{{#Wiki_filter:AmerenUE Callaway Plant PO Box 620 Fulton, MO 65251 September 4, 2008 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Mail Stop P1-137 Washington, DC 20555-0001 ULNRC-05537 Ameren Ladies and Gentlemen: 1111/ DOCKET NUMBER 50-483 CALLAWAY PLANT UNIT 1 UNION ELECTRIC CO. FACILITY OPERATING LICENSE NPF-30 CALLAWAY PLANT ERDS DATA POINT LIBRARY REVISIONS Ref:
- 1) 10 CFR 50, Appendix E.VI.3.a
- 2) NUREG - 1934, Revision 1 This correspondence is submitted in accordance with 10CFR50 Appendix E section VI.3.a, which requires any hardware and software changes that affect the transmitted data points identified in the ERDS Data Point Library be submitted to the NRC within 30 days after the changes are completed. Please find attached a revision for the Callaway Plant's ERDS Data Point Library reference file. These changes reflect changes made to Callaway's plant process computer on August 20, 2008.
Please contact Mr. Lewis Beaty, Computer Systems (573) 676-8632 for any questions. This letter does not contain new commitments. Sincerely, W. Neterer 4fq30 Si 2-o15 Plant Director LSB/nls Enclosure (68 pages) a subsidiary of Ameren Corporation
ULNRC-05537 September 4, 2008 Page 2 cc: Mr. Elmo E. Collins, Jr. Regional Administrator U.S. Nuclear Regulatory Commission Region IV 612 E. Lamar Blvd., Suite 400 Arlington, TX 76011-4125 Senior Resident Inspector Callaway Resident Office U.S. Nuclear Regulatory Commission 8201 NRC Road Steedman, MO 65077 Mr. Mohan C. Thadani (2 copies) Licensing Project Manager, Callaway Plant Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Mail Stop O-8G14 Washington, DC 20555-2738
ULNRC-05537 September 4, 2008 Page 3 Index and send hardcopy to QA File A160.0761 Hardcopy: Certrec Corporation 4200 South Hulen, Suite 422 Fort Worth, TX 76109 (Certrec receives ALL attachments as long as they are non-safeguards and may be publicly disclosed.) Electronic distribution for the following can be made via Other Situations ULNRC Distribution: A. C. Heflin F. M. Diya T. E. Herrmann L. H. Graessle S. A. Maglio S. L. Gallagher L. M. Belsky (NSRB) T. B. Elwood Ms. Diane M. Hooper (WCNOC) Mr. Dennis Buschbaum (TXU) Mr. Scott Bauer (Palo Verde) Mr. Stan Ketelsen (PG&E) Mr. Scott Head (STP) Mr. John ONeill (Pillsbury Winthrop Shaw Pittman LLP) Missouri Public Service Commission
Enclosure to ULNRC-05537 NRC EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY J-26060A Rev. 5 REV AFFECTED PAGES 0 NEW DOCUMENT 1 Page 2 & 9 change SEN0701 units from PCM to % 2 Change Section 2 pages 46, 48, 53-56, and 62 to revise system descriptions. Reference RFR 15126,
- SCR5929, 6247-6251.
3 Bulk issue for changes to Section 2 pages 15, 16, 17, 18, 44, 48, 53, 54, 55, 56. Reference MP 00-1008A, 00-1013A, SCR 6342, 6388-6391, 7595-
- 7598, 7737, 7739-7742,
- 7744, 7864-7867.
4 Bulk issue for changes to pages 4, 62-66. Reference MP 04-
- 1020, SCR 8258, 8259 8261,
- 8262, 8183,
- 8185, 8187, 8189 & 8324.
5 Bulk issue for changes to Section 1 pages 2-4 and Section 2 pages 6-9, 11-13, 19-41, 44-46, 48, 50, 51, 57-60, 64-66. Reference MP 07-0025.
