33408-0420 Exeter, NH 03823 Mr. Rajiv S. Kundalkar Regional Administrator, Region I Vice President - Nuclear Engineering U.S. Nuclear Regulatory Commission Florida Power & Light Company 475 Allendale Road P.O. Box 14000 King of Prussia, PA 19406 Juno Beach, FL 33408-0420 Office of the Attorney General James M. Peschel One Ashburton Place, 20th Floor Regulatory Programs Manager Boston, MA 02108 FPL Energy Seabrook, LLC PO Box 300 Board of Selectmen Seabrook, NH 03874 Town of Amesbury Town Hall Ms. Marjan Mashhadi Amesbury, MA 01913 Senior Attorney Florida Power & Light Company Mr. Robert Poole 801 Pennsylvania Ave., NW Suite 220 Federal Emergency Management Agency Washington, DC 20004 Region I 99 High Street, 6th Floor Boston, MA 02110 Mr. Tom Crimmins Polestar Applied Technology One First Street, Suite 4 Los Altos, CA 94019 John Giarrusso Massachusetts Emergency Management

Seabrook Station, Unit No. 1 cc:

Mr. Mark E. Warner Vice President, Nuclear Operations Support Florida Power & Light Company P.O. Box 14000 Juno Beach, FL 33408-0420