MONTHYEARML18263A2812018-09-20020 September 2018 (Waterford 3) - Part 21 Report of Westinghouse 7300 Circuit Card Increased Failure Rate ML17325B0222017-11-17017 November 2017 Fisher Controls International LLC Information Notice (FIN) 2017-05 ML17081A4532017-03-20020 March 2017 Part 21 - Plastic Jar Dedication Sampling ML15089A4362015-03-21021 March 2015 Part-21 Report - Valve Seat Leakage Defect W3F1-2014-0069, Part 21 Report of Time-Delay Relay Failure2014-11-12012 November 2014 Part 21 Report of Time-Delay Relay Failure W3F1-2014-0042, Part 21 Report of Pneumatic Valve Actuator Reverse Action2014-07-0909 July 2014 Part 21 Report of Pneumatic Valve Actuator Reverse Action W3F1-2014-0026, Notification of Potential Part 21 Report of Time-Delay Relays Spurious Actuation2014-04-11011 April 2014 Notification of Potential Part 21 Report of Time-Delay Relays Spurious Actuation ML14107A1612014-04-0909 April 2014 Qualtech Np Response to 10CFR Part 21 Notification on Allen Bradley Timing Relays, Event # 49911, Docket No. 99901414 ML14079A0282014-03-13013 March 2014 Part 21 - Allen Bradley Type 700RTC Relay Spuriously De-Energizing ML13165A3422013-06-12012 June 2013 60-Day Interim Report Involving an Evaluation of a Design Change to Magne-Blast Circuit Breakers ML12094A3712012-04-0202 April 2012 Part 21 Report - Rosemount Pressure Transmitters with Nonzero Based Calibrations ML12097A3162012-03-0202 March 2012 Part 21 Report - Rosemont Pressure Tranmitters Out of Tolerance Condition ML12066A1182012-03-0202 March 2012 Part 21 Report - Rosemount Pressure Transmitters with Nonzero Based Calibrations ML0934301402009-12-0202 December 2009 10CFR21 Reporting of Defects and Non-Compliance - Engine Systems, Inc. Report No. 1OCFR21-0098, Rev. 0, Amot Thermostatic Valve Element, P/N: 9760X ML0923900432009-08-25025 August 2009 Notification of Potential Part 21 Report Due to Radiation Monitor Defect ML0907611882009-03-11011 March 2009 Part 21 Notification - Defective Hk and K-Line Circuit Breaker Tension Springs ML0723304752007-08-14014 August 2007 Rosemount 1154 Pressure Transmitter Calibration Problem 2018-09-20
[Table view] Category:Deficiency Report (per 10CFR50.55e and Part 21)
MONTHYEARML23065A2002023-03-0303 March 2023 EN 56252 Update - Flow Serve - Final Notification of Potential Part 21 on Peerless 56 Frame DC Motors ML23030A6642023-01-27027 January 2023 Flowserve, Part 21 Second Interim Notification Report Re Peerless 56 Frame DC Motors ML22342B1402022-12-0202 December 2022 56252-EN 56252 - Flowserve - Limitorque - Interim Report Potential Part 21 on Peerless 56 Frame DC Motors ML21225A0812021-08-0404 August 2021 Lake Engineering Co., Final Report Per 10 CFR Part 21 Degraded Snubber SF1154 Hydraulic Fluid Batch No. 17BLVS293 ML21014A2342020-12-0707 December 2020 Fourth Interim Notification Per 10 CFR Part 21 Re Degraded Snubber SF1154 Hydraulic Fluid Batch No. 17BLVS293 ML20304A1612020-10-14014 October 2020 Lake Engineering Co., Degraded Snubber SF1154 Hydraulic Fluid Batch No. 16DLVS852 Final Report Per 10 CFR Part 21 ML20097B6912020-03-20020 March 2020 Second Interim Notification Per 10 CFR Part 21: Degraded Snubber SF1154 Hydraulic Fluid Batch No. 16DLVS852 ML18241A0292018-08-23023 August 2018 Hex Inverter Chip on Westinghouse 7300 Process Analog Control System Circuit Cards W3F1-2018-0040, Interim Report of a Deviation or Failure to Comply2018-07-0505 July 2018 Interim Report of a Deviation or Failure to Comply ML18081A1192018-03-15015 March 2018 Rosemount Nuclear Instruments, Inc., Submittal of Notification Under 10 CFR Part 21 for Certain Model 1154 and Model 1154 Serles H Pressure Transmitters and 01154-0153-0002 Amplifier Circuit Card Assemblies ML17325B0222017-11-17017 November 2017 Fisher Controls International LLC Information Notice (FIN) 2017-05 ML17324A9792017-11-17017 November 2017 Part 21 Report Re Fisher Type 461 Valve Plug Machining ML17194A8252017-07-11011 July 2017 Part 21 Report Re Wedge