ULNRC-05537, ERDS Data Point Library Revisions

From kanterella
Jump to navigation Jump to search
ERDS Data Point Library Revisions
ML082600611
Person / Time
Site: Callaway Ameren icon.png
Issue date: 09/04/2008
From: Neterer D
AmerenUE, Union Electric Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NUREG-1934, Rev 1, ULNRC-05537
Download: ML082600611 (71)


Text

AmerenUE PO Box 620 Callaway Plant Fulton, MO 65251 September 4, 2008 ,#-

U.S. Nuclear Regulatory Commission Attn: Document Control Desk Mail Stop P1-137 Washington, DC 20555-0001 ULNRC-05537

Ameren1111/ Ladies and Gentlemen:

DOCKET NUMBER 50-483 CALLAWAY PLANT UNIT 1 UNION ELECTRIC CO.

FACILITY OPERATING LICENSE NPF-30 CALLAWAY PLANT ERDS DATA POINT LIBRARY REVISIONS Ref: 1) 10 CFR 50, Appendix E.VI.3.a

2) NUREG - 1934, Revision 1 This correspondence is submitted in accordance with 10CFR50 Appendix E section VI.3.a, which requires any hardware and software changes that affect the transmitted data points identified in the ERDS Data Point Library be submitted to the NRC within 30 days after the changes are completed. Please find attached a revision for the Callaway Plant's ERDS Data Point Library reference file. These changes reflect changes made to Callaway's plant process computer on August 20, 2008.

Please contact Mr. Lewis Beaty, Computer Systems (573) 676-8632 for any questions.

This letter does not contain new commitments.

Sincerely, W. Neterer 4fq30 Si 2-o15

  • Plant Director LSB/nls Enclosure (68 pages) a subsidiary of Ameren Corporation

ULNRC-05537 September 4, 2008 Page 2 cc: Mr. Elmo E. Collins, Jr.

Regional Administrator U.S. Nuclear Regulatory Commission Region IV 612 E. Lamar Blvd., Suite 400 Arlington, TX 76011-4125 Senior Resident Inspector Callaway Resident Office U.S. Nuclear Regulatory Commission 8201 NRC Road Steedman, MO 65077 Mr. Mohan C. Thadani (2 copies)

Licensing Project Manager, Callaway Plant Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Mail Stop O-8G14 Washington, DC 20555-2738

ULNRC-05537 September 4, 2008 Page 3 Index and send hardcopy to QA File A160.0761 Hardcopy:

Certrec Corporation 4200 South Hulen, Suite 422 Fort Worth, TX 76109 (Certrec receives ALL attachments as long as they are non-safeguards and may be publicly disclosed.)

Electronic distribution for the following can be made via Other Situations ULNRC Distribution:

A. C. Heflin F. M. Diya T. E. Herrmann L. H. Graessle S. A. Maglio S. L. Gallagher L. M. Belsky (NSRB)

T. B. Elwood Ms. Diane M. Hooper (WCNOC)

Mr. Dennis Buschbaum (TXU)

Mr. Scott Bauer (Palo Verde)

Mr. Stan Ketelsen (PG&E)

Mr. Scott Head (STP)

Mr. John ONeill (Pillsbury Winthrop Shaw Pittman LLP)

Missouri Public Service Commission

Enclosure to ULNRC-05537 NRC EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY J-26060A Rev. 5 REV AFFECTED PAGES 0 NEW DOCUMENT 1 Page 2 & 9 change SEN0701 units from PCM to %

2 Change Section 2 pages 46, 48, 53-56, and 62 to revise system descriptions. Reference RFR 15126, SCR5929, 6247-6251.

3 Bulk issue for changes to Section 2 pages 15, 16, 17, 18, 44, 48, 53, 54, 55, 56.

Reference MP 00-1008A, 00-1013A, SCR 6342, 6388-6391, 7595-7598, 7737, 7739-7742, 7744, 7864-7867.

4 Bulk issue for changes to pages 4, 62-66. Reference MP 04-1020, SCR 8258, 8259 8261, 8262, 8183, 8185, 8187, 8189 & 8324.