Enclosure to ULNRC-05537 NRC EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY J-26060A Rev. 5 TABLE OF CONTENTS Title Critical Safety Function Parameters ERDS Data Point Library Section 1 2 Page Number 1 5
Enclosure to ULNRC-05537 J-26060A Rev. 5 SECTION 1 CRITICAL SAFETY FUNCTION PARAMETERS 1
Enclosure to ULNRC-05537 J-26060A Rev. 5 CRITICAL SAFETY FUNCTION PARAMETERS COMPUTER UNITS POINT PARAMETER PARAMETER DESCRIPTION REACTIVITY CONTROL NI POWER RNG NI INTER RNG NI SOURC RNG NL NL CORE COOLING REAC VES LEV TEMP CORE EX SUB MARGIN CORE FLOW Nuclear Instruments, Power Range Nuclear Instruments, Intermediate Range Nuclear Instruments, Source Range Post Accident Wide Range Post Accident Source Range 0 AMPS CPS PCM CPS SPDSS102 REU0640 SPDSS286 SEN0701 SEN0702 Reactor Vessel Water Level Highest Temperature at the Core Exit Saturation Temperature-Highest CET Total Reactor Coolant Flow 0 F F% REU0523 RJUITC08 SPDSC252 REU0487 STEAM GENERATORS SG LEVEL 1/A SG LEVEL 2/B SG LEVEL 3/C SG LEVEL 4/D SG PRESS 1/A SG PRESS 2/B SG PRESS 3/C SG PRESS 4/D MN FD FL 1/A MN FD FL 2/B MN FD FL 3/C MN FD FL 4/D AX FD FL 1/A AX FD FL 2/B AX FD FL 3/C AX FD FL 4/D HL TEMP 1/A HL TEMP 2/B HL TEMP 3/C HL TEMP 4/D CL TEMP 1/A CL TEMP 2/B Steam Generator Steam Generator Steam Generator Steam Generator Steam Generator Steam Generator Steam Generator Steam Generator 1 (or 2 (or 3 (or 4 (or 1 (or 2 (or 3 (or 4 (or Main Main Main Main A) Water Level B) Water Level C) Water Level D) Water Level A) Pressure B) Pressure C) Pressure D) Pressure Feedwater Flow Feedwater Flow Feedwater Flow Feedwater Flow Stm Gen 1 Stm Gen 2 Stm Gen 3 Stm Gen 4 Stm Gen 1 Stm Gen 2 Stm Gen 3 Stm Gen 4 Stm Gen 1 Stm Gen 2 Stm Gen 3' Stm Gen 4 Stm Gen 1 Stm Gen 2 (or A) (or B) (or C) (or D) (or A) (or B) (or C) (or D) (or A) (or B) (or C) (or D) (or A) (or B) %0 PSIG PSIG PSIG PSIG KLB/HR KLB/HR KLB/HR KLB/HR KLB/HR KLB/HR KLB/HR KLB/HR F F F F FF REL0404A REL0424A REL0444A REL0464A SPDSH263 SPDSH264 SPDSH265 SPDSH266 SPDSH005 SPDSH007 SPDSH008 SPDSH250 ALF0702 ALF0703 ALF0704 ALF0701 RET0419A RET0439A RET0459A RET0479A RET0406A RET0426A Auxiliary FW Flow Auxiliary FW Flow Auxiliary FW Flow Auxiliary FW Flow Inlet Temperature Inlet Temperature Inlet Temperature Inlet Temperature Outlet Temperature Outlet Temperature 2
Enclosure to ULNRC-05537 J-26060A Rev. 5 CRITICAL SAFETY FUNCTION PARAMETERS Stm Gen 3 (or C) Outlet Temperature Stm Gen 4 (or D) Outlet Temperature CL TEMP 3/C CL TEMP 4/D PARAMETER RCS INTEGRITY RCS PRESSURE PRZR LEVEL RCS CHG/MU HP SI FLOW LP SI FLOW CTMNT SMP NR CTMNT SMP WR F F RET0446A RET0466A PARAMETER DESCRIPTION COMPUTER UNITS POINT Reactor Coolant System Pressure Primary System Pressurizer Level Primary System Charging or Makeup Flow High Pressure Safety Injection Flow Low Pressure Safety Injection Flow Containment Sump Narrow Range Level Containment Sump Wide Range Level PSIG 0 GPM GPM GPM INCHES INCHES SPDSP252 REU0483 REU0503 REU0502 REU0501 LFL0702 LFL0701 RADIOACTIVITY CONTROL EFF GAS RAD EFF GAS RAD EFF GAS RAD EFF LIQ RAD COND A/E RAD CNMNT RAD RCS LTDN RAD MAIN SL 1/A MAIN SL 2/B MAIN SL 3/C MAIN SL 4/D Radioactivity of Released Gasses Radioactivity of Released Gasses Radioactivity of Released Gasses Radioactivity of Released Liquids Condenser Air Ejector Radioactivity Radiation Level in the Containment Rad Level of the RCS Letdown Line UCI/ML GTR0021B UCI/ML GHROO01B MR/HR FCR0385 UCI/ML HBROO18 UCI/ML GER0092 R/HR SPDSC254 UCI/ML SJR0001 Stm Gen 1 (or A) Stm Gen 2 (or B) Stm Gen 3 (or C) Stm Gen 4 (or D) Steam Line Rad Level Steam Line Rad Level Steam Line Rad Level Steam Line Rad Level NL NL NL NL Stm Line Stm Line Stm Line Stm Line A PORV Disch Rad Mon B PORV Disch Rad Mon C PORV Disch Rad Mon D PORV Disch Rad Mon MR/HR MR/HR MR/HR MR/HR ABRO111 ABRO112 ABRO113 ABRO114 SG BD RAD 1A SG BD RAD 2B SG BD RAD 3C SG BD RAD 4D Stm Gen 1 Stm Gen 2 Stm Gen 3 Stm Gen 4 (or A) Blowdown Rad Level (or B) Blowdown Rad Level (or C) Blowdown Rad Level (or D) Blowdown Rad Level UCI/ML BMR0025 CONTAINMENT CONDITIONS 3