Pin Failure in Anchor Darling Motor Operated Double Disc Gate Valves with Threaded Stem to Upper Wedge Connections ML17081A4532017-03-20020 March 2017 Part 21 - Plastic Jar Dedication Sampling ML17026A4142017-01-20020 January 2017 C&D Technologies, Inc. - Part 21 - Plastic Jar Dedication Sampling ML16321A4512016-10-21021 October 2016 Part 21 Reporting of Defects and Noncompliance ML16294A2642016-10-18018 October 2016 Part 21 Report - Defective Current to Pressure Transducers ML16243A4722016-08-25025 August 2016 Part 21 Reporting of Defects and Noncompliance ML16188A3762016-06-21021 June 2016 Part 21 Interim Evaluation of Deviation - Contractor Failure ML16139A8342016-05-10010 May 2016 Electroswitch - Transmittal of 10CFR Part 21 Reporting of Defects and Noncompliance Regarding Vendor Inspection of Electroswitch Corporation Docket No. 99900833 ML15303A0042015-10-23023 October 2015 Part 21 Report Regarding Westinghouse Type KIR-60 Current Transformer, Per Waterford, Unit 3 ML15103A4852015-04-0707 April 2015 Itt Engineered Valves - 2nd Interim Report to the NRC of 10 CFR 21 Event 50285, Reported by Itt 07/18/14 Concerning M I Diaphragms, Customer Testing ML15089A4362015-03-21021 March 2015 Part-21 Report - Valve Seat Leakage Defect W3F1-2014-0069, Part 21 Report of Time-Delay Relay Failure2014-11-12012 November 2014 Part 21 Report of Time-Delay Relay Failure ML14274A0522014-09-22022 September 2014 Final Report 10CFR Part 21 Evaluation Regarding Misaligned Separators in LCR-25 Standby Batteries, Revision 1 - Original Letter Did Not Include the List of Affected Utilities ML14261A1502014-09-17017 September 2014 Interim Report to the NRC of 10 CFR 21 Event 50285, Reported by Itt 07/18/14 Concerning M1 Diaphragms, Customer Testing ML14265A0492014-09-12012 September 2014 Amendment to Part 21 Report from Abb, Inc Re Deviation of K-Line Circuit Secondary Close Latch (Event #50371) ML14237A1212014-08-15015 August 2014 Notification of Potential Part 21 Re Notice of Deviation Regarding K-Line Circuit Breaker Secondary Close Latch W3F1-2014-0042, Part 21 Report of Pneumatic Valve Actuator Reverse Action2014-07-0909 July 2014 Part 21 Report of Pneumatic Valve Actuator Reverse Action ML14171A3562014-06-12012 June 2014 Masoneilan Actuators Discovered to Fail-Closed Instead of the Required Fail-Open Configuration ML14170A0132014-06-0909 June 2014 Part 21 (Event 50025) - Barton Model 288A and 289A Differential Pressure Switch Defect W3F1-2014-0026, Notification of Potential Part 21 Report of Time-Delay Relays Spurious Actuation2014-04-11011 April 2014 Notification of Potential Part 21 Report of Time-Delay Relays Spurious Actuation ML14101A4672014-04-11011 April 2014 (Waterford 3)- Notification of Potential Part 21 Report of Time-Delay Relays Spurious Actuation ML14079A0282014-03-13013 March 2014 Part 21 - Allen Bradley Type 700RTC Relay Spuriously De-Energizing ML13165A3422013-06-12012 June 2013 60-Day Interim Report Involving an Evaluation of a Design Change to Magne-Blast Circuit Breakers ML13099A2382013-03-27027 March 2013 Notification of Potential Part 21 Report Re Series 24 Csr Relays with Oversized Cam Drive Components ML13064A0122013-02-25025 February 2013 Notification of Potential Part 21 Report Re Wedge Pin Failure of an Anchor/Darling Double-Disc Gate Valve ML12352A1232012-12-13013 December 2012 60-Day Interim Report Involving an Evaluation of a Design Change to Magne-Blast Circuit Breakers ML12348A1362012-12-13013 December 2012 Part 21 60-Day Interim Report Notification: Adequacy of Design Change in Am Magne-Blast Circuit Breakers ML12283A2452012-09-28028 September 2012 Part 21 - Defective Masoneilan Transducer Model 8005N ML12094A3712012-04-0202 April 2012 Part 21 Report - Rosemount Pressure Transmitters with Nonzero Based Calibrations ML12066A1182012-03-0202 March 2012 Part 21 Report - Rosemount Pressure Transmitters with Nonzero Based Calibrations ML12097A3162012-03-0202 March 2012 Part 21 Report - Rosemont