'4 P O W E R & L I G H T! P o. BOX 6008 + NEW ORLEANS. LOUISIANA 70174 142 ORARONDE STREET
+ (504) 366-2345 UTiuTIES SYSTEM August 8, 1984 W3P84-2207 Q-3-A1.01.04 Q-3-P43.T3
' g) g g g g g 3 tir. John T. Collins Regional Administrator, Region IV q
U.S. Nuclear Regulatory Commission
)
L 611 Ryan Plaza Drive, Suite 1000 AUG 131984 1l Arlington, Texas 76012
[
Dear fir. Collins:
]
SUBJECT:
Waterford SES Unit No. 3 Docket No. 50-382 Special Safety Inspection on Fire Protection Notice of Deviation Items No. 382/8420-20 and No. 382/8420-18 As requested by the subject notice, a summary of actions taken to correct the following deviations are submitted for your review:
Item No. 382/8420-20:
"... procedure t!?1-7-010, Rev.
1, dated 5/1/83 failed to list a check for the required 6-year maintenance and 12 year hydrostatic test on dry chemical, stored pressure type of portable fire extinguishers with mild steel shells."
Response
A check for the required 6-year maintenance and 12-year hydrostatic test for dry chemical extinguishers has been listed in Revision 2 to procedure ?!?l-7-010 which was approved by our Plant Operations Review Committee on July 26, 1984.
This revision is expected to prevent the possibility of missing the required maintenance on dry chemical extinguishers.
Full compliance with requirements will be accomplished on August 10, 1984, when the new procedure is fully implemented by plant manager approval.
Item No. 382/8420-18:
... procedure FP-1-004, Rev. 2, fails to provide an adequate surveillance procedure to ensure that the minimum inventory of personnel protective equipment is verified."
Mgaggg{fo j
G
oMr. John T.' Collins W3P84-2207
- August 8, 1984 Page 2.
. Response:
FP-1-004= was. deleted and the applicable surveillance requirement was included in procedure FP-1-019,
" Fire Brigade i
Equipment."
No further actions are necessary in that the equipment necessary for-fire brigade operations has been adequately provided along with, the necessary administrative procedures.
As of June 6, i
1984, Waterford.3 has been in full compliance with -the requirement to ensure verification of a minimum inventory of personnel protective equipment.
'It is expected the corrective actions described ~ are sufficient to. resolve the subject. deviations.
Should you have any further questions or desire additional information l
contact our fire protection licensing
. engineer Kevin Curley at (p ease 504) 363-8950.
Yo'urs.very truly,
!K. W. Cook
. Nuclear Support and Licensing Manager
.KWC/KNC/sab cc:
E.
L.- Blake,. = W. M. Steven::on, J. E. Gagliardo, D. M. Crutchfield, J. Wilson, G.-L. Constable, D.'J. Kubicki, N. Fiorvante t
NS40476SEG f
I l
l'
- - - - -