Enclosure to ULNRC-05537 J-26060A Rev. 5 CRITICAL SAFETY FUNCTION PARAMETERS CTMNT PRESS CTMNT TEMP H2 CONC Containment Pressure Containment Temperature Containment Hydrogen Concentration PSIG F0 SPDSC253 GNT0701 SPDSCH2A COMPUTER PARAMETER DESCRIPTION UNITS POINT PARAMETER MISCELLANEOUS PARAMETERS BWST LEVEL WIND SPEED WIND SPEED WIND DIR WIND DIR STAB CLASS Borated Water Storage Tank Level Wind Speed at the Reactor Site Wind Speed at the Reactor Site Wind Direction at the Reactor Site Wind Direction at the Reactor Site Air Stability at the Reactor Site 0 MPH MPH DEGFR DEGFR STABI REU0511 RDS5010A RDS5060A RDZ5010A RDZ5060A RDUO701A 4
Enclosure to ULNRC-05537 J-26060A Rev. 5 SECTION 2 ERDS DATA POINT LIBRARY 5
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A NI POWER RNG SPDSS102 POWER RANGE LEVEL AVG NUCLEAR INSTR POWER RANGE A% EACH 1% EQUALS APROX. 12 MW 0.OOOE+00 1.200E+02 N/A N/A P 4 AVERAGE REACTOR CAVITY N/A N/A N/A LOW N/A N/A MAY FAIL HIGH. 6
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A NI INTER RNG REU0640 AVERAGE INTERMEDIATE RANGE Q NUCLEAR INSTR INTERMEDIATE RANGE A AMPS N/A 1.OOOE-II 1.OOOE-03 N/A N/A P 2 AVERAGE REACTOR CAVITY N/A N/A N/A LOW N/A N/A MAY FAIL HIGH. 7
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CWl N/A NI SOURC RNG SPDSS286 SOURCE RANGE POWER LEVEL AVG NUCLEAR INSTR SOURCE RANGE A CPS N/A 2.500E-01 1.OOOE+06 N/A N/A P 2 AVERAGE REACTOR CAVITY N/A 1E-10 AMPS >1E-10 AMPS LOW N/A N/A MAY FAIL HIGH. 8
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A NL SEN0701 POST ACCIDENT WIDE RANGE POST ACCIDENT WIDE RANGE A0 PERCENT
- E-03 1.OOOE-08 2.OOOE+02 N/A N/A P
2 AVERAGE REACTOR CAVITY N/A N/A N/A LOW N/A N/A MAY FAIL HIGH. 9
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/01/91 CW1 N/A NL SEN0702 POST ACCIDENT SOURCE RANGE POST ACCIDENT SOURCE RANGE A CPS N/A 1.OOOE-01 1.OOOE+05 N/A N/A P 2 AVERAGE REACTOR CAVITY N/A N/A N/A LOW N/A N/A, MAY FAIL HIGH. 10
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A REAC VES LEV REU0523 RX VESSEL WR A/B LEVEL AVG REACTOR VESSEL WATER LEVEL A0 TOTAL INSIDE FLUID HEIGHT 494.9 INCHES -2.500E+00 1.250E+02 COMPLX BOTTOM OF VESSEL P 2 AVERAGE REACTOR VESSEL N/A N/A N/A LOW Y WET USES DIFFERENTIAL PRESSURE ACROSS THE VESSEL TO DETERMINE VESSEL LEVEL OR RELATIVE VOID CONTENT OF THE CIRCULATING PRIMARY COOLANT SYSTEM FLUID. MAY FAIL HIGH. 11
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 8/29/2008 CWN N/A TEMP CORE EX RJUITC08 HOTTEST NON BAD TC lMA HIGHEST TEMP AT CORE EXIT A F N/A 0.OOOE+00 2.300E+03 N/A N/A P 50 MAXIMUM REACTOR VESSEL N/A N/A N/A LOW N/A N/A MAY FAIL HIGH. 12
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/2 1/2008 CW1 N/A SUB MARGIN SPDSC252 RCS COOLANT SUBCOOLING SATURATION TEMP - HIGHEST CET A F N/A -2.OOOE+02 2.OOOE+03 N/A N/A P 4 AVERAGE OF LOWEST VALUE FROM EACH TRAIN REACTOR VESSEL N/A N/A N/A LOW N/A N/A MAY FAIL HIGH. 13
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/01/91 CW1 N/A CORE FLOW REU0487 REACTOR COOLANT LOOP AVE FLOW TOTAL REACTOR COOLANT FLOW A EACH 1% EQUALS APROX. 1.394E+06 LB/HR 0.OOOE+00 1.200E+02 N/A N/A P 12 AVERAGE CROSSOVER LEG N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 14