5 Bulk issue for changes to Section 1 pages 2-4 and Section 2 pages 6-9, 11-13, 19-41, 44-46, 48, 50, 51, 57-60, 64-66.

Reference MP 07-0025.

Enclosure to ULNRC-05537 NRC EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY J-26060A Rev. 5 TABLE OF CONTENTS Section Title Page Number 1 Critical Safety Function Parameters 1 2 ERDS Data Point Library 5

Enclosure to ULNRC-05537 J-26060A Rev. 5 SECTION 1 CRITICAL SAFETY FUNCTION PARAMETERS 1

Enclosure to ULNRC-05537 J-26060A Rev. 5 CRITICAL SAFETY FUNCTION PARAMETERS COMPUTER PARAMETER PARAMETER DESCRIPTION UNITS POINT REACTIVITY CONTROL NI POWER RNG Nuclear Instruments, Power Range 0 SPDSS102 NI INTER RNG Nuclear Instruments, Intermediate Range AMPS REU0640 NI SOURC RNG Nuclear Instruments, Source Range CPS SPDSS286 NL Post Accident Wide Range PCM SEN0701 NL Post Accident Source Range CPS SEN0702 CORE COOLING REAC VES LEV Reactor Vessel Water Level 0 REU0523 TEMP CORE EX Highest Temperature at the Core Exit F RJUITC08 SUB MARGIN Saturation Temperature-Highest CET F SPDSC252 CORE FLOW Total Reactor Coolant Flow REU0487 STEAM GENERATORS SG LEVEL 1/A Steam Generator 1 (or A) Water Level % REL0404A 0

SG LEVEL 2/B Steam Generator 2 (or B) Water Level % REL0424A SG LEVEL 3/C Steam Generator 3 (or C) Water Level REL0444A SG LEVEL 4/D Steam Generator 4 (or D) Water Level REL0464A SG PRESS 1/A Steam Generator 1 (or A) Pressure PSIG SPDSH263 SG PRESS 2/B Steam Generator 2 (or B) Pressure PSIG SPDSH264 PSIG SG PRESS 3/C Steam Generator 3 (or C) Pressure PSIG SPDSH265 SG PRESS 4/D Steam Generator 4 (or D) Pressure SPDSH266 MN FD FL 1/A Stm Gen 1 (or A) Main Feedwater Flow KLB/HR SPDSH005 MN FD FL 2/B Stm Gen 2 (or B) Main Feedwater Flow KLB/HR SPDSH007 MN FD FL 3/C Stm Gen 3 (or C) Main Feedwater Flow KLB/HR SPDSH008 MN FD FL 4/D Stm Gen 4 (or D) Main Feedwater Flow KLB/HR SPDSH250 AX FD FL 1/A Stm Gen 1 (or A) Auxiliary FW Flow KLB/HR ALF0702 KLB/HR AX FD FL 2/B Stm Gen 2 (or B) Auxiliary FW Flow KLB/HR ALF0703 AX FD FL 3/C Stm Gen 3 (or C) Auxiliary FW Flow KLB/HR ALF0704 AX FD FL 4/D Stm Gen 4 (or D) Auxiliary FW Flow ALF0701 HL TEMP 1/A Stm Gen 1 (or A) Inlet Temperature F RET0419A HL TEMP 2/B Stm Gen 2 (or B) Inlet Temperature F RET0439A HL TEMP 3/C Stm Gen 3' (or C) Inlet Temperature F RET0459A HL TEMP 4/D Stm Gen 4 (or D) Inlet Temperature F RET0479A CL TEMP 1/A Stm Gen 1 (or A) Outlet Temperature F RET0406A F

CL TEMP 2/B Stm Gen 2 (or B) Outlet Temperature RET0426A 2

Enclosure to ULNRC-05537 J-26060A Rev. 5 CRITICAL SAFETY FUNCTION PARAMETERS CL TEMP 3/C Stm Gen 3 (or C) Outlet Temperature F RET0446A CL TEMP 4/D Stm Gen 4 (or D) Outlet Temperature F RET0466A COMPUTER PARAMETER PARAMETER DESCRIPTION UNITS POINT RCS INTEGRITY RCS PRESSURE Reactor Coolant System Pressure PSIG SPDSP252 0