Pressure Tranmitters Out of Tolerance Condition ML11363A1882011-12-0202 December 2011 10CFR21 Reporting of Defects and Non-Compliance - Engine Systems, Inc. Report No. 10CFR21-0098, Rev. 3, Amot Thermostatic Valve Element P/N: 9760X ML11336A3692011-12-0101 December 2011 Notification of Potential Part 21 Interim Report on Thermostatic Valve Failure on Palo Verde EDG ML11251A1982011-09-0606 September 2011 Notification Under 10 CFR Part 21 on Certain Rosemount Model 1153 Series B, 1164 and 1154 Series H Pressure Transmitters, May Not Perform Their Intended Safety Function ML1109701512011-04-0101 April 2011 Interim Report on Thermostatic Valve Failure on Palo Verde EDG ML0934301402009-12-0202 December 2009 10CFR21 Reporting of Defects and Non-Compliance - Engine Systems, Inc. Report No. 1OCFR21-0098, Rev. 0, Amot Thermostatic Valve Element, P/N: 9760X ML0930304542009-10-23023 October 2009 Hilti, Inc., Potential Delivery of Nonconforming Washers, and Affected Utilities or Plants Are Pilgrim, Brunswick, Arizona Public Service, and Waterford 3 ML0930205602009-10-23023 October 2009 Potential Delivery of Nonconforming Washers Supplied with Expansion Anchors Type Hilti Kwik Bolt KB3 SS316, 1/4 and 3/8 Diameters, All Lengths, Which May Meet the Definition of a Defect within 10 CFR Part 21 2023-03-03
[Table view] |
Text
Entergy Operations, Inc.
17265 River Road Killona, LA 70057-3093 Tel 504-739-6660 Fax 504-739-6678 mchisum@entergy.com Michael R. Chisum Site Vice President Waterford 3 10 CFR 21.21 W3F1-2014-0069 November 12, 2014 U.S. Nuclear Regulatory Commission Attn: Document Control Desk 11555 Rockville Pike Rockville, MD 20852
Subject:
Part 21 Report of Time-Delay Relay Failure Waterford Steam Electric Station, Unit 3 (Waterford 3)
Docket No. 50-382 License No. NPF-38
Dear Sir or Madam:
Pursuant to 10 CFR 21.21(d)(3)(ii), Entergy is providing the Waterford Steam Electric Station, Unit 3 (Waterford 3) required written notification of the identification of a defect associated with the failure of a time-delay relay. This information was initially reported to the NRC Operations Center on October 15, 2014.
The attachment to this letter provides the information required by 10 CFR 21.21, including details associated with the failure of a certain time-delay relay at Waterford 3.
This report contains no new commitments. Please contact John P. Jarrell, Regulatory Assurance Manager, at (504) 739-6685, if you have questions regarding this information.
Sincerely,
Attachment:
Waterford 3 Part 21 Report of Allen Bradley 700RTC Relay
W3F1-2014-0069 Page 2 cc: Mr. Marc L. Dapas, Regional Administrator U.S. NRC, Region IV RidsRgn4MailCenter@nrc.gov U.S. NRC Project Manager for Waterford 3 Alan.Wang@nrc.gov Michael.Orenak@nrc.gov U.S. NRC Senior Resident Inspector for Waterford 3 Frances.Ramirez@nrc.gov Chris.Speer@nrc.gov
Attachment to W3F1-2014-0069 Waterford 3 Part 21 Report of Allen Bradley 700RTC Relay
W3F1-2014-0069 Attachment Page 1 of 3 Waterford 3 Part 21 Report of Allen Bradley 700RTC Relay This written notification information follows the format of and addresses the considerations contained in 10CFR21.21(d)(4)(i)-(ix).
I. Name and Address Michael R. Chisum 17265 River Road Killona, LA 70057 II. Facility, Activity or Component The basic component is an electrical relay. Allen Bradley 700RTC relays installed at Waterford Steam Electric Station, Unit 3 (Waterford 3) susceptible to the deviation are used in monitoring undervoltage conditions for the 3A3, 3B3, 3A31, and 3B31 safety related electrical buses, as well as other applications, such as time delay relays for starting Engineered Safety Features Actuation Signal (ESFAS) equipment.
Ill. Constructor or Supplier The basic component containing a defect was provided by QualTech NP as the qualifying vendor of the Allen Bradley manufactured 700RTC relay. QualTech NP has been notified of the 10CFR Part 21 notification and provided failure analysis documentation.