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/31/2005 CW1 N/A SG LEVEL 1/A REL0404A SG A WR LEVEL STEAM GEN A WATER LEVEL A0 100% = 586.9 INCHES
- 0. OOOE+00 1.OOOE+02 TUBSHT 13 INCHES ABOVE TUBE SHEET S
1 N/A STEAM GENERATOR A HIHI/HI /LO /LOLO 97 /92 /NA /NA (Plant mode 1-3) 97 /92 /87 /NA (Plant mode 4) NA /NA /87 /NA (Plant mode 5-6) N/A N/A LOW Y WET 73.3% IS TOP OF HIGHEST TUBE. MAY FAIL HIGH. 15
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg Unique System Desc: 10/31/2005 CWl N/A SG LEVEL 2/B REL0424A SG B WR LEVEL STEAM GEN B WATER LEVEL A0 100% = 586.9 INCHES 0.OOOE+00 1.OOOE+02 TUBSHT 13 INCHES ABOVE TUBE SHEET S 1 N/A STEAM GENERATOR B HIHI/HI /LO /LOLO 97 /92 /NA /NA (Plant mode 1-3) 97 /92 /87 /NA (Plant mode 4) NA /NA /87 /NA (Plant mode 5-6) N/A N/A LOW Y WET 73.3% IS TOP OF HIGHEST TUBE. MAY FAIL HIGH. 16
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/31/2005 CW1 N/A SG LEVEL 3/C REL0444A SG C WR LEVEL STEAM GEN C WATER LEVEL A0 100% = 586.9 INCHES 0.OOOE+00 1.OOOE+02 TUBSHT 13 INCHES ABOVE TUBE SHEET S 1 N/A STEAM GENERATOR C HIHI/HI /LO /LOLO 97 /92 /NA /NA (Plant mode 1-3) 97 /92 /87 /NA (Plant mode 4) NA /NA /87 /NA (Plant mode 5-6) N/A N/A LOW Y WET 73.3% IS TOP OF HIGHEST TUBE. MAY FAIL HIGH. 17
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/31/2005 CWl N/A SG LEVEL 4/D REL0464A SG D WR LEVEL STEAM GEN D WATER LEVEL A0 100% = 586.9 INCHES
- 0. OOOE+00 1.OOOE+02 TUBSHT 13 INCHES ABOVE TUBE SHEET S
1 N/A STEAM GENERATOR D HIHI/HI /LO /LOLO 97 /92 /NA /NA (Plant mode 1-3) 97 /92 /87 /NA (Plant mode 4) NA /NA /87 /NA (Plant mode 5-6) N/A N/A LOW N/A N/A 73.3% IS TOP OF HIGHEST TUBE. MAY FAIL HIGH. 18
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A SG PRESS 1/A SPDSH263 SG A AVG PRESSURE STEAM GENERATOR A PRESSURE A PSIG N/A 0.OOOE+00 1.300E+03 N/A N/A P 3 AVERAGE SECONDARY SIDE DOWNSTREAM SG A N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 19
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A SG PRESS 2/B SPDSH264 SG B AVG PRESSURE STEAM GENERATOR B PRESSURE A PSIG N/A 0.OOOE+00 1.300E+03 N/A N/A P 3 AVERAGE SECONDARY SIDE DOWNSTREAM SG B N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 20
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CWl N/A SG PRESS 3/B SPDSH265 SG C AVG PRESSURE STEAM GENERATOR C PRESSURE A PSIG N/A 0.OOOE+00 1.300E+03 N/A N/A P 3 AVERAGE SECONDARY SIDE DOWNSTREAM SG C N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 21
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A SG PRESS 4/D SPDSH266 SG D AVG PRESSURE STEAM GENERATOR D PRESSURE A PSIG N/A 0.OOOE+00 1.300E+03 N/A N/A P 3 AVERAGE SECONDARY SIDE DOWNSTREAM SG D N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 22
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A MN FD FL 1/A SPDSH005 SG A MAIN FEEDWATER FLOW STM GEN A MAIN FEEDWATER FLOW A KLB/HR N/A
- 0. OOOE+00 5.000E+03 N/A N/A P
2 AVERAGE FROM FEEDWATER SYSTEM UPSTREAM SG A N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 23
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A MN FD FL 2/B SPDSH007 SG B MAIN FEEDWATER FLOW STM GEN B MAIN FEEDWATER FLOW 'A KLB/HR N/A 0.OOOE+00 5.OOOE+03 N/A N/A P 2 AVERAGE FROM FEEDWATER SYSTEM UPSTREAM SG B N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 24
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CWl N/A MN FD FL 3/C SPDSH008 SG C MAIN FEEDWATER FLOW STM GEN C MAIN FEEDWATER FLOW A KLB/HR N/A 0.OOOE+00 5.OOOE+03 N/A N/A P 2 AVERAGE FROM FEEDWATER SYSTEM UPSTREAM SG C N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 25