PRZR LEVEL Primary System Pressurizer Level REU0483 RCS CHG/MU Primary System Charging or Makeup Flow GPM REU0503 HP SI FLOW High Pressure Safety Injection Flow GPM REU0502 LP SI FLOW Low Pressure Safety Injection Flow GPM REU0501 CTMNT SMP NR Containment Sump Narrow Range Level INCHES LFL0702 CTMNT SMP WR Containment Sump Wide Range Level INCHES LFL0701 RADIOACTIVITY CONTROL EFF GAS RAD Radioactivity of Released Gasses UCI/ML GTR0021B EFF GAS RAD Radioactivity of Released Gasses UCI/ML GHROO01B EFF GAS RAD Radioactivity of Released Gasses MR/HR FCR0385 EFF LIQ RAD Radioactivity of Released Liquids UCI/ML HBROO18 COND A/E RAD Condenser Air Ejector Radioactivity UCI/ML GER0092 CNMNT RAD Radiation Level in the Containment R/HR SPDSC254 RCS LTDN RAD Rad Level of the RCS Letdown Line UCI/ML SJR0001 MAIN SL 1/A Stm Gen 1 (or A) Steam Line Rad Level MAIN SL 2/B Stm Gen 2 (or B) Steam Line Rad Level MAIN SL 3/C Stm Gen 3 (or C) Steam Line Rad Level MAIN SL 4/D Stm Gen 4 (or D) Steam Line Rad Level NL Stm Line A PORV Disch Rad Mon MR/HR ABRO111 NL Stm Line B PORV Disch Rad Mon MR/HR ABRO112 NL Stm Line C PORV Disch Rad Mon MR/HR ABRO113 NL Stm Line D PORV Disch Rad Mon MR/HR ABRO114 SG BD RAD 1A Stm Gen 1 (or A) Blowdown Rad Level UCI/ML BMR0025 SG BD RAD 2B Stm Gen 2 (or B) Blowdown Rad Level SG BD RAD 3C Stm Gen 3 (or C) Blowdown Rad Level SG BD RAD 4D Stm Gen 4 (or D) Blowdown Rad Level CONTAINMENT CONDITIONS 3

Enclosure to ULNRC-05537 J-26060A Rev. 5 CRITICAL SAFETY FUNCTION PARAMETERS CTMNT PRESS Containment Pressure PSIG SPDSC253 CTMNT TEMP Containment Temperature F0 GNT0701 H2 CONC Containment Hydrogen Concentration SPDSCH2A COMPUTER PARAMETER PARAMETER DESCRIPTION UNITS POINT MISCELLANEOUS PARAMETERS BWST LEVEL Borated Water Storage Tank Level 0 REU0511 WIND SPEED Wind Speed at the Reactor Site MPH RDS5010A WIND SPEED Wind Speed at the Reactor Site MPH RDS5060A WIND DIR Wind Direction at the Reactor Site DEGFR RDZ5010A WIND DIR Wind Direction at the Reactor Site DEGFR RDZ5060A STAB CLASS Air Stability at the Reactor Site STABI RDUO701A 4

Enclosure to ULNRC-05537 J-26060A Rev. 5 SECTION 2 ERDS DATA POINT LIBRARY 5

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: NI POWER RNG Point ID: SPDSS102 Plant Spec Point Desc: POWER RANGE LEVEL AVG Generic/Cond Desc: NUCLEAR INSTR POWER RANGE Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: EACH 1% EQUALS APROX. 12 MW Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 1.200E+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 4 How Processed: AVERAGE Sensor Locations: REACTOR CAVITY Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

