W3P88-1248, Monthly Operating Rept for June 1988,for Waterford 3
| ML20151A170 | |
| Person / Time | |
|---|---|
| Site: | Waterford |
| Issue date: | 06/30/1988 |
| From: | Burski R, Geoffrey Miller LOUISIANA POWER & LIGHT CO. |
| To: | NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM) |
| References | |
| W3P88-1248, NUDOCS 8807190273 | |
| Download: ML20151A170 (7) | |
Text
.
f NRC MONTHLY OPERATING REPORT
SUMMARY
OF OPERATIONS WATERFORD 3 JUNE 1988 The unit experienced two outages and one power reduction during the month.
[
ll(
8807190273 880630 PDR ADOCK 05000392 R
_ m _.
.r
[
t PRESSURIZER SAFETY VALVE FAILURES AND CHALLENGES WATERFORD 3
-l During the month of' June 1988, there were no pressurizer safety valve failures l
or enallenges.
0 r..
!b
- l i
2 e
f 4
5 5
i i
l I
li L
a b
i 3
b f
f i
n e
?e OPERATING DATA REPORT UNIT NAME: WATERFORD 3 CITY / STATE: KILLONA/LA i
lu.TE : JULY 1988 OPERATING STATUS
- 1. Docket: 50-382 Notes
- 2. Reporting Period: June 1988
- 3. Utility
Contact:
GEORGE MILLER Phone Number:
(504) 467-8211
- 4. Licentud Thermal Power (MWt): 3390
- 5. Nameplate Rating (Gross Mwe): 1153
- 6. Design Electrical hating (Net. MWe): 1104
- 7. Maximum Dependable Capacity (Gross MWe): 1120
- 8. Maximum Dependable Capacity (Net MWe): 1073
- 9. If Changes Occur la Capacity Ratings (Items Number 4 Through 8) Since Last Report, Give Reasons:
10.
Power Level To Which Restricted, if Any (Net MWe):
NONE
- 11. Reasons for Restrictions, If Any: N/A 1his Month Yr.-to-Date Cumulative 12-Hours In Reporting Period -
720 4367.0 24264.0 _
- 13. Number Of Hours Reactor Was Critical 692.2 2860.9 18965.5
- 14. Reactor Reserve Shutdown Hours 15 Hours Generator On-Line 674.5 2730.3 18544.7 16.
Unit Reserve Shutdown Hours
=,
g-1 j
OPERATING DATA REPORT (Continued)
This Month Yr.-to-Date Cumulative
- 17. Gross Thermal Energy 1,934,985 8,796,024 60,256,996 j
Generated (MWH) l 18.
Gross Electrical Energy 636,710 2,961,440 20,342,250 Generated (MVH)-
- 19. Net Electrical Energy 600,552 2,805,157 19,329,626 Generated (MWH) i
- 20. Unit Service Factor 93.7 62.5 76.4
- 81. Unit Availability Factor 93.7 62.5 76.4 7
)
- 22. Unit Capacity Factor 77.6 59.8 74.1 (Using MDC Net)
- 23. Unit Capacity Factor 75.6 58.2 72.2 (Using DER Net) t t
- 24. Unit Forced Outage Rate 5.5 5.2 7.4 1
35.
Unit Forced Outage Hours 39.4 156.7 1487.0 l
l l
- 26. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
27.
If Shut Down At End of Report Period, Estimated Date Of Startup:
- 38. Units In Test Status (Prior to Commercial Operation):
Forecast Achieved INITIAL CRITICALITY 3/4/85 INITIAL ELECTRICITY 3/18/85 COMMERCIAL OPERATION 9/24/85
3 i
AVERAGE DAILY UNIT POWER LEVEL i
DOCKET NO. 50-382 UNIT WATERFORD 3 DATE JULY 1988 COMPLETED BY GEORGE MILLER TELEPHONE 504-467-8211 MONTH JUNE 1988 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(NWe-Net) 1 59 17 1090 2
190 18 1092 3
588 19 1094 4
665 20 1091 5
679 21 1092 6
841 22 1093 7
991 23 1092 8
1035 24 1091 l
9 1089 25 1090 10 806 26 1090 11 590 27 1090 12 679 28 1089 5
13 558 29 1090 14
-49 30 1089 15 115 31 16 915 INSTRUCTIONS On this format, list the average daily unit power level in MWe-Net for each day in the reporting month. Compute to the nearest whole megawatt.
UNIT SHUTDOWS ann POWER REDUCTIONS REPORT FOR JtWE 1988 DOCKET NO 50-382 UNIT NAfE WATERFORD 3 DATE JULY 1988 COMPLETED BY GEORGE MILMR TEEPHONE 504-467-8211 Method of Licensee Cause & Corrective Duration Shutting Event System Component Action to l
No.
Date Type (HOURS)
REASON 2 Down Reactor 3 Report #
Coded Code 6 Prevent Recurrence 88-04 880601 S
6.1 B
9 N/A TA TRB Turbine overspeed test.
88-05 880610 F
0.0 H
5 N/A SJ P
Unit-load reduction due to high vibration on a steam generator feed pump.
88-06 880613 F
39.4 H
I 88-015 AB V
Unit shutdown due to excessive reactor' coolant system leakage.
1 2
3 F: Forced Reason:
Method S: Scheduled A-Equipment Failure (Explaan) 1-Manual B-Maintenance or Test 2-Manual Scram.'
C-Refueling 3-Automatic Scram.
D-Regulatory Restriction 4-Continuation 4
E-Operator Training &
5-Load Reduction IEEE Std. 805-1984 License Examination 9-Other 5
F-Administrative IEEE Std. 803A-1983 G-Operational Error (Explain)
H-Other (Explain)
A r
LOUIS 1 AN A / 317 BARONNESTREET P. O. BOX 60340 POWE R & LIGHT NEW ORLEANS, LOUISIANA 70160 (504) 595-3100 UT i$sbsS[U July 15, 1988 W3P88-1248 A4.05 QA U.S. Nuclear Regulatory Cor.anission ATTN: Document Control Desk Washington, D.C. 20555
Subject:
Waterford 3 SES Docket No. 50-382 License No. NPF-38 MONTHLY OPERATING REPORT Enclosed is the subject monthly report which covers the operating statistics for the month of June 1988. This report is submitted per Section 6.9.1.6 of the Waterford 3 Technical Specifications for Facility Operating License No. NPF-38.
Very truly yours,
}.
4 R.1. Burski Manager Nuclear Safety & Regulatory Affairs RFB:LWL:ssf Enclosure cc:
R.D. Martin, NRC Region IV NRC Resident Inr ectors Office J.A. Calvo, NRC-NRR D.L. Wigginton, NRC-NRR INFO Records Center (J.T. Wheelock)
E.L. Blake W.M. Stevenson u
I l
\\
"AN EQUAL OPPORTUNITY EMPLOYER" l