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CWl N/A MN FD FL 4/D SPDSH250 SG D MAIN FEEDWATER FLOW STM GEN D MAIN FEEDWATER FLOW A KLB/HR N/A 0.OOOE+00 5.000E+03 N/A N/A P 2 AVERAGE FROM FEEDWATER SYSTEM UPSTREAM SG D N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 26
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A AX FD FL 1/A ALF0702 AFW TO SG A FLOW STM GEN A AUXILIARY FW FLOW A KLB/HR N/A 0.000E+00 2.000E+02 N/A N/A S 1 N/A FROM AUX FEEDWATER SYSTEM UPSTREAM SG A N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 27
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A AX FD FL 2/B ALF0703 AFW TO SG B FLOW STM GEN B AUXILIARY FW FLOW A KLB/HR N/A 0.OOOE+00 2.000E+02 N/A N/A S 1 N/A FROM AUX FEEDWATER SYSTEM UPSTREAM SG B N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 28
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A AX FD FL 3/C ALF0704 AFW TO SG C FLOW STM GEN C AUXILIARY FW FLOW A KLB/HR N/A 0.000E+00 2.OOOE+02 N/A N/A S 1 N/A FROM AUX FEEDWATER SYSTEM UPSTREAM SG C N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 29
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter:. Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor. Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 8/29/2008 CWl N/A AX FD FL 4/D ALF0701 AFW TO SG D FLOW STM GEN D AUXILIARY FW FLOW A KLB/HR N/A 0.000E+00 2.000E+02 N/A N/A S 1 N/A FROM AUX FEEDWATER SYSTEM UPSTREAM SG D N/A N/A N/A LOW N/A N/A MAY FAIL HIGH. 30
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A HL TEMP 1/A RET041,9A RCS LOOP A WR HOT LEG TEMP STM GEN A INLET TEMPERATURE A F N/A 0.OOOE+00 7.OOOE+02 N/A N/A S 1 N/A LOOP N/A 1 HOT LEG N/A N/A LOW N/A N/A MAY FAIL HIGH. 31
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A HL TEMP 2/B RET0439A RCS LOOP B WR HOT LEG TEMP STM GEN B INLET TEMPERATURE A F N/A 0.OOOE+00 7.OOOE+02 N/A N/A S 1 N/A LOOP N/A 2 HOT LEG N/A N/A LOW N/A N/A MAY FAIL HIGH. 32
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CWl N/A HL TEMP 3/C RET0459A RCS LOOP C WR HOT LEG TEMP STM GEN C INLET TEMPERATURE A F N/A 0.OOOE+00 7.OOOE+02 N/A N/A S 1 N/A LOOP 3 HOT LEG N/A N/A N/A LOW N/A N/A MAY FAIL HIGH. 33
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A HL TEMP 4/D RET0479A RCS LOOP D WR HOT LEG TEMP STM GEN D INLET TEMPERATURE A F N/A
- 0. OOOE+00 7.OOOE+02 N/A N/A S
1 N/A LOOP N/A 4 HOT LEG N/A N/A LOW N/A N/A MAY FAIL HIGH. 34
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or-SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CWl N/A CL TEMP 1/A RET0406A RCS LOOP A WR COLD LEG TEMP STM GEN A OUTLET TEMPERATURE A F N/A 0.OOOE+00 7.OOOE+02 N/A N/A S 1 N/A LOOP N/A 1 COLD LEG N/A N/A LOW N/A N/A MAY FAIL HIGH. 35
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A CL TEMP 2/B RET0426A RCS LOOP B WR COLD LEG TEMP STM GEN B OUTLET TEMPERATURE A F N/A 0.OOOE+00 7.OOOE+02 N/A N/A S 1 N/A LOOP 2 COLD LEG N/A N/A N/A LOW N/A N/A MAY FAIL HIGH. 36
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A CL TEMP 3/C RET0446A RCS LOOP C WR COLD LEG TEMP STM GEN C OUTLET TEMPERATURE A F N/A 0.OOOE+00 7.OOOE+02 N/A N/A S 1 N/A LOOP N/A 3 COLD LEG N/A N/A LOW N/A N/A MAY FAIL HIGH. 37
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CWl N/A CL TEMP 4/D RET0466A RCS LOOP D WR COLD LEG TEMP STM GEN D OUTLET TEMPERATURE A F N/A 0.OOOE+00 7.OOOE+02 N/A N/A S 1 N/A LOOP N/A 4 COLD LEG N/A N/A LOW N/A N/A MAY FAIL HIGH. 38