6

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: NI INTER RNG Point ID: REU0640 Plant Spec Point Desc: AVERAGE INTERMEDIATE RANGE Q Generic/Cond Desc: NUCLEAR INSTR INTERMEDIATE RANGE Analog/Digital: A Engr Units/Dig States: AMPS Engr Units Conversion: N/A Minimum Instr Range: 1.OOOE-II Maximum Instr Range: 1.OOOE-03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: REACTOR CAVITY Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

7

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: NI SOURC RNG Point ID: SPDSS286 Plant Spec Point Desc: SOURCE RANGE POWER LEVEL AVG Generic/Cond Desc: NUCLEAR INSTR SOURCE RANGE Analog/Digital: A Engr Units/Dig States: CPS Engr Units Conversion: N/A Minimum Instr Range: 2.500E-01 Maximum Instr Range: 1.OOOE+06 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: REACTOR CAVITY Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: 1E-10 AMPS NI Detector Power Supply Turn-on Power Level: >1E-10 AMPS Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

8

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: NL Point ID: SEN0701 Plant Spec Point Desc: POST ACCIDENT WIDE RANGE Generic/Cond Desc: POST ACCIDENT WIDE RANGE Analog/Digital: A 0

Engr Units/Dig States:

Engr Units Conversion: PERCENT

  • E-03 Minimum Instr Range: 1.OOOE-08 Maximum Instr Range: 2.OOOE+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: REACTOR CAVITY Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

9

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/01/91 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: NL Point ID: SEN0702 Plant Spec Point Desc: POST ACCIDENT SOURCE RANGE Generic/Cond Desc: POST ACCIDENT SOURCE RANGE Analog/Digital: A Engr Units/Dig States: CPS Engr Units Conversion: N/A Minimum Instr Range: 1.OOOE-01 Maximum Instr Range: 1.OOOE+05 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: REACTOR CAVITY Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A, Unique System Desc: MAY FAIL HIGH.

10

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: REAC VES LEV Point ID: REU0523 Plant Spec Point Desc: RX VESSEL WR A/B LEVEL AVG Generic/Cond Desc: REACTOR VESSEL WATER LEVEL Analog/Digital: A 0

Engr Units/Dig States:

Engr Units Conversion: TOTAL INSIDE FLUID HEIGHT 494.9 INCHES Minimum Instr Range: -2.500E+00 Maximum Instr Range: 1.250E+02 Zero Point

Reference:

COMPLX Reference Point Notes: BOTTOM OF VESSEL PROC or SENS: P Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: REACTOR VESSEL Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: WET Unique System Desc: USES DIFFERENTIAL PRESSURE ACROSS THE VESSEL TO DETERMINE VESSEL LEVEL OR RELATIVE VOID CONTENT OF THE CIRCULATING PRIMARY COOLANT SYSTEM FLUID.

MAY FAIL HIGH.

11

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 8/29/2008 Reactor Unit: CWN Data Feeder: N/A NRC ERDS Parameter: TEMP CORE EX Point ID: RJUITC08 Plant Spec Point Desc: HOTTEST NON BAD TC lMA Generic/Cond Desc: HIGHEST TEMP AT CORE EXIT Analog/Digital: A Engr Units/Dig States: F Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 2.300E+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 50 How Processed: MAXIMUM Sensor Locations: REACTOR VESSEL Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

12

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/2 1/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: SUB MARGIN Point ID: SPDSC252 Plant Spec Point Desc: RCS COOLANT SUBCOOLING Generic/Cond Desc: SATURATION TEMP - HIGHEST CET Analog/Digital: A Engr Units/Dig States: F Engr Units Conversion: N/A Minimum Instr Range: -2.OOOE+02 Maximum Instr Range: 2.OOOE+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 4 How Processed: AVERAGE OF LOWEST VALUE FROM EACH TRAIN Sensor Locations: REACTOR VESSEL Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

13

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/01/91 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: CORE FLOW Point ID: REU0487 Plant Spec Point Desc: REACTOR COOLANT LOOP AVE FLOW Generic/Cond Desc: TOTAL REACTOR COOLANT FLOW Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: EACH 1% EQUALS APROX. 1.394E+06 LB/HR Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 1.200E+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 12 How Processed: AVERAGE Sensor Locations: CROSSOVER LEG Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