IV. Defect and Safety Hazard Nature of the defect:
Waterford 3 has experienced unexpected automatic starting of control room ventilation equipment on 4/23/2014 and 4/25/2014. The direct cause of the unexpected actuations of the equipment was determined to be the failure of an Allen Bradley model 700RTC relay, EG EREL2342 H. The failure of the associated relays caused the equipment to perform its required safety function. The relay, EG EREL2342 H, was replaced on 04/26/14 due the relay LED lamp being found off with power on the relay coil terminals.
No additional auto starts of the associated control room ventilation equipment have been reported after the relay replacement.
Independent failure analysis performed by Southwest Research Institute (SwRI) on an Allen Bradley model 700RTC00110U1 relay that failed in service at Waterford 3 identified the relays L22 coil was electrically open. Detailed destructive analysis of L22 coil revealed corrosion of the winding in multiple locations near the start-end terminal and in the bobbin-flange slot for the start-end winding pigtail. At one point near the start end of the winding there was a corrosion-induced open circuit in one of the coil-winding turns. Corrosion products removed from various locations near the failure site on L22 coil contained significant concentrations of chlorine. The independent failure analysis concluded the in-plant failure observed at Waterford 3 was caused by corrosion near the start end of the relays L22 coil winding. Source of the corrosive material that damaged
W3F1-2014-0069 Attachment Page 2 of 3 the winding was not apparent, but it is likely that it was introduced during manufacture of the coil based on review of storage practices at WF3. The qualifying vendor (Qual Tech NP) has been contacted and they have provided the completed failure analysis to the manufacturer (Allen Bradley).
Safety hazard which could have been created:
Four Allen Bradley 700RTC relays susceptible to the deviation are used in monitoring undervoltage conditions for the 3A3, 3B3, 3A31, and 3B31 safety related electrical buses. If an undervoltage condition occurs, then these relays provide a Bus Voltage Lost alarm. This Bus Voltage Lost alarm will be actuated if a failure of one of the Allen-Bradley relays listed above occurs while the bus remains energized. Additionally, if an undervoltage condition occurs concurrent with a Loss of Offsite Power or concurrent with a Safety Injection Actuation Signal while the Emergency Diesel Generator Load Sequencer is between the S3 and S8 load blocks (192 seconds), then the failure of these relays will initiate a sequencer lock out and the white Lock Out light for the sequencer will be lit. Under this scenario, the Emergency Diesel Generator will automatically start and come up to rated voltage within 10 seconds. Once the sequencer detects the bus is at full rated voltage after a Loss of Offsite Power, it will begin to sequence on loads. During the loading sequence, if the observed failure mode occurs between the S3 and S8 load block, then the lockout feature will be active. All loads previously sequenced on, prior to the lockout, will remain running. At the point of coil failure of the relay, no further automatic loading will occur. The relay failure at Waterford 3 occurred after being in service only three to four months. The under voltage relays listed above have been installed for over five months. The relays installed in the 3A3, 3B3, 3A31, and 3B31 safety related electrical buses could have been susceptible to this condition if a relay with this deviation were installed in these applications. In this instance, the relays could prevent safety functions from being accomplished due to Engineering Safety Features equipment not receiving power in the time sequence assumed by the safety analysis, and thus could have created a substantial safety hazard.
V. Date On 10/10/2014, Engineering evaluation determined the Deviation could create a Substantial Safety Hazard, as defined in 10CFR21, and subsequently provided the Site Vice President (responsible officer) information of the Defect two working days later, on 10/14/2014. NRC Headquarters Operations Center was notified by telephone on 10/15/2014 (Ref. EN#50539).
VI. Location and Number of Defective Components Thirty three (33) Allen Bradley 700RTC relays are installed at Waterford 3. These applications are used in monitoring undervoltage conditions for the 3A3, 3B3, 3A31, and 3B31 safety related electrical buses, as well as other applications, such as time delay relays for starting Engineered Safety Features Actuation Signal (ESFAS) equipment.
W3F1-2014-0069 Attachment Page 3 of 3 Only one Allen Bradley 700RTC relay has been identified with this Deviation and associated failure mode.
VII. Corrective Action The failed Allen Bradley 700RTC relay (EG EREL2342 H) was replaced by Entergys Electrical Maintenance organization at Waterford 3 as of 4/26/2014.
Perform an Engineering Study to determine possible solution to resolve Allen Bradley 700RTC relay failures that have occurred at Waterford 3. Issue additional actions to implement the results of the engineering study to resolve Allen Bradley 700RTC relay failures at Waterford 3. This action is to be performed by Entergys Engineering organization at Waterford 3 and is due by 1/15/2015.
VIII. Advice None.
IX. Early Site Permit This is not an early site permit concern.