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A RCS WR AVG PRESSURE SPDSP252 RCS WR AVG PRESSURE REACTOR COOLANT SYSTEM PRESSURE A PSIG N/A 0.OOOE+00 3.000E+03 N/A N/A P 2 AVERAGE TUBING FROM REACTOR VESSEL N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 39
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 08/29/08 CW1 N/A PRZR LEVEL REU0483 PZR LEVEL 1/2/3 AVG PRIMARY SYSTEM PRESSURIZER LEVEL A% 100% = 555 INCHES 0.OOOE+00 1.OOOE+02 COMPLX 40 INCHES ABOVE PRESSURIZER BOTTOM P 3 AVERAGE PRESSURIZER N/A N/A N/A LOW Y WET PRESSURIZER VOLUME IS 1800 CUBIC FEET. HEATER TOPS AT 17.5% LEVEL. MAY FAIL HIGH. 40
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A RCS CHG/MU REU0503 CHG PUMP SI FLOW PRI SYS CHARGING OR MAKEUP FLOW A GPM N/A
- 0. 000E+00 1.140E+03 N/A N/A P
2 sUM UPSTREAM OF CENTRIFUGAL CHARGING PUMP N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 41
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/01/91 CW1 N/A HP SI FLOW REU0502 SI PUMP DISCHARGE FLOW HI PRESS SAFETY INJECTION FLOW A GPM N/A
- 0. OOOE+00
- 1. 600E+03 N/A N/A P
2 sUM DOWNSTREAM SI PUMPS N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 42
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder-NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/01/91 CWl N/A LP SI FLOW REU0501 RHR FLOW LO PRESS SAFETY INJECTION FLOW A GPM N/A
- 0. OOOE+00 1.450E+04 N/A N/A P
3 SUM DOWNSTREAM RHR PUMPS N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 43
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 8/29/2008 CW1 N/A CTMNT SMP NR LFL0702 CTMT NORMAL SUMP NR LEVEL CONTAINMENT SMP NARROW RANGE LVL A IN 9.77 GAL/INCH 1.175E+01 2.575E+01 TNKBOT N/A P 2 MAXIMUM CONTAINMENT NORMAL SUMPS N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 44
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A CTMNT SMP WR LFL0701 CTMT NORMAL SUMP WR LEVEL CONTAINMENT SMP WIDE RANGE LVL A IN 41.6 GAL/INCH 0.OOOE+00 1.560E+02 TNKBOT N/A P 2 MAXIMUM CONTAINMENT NORMAL SUMPS N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 45
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A EFF GAS RAD GTR0021B UNIT VENT GAS RAD MON RADIOACTIVITY OF RELEASED GASSES A UCI/ML N/A 1.OOOE-07 1.OOOE+05 N/A N/A S 1 N/A UNIT VENT DWNSTRM LAST PNT OF RAD ENTRY N/A N/A N/A LOW N/A N/A UNIT VENT NOMINAL FLOW RATES (CFM) 16500 MN STM ENCLOSURE BLD EXHAUST 32000 FULL SPEED AUX/FUEL BLD EXHAUST 12000 SLOW SPEED 6300 ACCESS CONTROL 1000 COND AIR REMOVAL FILTRATION 20000 CONT. SHUTDOWN PURGE EXHAUST 4000 CONT. MINIPURGE EXHAUST 9000 FUEL BLD EMERG EXHAUST ALERT/HIGH ALARMS PER ODCM ON RMS RM-II. MAY FAIL HIGH. 46
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 04/09/92 CWl N/A EFFS GAS RAD GHROO10B RADWASTE VENT GAS RAD MON RADIOACTIVITY OF RELEASED GASSES A UCI/ML 2.039E+10 ML/HR 1.OOOE-07 1.OOOE+05 N/A N/A S 1 N/A DOWNSTREAM OF EXHAUST FILTER AND FANS N/A N/A N/A LOW N/A N/A MONITORS GASEOUS RADIOACTIVITY IN THE EFFLUENT RADWASTE BUILDING DUCT. ISOLATES WASTE GAS DECAY TANK DISCHARGE LINE ON HIGH ALARM. FLOW IS 12000 SCFM. ALERT/HIGH ALARMS PER ODCM ON RMS RM-11. MAY FAIL HIGH. 47
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: '7/21/2008 CW1 N/A EFFS GAS RAD FCR0385 AFW PUMP TURBINE DISCH RAD MON RADIOACTIVITY OF RELEASES GASSES A MR/HR N/A 1.OOOE-02 1.OOOE+05 N/A N/A S 1 N/A VIEWS PLUME FROM TURBINE EXHAUST HIHI / HI /LO /LOLO 8.5OE2 /1.5E2 /NA /NA N/A N/A LOW N/A N/A MULTIPLY VALUE BY 5.51E-02 TO CONVERT UNITS TO UCI/ML. THIS CONVERSION FACTOR TAKES INTO CONDIDERATION PLUME SIZE AND DISTANCE FACTORS. MAY FAIL HIGH. 48