14

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/31/2005 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: SG LEVEL 1/A Point ID: REL0404A Plant Spec Point Desc: SG A WR LEVEL Generic/Cond Desc: STEAM GEN A WATER LEVEL Analog/Digital: A 0

Engr Units/Dig States:

Engr Units Conversion: 100% = 586.9 INCHES Minimum Instr Range: 0. OOOE+00 Maximum Instr Range: 1.OOOE+02 Zero Point

Reference:

TUBSHT Reference Point Notes: 13 INCHES ABOVE TUBE SHEET PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: STEAM GENERATOR A Alarm/Trip Set Points: HIHI/HI /LO /LOLO 97 /92 /NA /NA (Plant mode 1-3) 97 /92 /87 /NA (Plant mode 4)

NA /NA /87 /NA (Plant mode 5-6)

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: WET Unique System Desc: 73.3% IS TOP OF HIGHEST TUBE.

MAY FAIL HIGH.

15

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/31/2005 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: SG LEVEL 2/B Point ID: REL0424A Plant Spec Point Desc: SG B WR LEVEL Generic/Cond Desc: STEAM GEN B WATER LEVEL Analog/Digital: A 0

Engr Units/Dig States:

Engr Units Conversion: 100% = 586.9 INCHES Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 1.OOOE+02 Zero Point

Reference:

TUBSHT Reference Point Notes: 13 INCHES ABOVE TUBE SHEET PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: STEAM GENERATOR B Alarm/Trip Set Points: HIHI/HI /LO /LOLO 97 /92 /NA /NA (Plant mode 1-3) 97 /92 /87 /NA (Plant mode 4)

NA /NA /87 /NA (Plant mode 5-6)

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg WET Unique System Desc: 73.3% IS TOP OF HIGHEST TUBE.

MAY FAIL HIGH.

16

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/31/2005 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: SG LEVEL 3/C Point ID: REL0444A Plant Spec Point Desc: SG C WR LEVEL Generic/Cond Desc: STEAM GEN C WATER LEVEL Analog/Digital: A 0

Engr Units/Dig States:

Engr Units Conversion: 100% = 586.9 INCHES Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 1.OOOE+02 Zero Point

Reference:

TUBSHT Reference Point Notes: 13 INCHES ABOVE TUBE SHEET PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: STEAM GENERATOR C Alarm/Trip Set Points HIHI/HI /LO /LOLO 97 /92 /NA /NA (Plant mode 1-3) 97 /92 /87 /NA (Plant mode 4)

NA /NA /87 /NA (Plant mode 5-6)

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: WET Unique System Desc: 73.3% IS TOP OF HIGHEST TUBE.

MAY FAIL HIGH.

17

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/31/2005 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: SG LEVEL 4/D Point ID: REL0464A Plant Spec Point Desc: SG D WR LEVEL Generic/Cond Desc: STEAM GEN D WATER LEVEL Analog/Digital: A 0

Engr Units/Dig States:

Engr Units Conversion: 100% = 586.9 INCHES Minimum Instr Range: 0. OOOE+00 Maximum Instr Range: 1.OOOE+02 Zero Point

Reference:

TUBSHT Reference Point Notes: 13 INCHES ABOVE TUBE SHEET PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: STEAM GENERATOR D Alarm/Trip Set Points: HIHI/HI /LO /LOLO 97 /92 /NA /NA (Plant mode 1-3) 97 /92 /87 /NA (Plant mode 4)

NA /NA /87 /NA (Plant mode 5-6)

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: 73.3% IS TOP OF HIGHEST TUBE.

MAY FAIL HIGH.