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 04/09/92 CW1 N/A EFF LIQ.RAD HBROO18 RADWASTE LIQUID DIS RAD MON RADIOACTIVITY OF RELEASED LIQUID A UCI/ML MAX 2.082E+06 ML/MIN 1.OOOE-07 9.990E-02 N/A N/A S 1 N/A UPSTREAM OF DISCHARGE VALVE N/A N/A N/A LOW N/A N/A HIGH RADIOACTIVITY ALARM CLOSES THE LIQUID RADWASTE SYSTEM DISCHARGE VALVE. FLOW IS 0-550 GPM. ALERT/HIGH ALARMS PER ODCM ON RMS RM-lI. MAY FAIL HIGH. 49
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: FILTERS Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A COND A/E PAD GER0092 CONDENSER DISCHARGE RAD MONITOR CONDESER AIR EJECTOR RAD A UCI/ML 1.699E+09 ML/HR 1.OOOE-07 1.OOOE-02 N/A N/A S 1 N/A UPSTREAM OF COND AIR REMOVAL SYS N/A N/A N/A LOW N/A N/A THIS MONITOR CLOSES STEAM GENERATOR BLOWDOWN ISOLATION VALVE ON HIGH ALARMS. DISCHARGES THROUGH UNIT VENT. FLOW IS 1000 SCFM. ALERT/HIGH = 2.OE-06/2.OE-05 UCI/ML ON RMS RM-11. MAY FAIL HIGH. 50
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A CNTMNT RAD SPDSC254 CTMT HI RNG AREA RAD MON RADIATION LEVEL IN CONTAINMENT A R/HR N/A 1.OOOE-01 1.OOOE+08 N/A N/A P 2 MAXIMUM INSIDE SURFACE OF CONTAINMENT WALL N/A N/A N/A LOW N/A N/A MAY FAIL HIGH. 51
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 04/09/92 CW1 N/A RCS LTDN RAD SJR0001 CVCS LETDOWN RAD MON RAD LVL OF RCS LETDOWN LINE A UCI/ML MAX 640 ML/MIN 1.OOOE-03 1.700E+03 N/A N/A S 1 N/A UPSTREAM OF CVCS LETDOWN DEMINERALIZERS N/A N/A N/A LOW N/A N/A VARIABLE ALERT/HIGH ALARMS ON RMS RM-II. MAY FAIL HIGH. 52
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/31/2005 CW1 N/A NL ABRO111 STM LINE A PORV DISCH RAD MON STM LINE A PORV DISCH RAD MON A MR/HR N/A 1.OOOE-02 1.OOOE+05 N/A N/A S 1 N/A VIEWS PLUME FROM SG A PORV HIHI /HI/LO/LOLO 1.46E2/27/NA/NA N/A N/A LOW N/A N/A MULTIPLY VALUE BY 4.06E-02 TO CONVERT UNITS TO UCI/ML. THIS CONVERSION FACTOR TAKES INTO CONSIDERATION PLUME SIZE AND DISTANCE FACTORS. MAY FAIL HIGH. 53
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/31/2005 CW1 N/A N/A ABR0112 STM LINE B PORV DISCH RAD MON STM LINE B PORV DISCH RAD MON A MR/HR N/A 1.OOOE-02 1.OOOE+05 N/A N/A S 1 N/A VIEWS PLUME FROM SG B PORV HIHI /HI/LO/LOLO 1.46E2/27/NA/NA N/A N/A LOW N/A N/A MULTIPLY VALUE BY 4.06E-02 TO CONVERT UNITS TO UCI/ML. THIS CONVERSION FACTOR TAKES INTO CONSIDERATION PLUME SIZE AND DISTANCE FACTORS. MAY FAIL HIGH. 54
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/31/2005 CWl N/A NL ABRO113 STM LINE C STM LINE C A MR/HR N/A 1.OOOE-02 1.OOOE+05 N/A N/A S 1 PORV DISCH RAD MON PORV DISCH RAD MON N/A VIEWS PLUME FROM SG C PORV HIHI /HI/LO/LOLO 1.46E2/27/NA/NA N/A N/A LOW N/A N/A MULTIPLY VALUE BY 4.06E-02 TO CONVERT UNITS TO UCI/ML. THIS CONVERSION FACTOR TAKES INTO CONSIDERATION PLUME SIZE AND DISTANCE FACTORS. MAY FAIL HIGH. 55
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc:
- Generic/Cond Desc:
Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: N1 Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/31/2005 CWl N/A NL ABR0114 STM LINE D PORV DISCH RAD MON STM LINE D PORV DISCH RAD MON A MR/HR N/A 1.OOOE-02 1.OOOE+05 N/A N/A S 1 N/A VIEWS PLUME FROM SG D PORV HIHI /HI/LO/LOLO 1.46E2/27/NA/NA N/A N/A LOW N/A N/A MULTIPLY VALUE BY 4.06E-02 TO CONVERT UNITS TO UCI/ML. THIS CONVERSION FACTOR TAKES INTO CONSIDERATION PLUME SIZE AND DISTANCE FACTORS. MAY FAIL HIGH. 56
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A SG BD PAD 1A BMR0025 SG BLOWDWN PROCESS RAD MON STM GEN BLOWDOWN RADIATION LEVEL A UCI/ML MAX 640 ML/MIN 1.000E-07 1.000E-02 N/A N/A S 1 N/A DOWNSTREAM OF SAMPLE SYS HEAT EXCHANGER N/A N/A N/A LOW N/A N/A MONITOR CLOSES STEAM GENERATOR BLOWDOWN ISOLATION TO PREVENT THE DISCHARGE OF RADIOACIVE FLUID AND TO LIMIT RADIAOCTIVE CONTAMINATION OF THE BLOWDOWN DEMINERALIZERS. MONITORS DOWNSTREAM COMB OF 4 LOOPS. RMS RM-11 ALERT/HIGH ALARMS = 1.0E-05/1.OE-04 UCI/ML. MAY FAIL HIGH. 57