18

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: SG PRESS 1/A Point ID: SPDSH263 Plant Spec Point Desc: SG A AVG PRESSURE Generic/Cond Desc: STEAM GENERATOR A PRESSURE Analog/Digital: A Engr Units/Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 1.300E+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 3 How Processed: AVERAGE Sensor Locations: SECONDARY SIDE DOWNSTREAM SG A Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

19

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: SG PRESS 2/B Point ID: SPDSH264 Plant Spec Point Desc: SG B AVG PRESSURE Generic/Cond Desc: STEAM GENERATOR B PRESSURE Analog/Digital: A Engr Units/Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 1.300E+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 3 How Processed: AVERAGE Sensor Locations: SECONDARY SIDE DOWNSTREAM SG B Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

20

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: SG PRESS 3/B Point ID: SPDSH265 Plant Spec Point Desc: SG C AVG PRESSURE Generic/Cond Desc: STEAM GENERATOR C PRESSURE Analog/Digital: A Engr Units/Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 1.300E+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 3 How Processed: AVERAGE Sensor Locations: SECONDARY SIDE DOWNSTREAM SG C Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

21

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: SG PRESS 4/D Point ID: SPDSH266 Plant Spec Point Desc: SG D AVG PRESSURE Generic/Cond Desc: STEAM GENERATOR D PRESSURE Analog/Digital: A Engr Units/Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 1.300E+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 3 How Processed: AVERAGE Sensor Locations: SECONDARY SIDE DOWNSTREAM SG D Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

22

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: MN FD FL 1/A Point ID: SPDSH005 Plant Spec Point Desc: SG A MAIN FEEDWATER FLOW Generic/Cond Desc: STM GEN A MAIN FEEDWATER FLOW Analog/Digital: A Engr Units/Dig States: KLB/HR Engr Units Conversion: N/A Minimum Instr Range: 0. OOOE+00 Maximum Instr Range: 5.000E+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: FROM FEEDWATER SYSTEM UPSTREAM SG A Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

23

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: MN FD FL 2/B Point ID: SPDSH007 Plant Spec Point Desc: SG B MAIN FEEDWATER FLOW Generic/Cond Desc: STM GEN B MAIN FEEDWATER FLOW Analog/Digital: 'A Engr Units/Dig States: KLB/HR Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 5.OOOE+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: FROM FEEDWATER SYSTEM UPSTREAM SG B Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

24

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: MN FD FL 3/C Point ID: SPDSH008 Plant Spec Point Desc: SG C MAIN FEEDWATER FLOW Generic/Cond Desc: STM GEN C MAIN FEEDWATER FLOW Analog/Digital: A Engr Units/Dig States: KLB/HR Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 5.OOOE+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: FROM FEEDWATER SYSTEM UPSTREAM SG C Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

25

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: MN FD FL 4/D Point ID: SPDSH250 Plant Spec Point Desc: SG D MAIN FEEDWATER FLOW Generic/Cond Desc: STM GEN D MAIN FEEDWATER FLOW Analog/Digital: A Engr Units/Dig States: KLB/HR Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 5.000E+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: FROM FEEDWATER SYSTEM UPSTREAM SG D Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

26

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: AX FD FL 1/A Point ID: ALF0702 Plant Spec Point Desc: AFW TO SG A FLOW Generic/Cond Desc: STM GEN A AUXILIARY FW FLOW Analog/Digital: A Engr Units/Dig States: KLB/HR Engr Units Conversion: N/A Minimum Instr Range: 0.000E+00 Maximum Instr Range: 2.000E+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: FROM AUX FEEDWATER SYSTEM UPSTREAM SG A Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

27

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: AX FD FL 2/B Point ID: ALF0703 Plant Spec Point Desc: AFW TO SG B FLOW Generic/Cond Desc: STM GEN B AUXILIARY FW FLOW Analog/Digital: A Engr Units/Dig States: KLB/HR Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 2.000E+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: FROM AUX FEEDWATER SYSTEM UPSTREAM SG B Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

28

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: AX FD FL 3/C Point ID: ALF0704 Plant Spec Point Desc: AFW TO SG C FLOW Generic/Cond Desc: STM GEN C AUXILIARY FW FLOW Analog/Digital: A Engr Units/Dig States: KLB/HR Engr Units Conversion: N/A Minimum Instr Range: 0.000E+00 Maximum Instr Range: 2.OOOE+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: FROM AUX FEEDWATER SYSTEM UPSTREAM SG C Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

29

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 8/29/2008 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter:. AX FD FL 4/D Point ID: ALF0701 Plant Spec Point Desc: AFW TO SG D FLOW Generic/Cond Desc: STM GEN D AUXILIARY FW FLOW Analog/Digital: A Engr Units/Dig States: KLB/HR Engr Units Conversion: N/A Minimum Instr Range: 0.000E+00 Maximum Instr Range: 2.000E+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor. Locations: FROM AUX FEEDWATER SYSTEM UPSTREAM SG D Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

30

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: HL TEMP 1/A Point ID: RET041,9A Plant Spec Point Desc: RCS LOOP A WR HOT LEG TEMP Generic/Cond Desc: STM GEN A INLET TEMPERATURE Analog/Digital: A Engr Units/Dig States: F Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 7.OOOE+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: LOOP 1 HOT LEG Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

31

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: HL TEMP 2/B Point ID: RET0439A Plant Spec Point Desc: RCS LOOP B WR HOT LEG TEMP Generic/Cond Desc: STM GEN B INLET TEMPERATURE Analog/Digital: A Engr Units/Dig States: F Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 7.OOOE+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: LOOP 2 HOT LEG Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

32

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: HL TEMP 3/C Point ID: RET0459A Plant Spec Point Desc: RCS LOOP C WR HOT LEG TEMP Generic/Cond Desc: STM GEN C INLET TEMPERATURE Analog/Digital: A Engr Units/Dig States: F Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 7.OOOE+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: LOOP 3 HOT LEG Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

33

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: HL TEMP 4/D Point ID: RET0479A Plant Spec Point Desc: RCS LOOP D WR HOT LEG TEMP Generic/Cond Desc: STM GEN D INLET TEMPERATURE Analog/Digital: A Engr Units/Dig States: F Engr Units Conversion: N/A Minimum Instr Range: 0. OOOE+00 Maximum Instr Range: 7.OOOE+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: LOOP 4 HOT LEG Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

34

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: CL TEMP 1/A Point ID: RET0406A Plant Spec Point Desc: RCS LOOP A WR COLD LEG TEMP Generic/Cond Desc: STM GEN A OUTLET TEMPERATURE Analog/Digital: A Engr Units/Dig States: F Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 7.OOOE+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or-SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: LOOP 1 COLD LEG Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

35

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: CL TEMP 2/B Point ID: RET0426A Plant Spec Point Desc: RCS LOOP B WR COLD LEG TEMP Generic/Cond Desc: STM GEN B OUTLET TEMPERATURE Analog/Digital: A Engr Units/Dig States: F Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 7.OOOE+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: LOOP 2 COLD LEG Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

36

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: CL TEMP 3/C Point ID: RET0446A Plant Spec Point Desc: RCS LOOP C WR COLD LEG TEMP Generic/Cond Desc: STM GEN C OUTLET TEMPERATURE Analog/Digital: A Engr Units/Dig States: F Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 7.OOOE+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: LOOP 3 COLD LEG Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

37

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: CL TEMP 4/D Point ID: RET0466A Plant Spec Point Desc: RCS LOOP D WR COLD LEG TEMP Generic/Cond Desc: STM GEN D OUTLET TEMPERATURE Analog/Digital: A Engr Units/Dig States: F Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 7.OOOE+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: LOOP 4 COLD LEG Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

38

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: RCS WR AVG PRESSURE Point ID: SPDSP252 Plant Spec Point Desc: RCS WR AVG PRESSURE Generic/Cond Desc: REACTOR COOLANT SYSTEM PRESSURE Analog/Digital: A Engr Units/Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 3.000E+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: TUBING FROM REACTOR VESSEL Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

39

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 08/29/08 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: PRZR LEVEL Point ID: REU0483 Plant Spec Point Desc: PZR LEVEL 1/2/3 AVG Generic/Cond Desc: PRIMARY SYSTEM PRESSURIZER LEVEL Analog/Digital: A%

Engr Units/Dig States:

Engr Units Conversion: 100% = 555 INCHES Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 1.OOOE+02 Zero Point

Reference:

COMPLX Reference Point Notes: 40 INCHES ABOVE PRESSURIZER BOTTOM PROC or SENS: P Number of Sensors: 3 How Processed: AVERAGE Sensor Locations: PRESSURIZER Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: WET Unique System Desc: PRESSURIZER VOLUME IS 1800 CUBIC FEET. HEATER TOPS AT 17.5% LEVEL.