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CWI N/A CTMNT PRESS SPDSC253 CTMT AVG PRESSURE CONTAINMENT PRESSURE A PSIG N/A 0.OOOE+00 6.900E+01 N/A N/A P 3 AVERAGE CONTAINMENT BLDG 2026' ELEVATION N/A N/A N/A LOW Y N/A MAY FAIL HIGH. 58
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CWI N/A CTMNT TEMP GNT0701 CTMT TEMP AVG CONTAINMENT TEMPERATURE A F N/A 0.000E+00 4.000E+02 N/A N/A P 4 AVERAGE CONTAINMENT BLDG 2047' ELEVATION N/A N/A N/A LOW N/A N/A MAY FAIL HIGH. 59
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A H2 CONC SPDSCH2A CTMT H2 AVG CONTAINMENT HYDROGEN CONC A0 CONTAINMENT VOLUME = 2.5E+06 CUBIC FEET 0.OOOE+00 1.OOOE+01 N/A N/A P 2 AVERAGE CONTAINMENT BLDG 2047' ELEVATION N/A N/A N/A LOW N/A N/A MAY FAIL HIGH. 60
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 04/09/92 CW1 N/A BWST LEVEL REU0511 RWST LEVEL BORATED WATER STORAGE TANK LEVEL A% 100% = 419445 GALLONS 0.000E+00 1.000E+02 COMPLX 0% = 18722 GALLONS P 4 AVERAGE REFUELING WATER STORAGE TANK N/A N/A N/A LOW Y WET MAY FAIL HIGH. 61
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/08/2007 CW1 N/A WIND SPEED RDS5010A MET TWR 10M A WIND SPEED WIND SPEED AT REACTOR SITE A MPH N/A 0, OOOE+00 1.OOOE+02 N/A N/A S 1 N/A MET TOWER AT 10 METERS ELEVATION HIHI/HI/LO/LOLO 40 /NA/NA/NA N/A N/A LOW N/A N/A 62
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector. Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 10/08/2007 CW1 N/A WIND SPEED RDS5060A MET TOWER 60M A WIND SPEED WIND SPEED AT REACTOR SITE A MPH N/A 0.000E+00 1.000E+02 N/A N/A S 1 N/A MET TOWER AT 60 METERS ELEVATION N/A N/A N/A LOW N/A N/A 63
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A WIND DIR RDZ5010A MET TOWER 10M A WIND DIRECTION WIND DIRECTION AT REACTOR SITE A DEG N/A 0.000E+00 3.600E+02 N/A N/A S 1 N/A MET TOWER AT 10 METERS ELEVATION N/A N/A N/A LOW N/A N/A MEASURED IN THE "FROM" DIRECTION. 0 DEG = NORTH. MAY FAIL IN ANY MODE. 64
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CW1 N/A WIND DIR RDZ5060A MET TOWER 60M A WIND DIRECTION WIND DIRECTION AT REACTOR SITE A DEG N/A 0.OOOE+00 3.600E+02 N/A N/A S 1 N/A MET TOWER AT 60 METERS ELEVATION N/A N/A N/A LOW N/A N/A MEASURED IN THE "FROM" DIRECTION. 0 DEG = NORTH. MAY FAIL IN ANY MODE. 65
Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: Reactor Unit: Data Feeder: NRC ERDS Parameter: Point ID: Plant Spec Point Desc: Generic/Cond Desc: Analog/Digital: Engr Units/Dig States: Engr Units Conversion: Minimum Instr Range: Maximum Instr Range: Zero Point
Reference:
Reference Point Notes: PROC or SENS: Number of Sensors: How Processed: Sensor Locations: Alarm/Trip Set Points: NI Detector Power Supply Cut-off Power Level: NI Detector Power Supply Turn-on Power Level: Instrument Failure Mode: Temperature Compensation For DP Transmitters: Level Reference Leg: Unique System Desc: 7/21/2008 CWl N/A STAB CLASS RDU0701A MET TWR A STABILITY (1-7=A-G) AIR STABILITY AT REACTOR SITE A N/A 1.OOOE+00 7.OOOE+00 N/A N/A P 7 N/A MET TOWER N/A N/A N/A LOW N/A N/A STABILITY PRIMARILY BASED ON RATE OF VERTICAL TEMPERATURE CHANGE. IF NOT VALIDATED GOOD, STABILITY IS BASED ON STANDARD DEVIATION OF WIND DIRECTION WHEN WIND SPEEDS ARE ABOVE 1 M/S. 1 2 3 4 5 67 = EXTREMELY UNSTABLE = MODERATELY UNSTABLE = SLIGHTLY UNSTABLE = NEUTRAL = SLIGHTLY STABLE = MODERATELY STABLE = EXTREMELY STABLE}}