MAY FAIL HIGH.

40

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: RCS CHG/MU Point ID: REU0503 Plant Spec Point Desc: CHG PUMP SI FLOW Generic/Cond Desc: PRI SYS CHARGING OR MAKEUP FLOW Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0. 000E+00 Maximum Instr Range: 1.140E+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: sUM Sensor Locations: UPSTREAM OF CENTRIFUGAL CHARGING PUMP Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

41

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/01/91 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: HP SI FLOW Point ID: REU0502 Plant Spec Point Desc: SI PUMP DISCHARGE FLOW Generic/Cond Desc: HI PRESS SAFETY INJECTION FLOW Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0. OOOE+00 Maximum Instr Range: 1. 600E+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: sUM Sensor Locations: DOWNSTREAM SI PUMPS Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

42

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/01/91 Reactor Unit: CWl Data Feeder- N/A NRC ERDS Parameter: LP SI FLOW Point ID: REU0501 Plant Spec Point Desc: RHR FLOW Generic/Cond Desc: LO PRESS SAFETY INJECTION FLOW Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0. OOOE+00 Maximum Instr Range: 1.450E+04 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 3 How Processed: SUM Sensor Locations: DOWNSTREAM RHR PUMPS Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

43

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 8/29/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: CTMNT SMP NR Point ID: LFL0702 Plant Spec Point Desc: CTMT NORMAL SUMP NR LEVEL Generic/Cond Desc: CONTAINMENT SMP NARROW RANGE LVL Analog/Digital: A Engr Units/Dig States: IN Engr Units Conversion: 9.77 GAL/INCH Minimum Instr Range: 1.175E+01 Maximum Instr Range: 2.575E+01 Zero Point

Reference:

TNKBOT Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: MAXIMUM Sensor Locations: CONTAINMENT NORMAL SUMPS Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

44

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: CTMNT SMP WR Point ID: LFL0701 Plant Spec Point Desc: CTMT NORMAL SUMP WR LEVEL Generic/Cond Desc: CONTAINMENT SMP WIDE RANGE LVL Analog/Digital: A Engr Units/Dig States: IN Engr Units Conversion: 41.6 GAL/INCH Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 1.560E+02 Zero Point

Reference:

TNKBOT Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: MAXIMUM Sensor Locations: CONTAINMENT NORMAL SUMPS Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

45

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: GTR0021B Plant Spec Point Desc: UNIT VENT GAS RAD MON Generic/Cond Desc: RADIOACTIVITY OF RELEASED GASSES Analog/Digital: A Engr Units/Dig States: UCI/ML Engr Units Conversion: N/A Minimum Instr Range: 1.OOOE-07 Maximum Instr Range: 1.OOOE+05 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: UNIT VENT DWNSTRM LAST PNT OF RAD ENTRY Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: UNIT VENT NOMINAL FLOW RATES (CFM) 16500 MN STM ENCLOSURE BLD EXHAUST 32000 FULL SPEED AUX/FUEL BLD EXHAUST 12000 SLOW SPEED 6300 ACCESS CONTROL 1000 COND AIR REMOVAL FILTRATION 20000 CONT. SHUTDOWN PURGE EXHAUST 4000 CONT. MINIPURGE EXHAUST 9000 FUEL BLD EMERG EXHAUST ALERT/HIGH ALARMS PER ODCM ON RMS RM-II.

MAY FAIL HIGH.

46

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 04/09/92 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: EFFS GAS RAD Point ID: GHROO10B Plant Spec Point Desc: RADWASTE VENT GAS RAD MON Generic/Cond Desc: RADIOACTIVITY OF RELEASED GASSES Analog/Digital: A Engr Units/Dig States: UCI/ML Engr Units Conversion: 2.039E+10 ML/HR Minimum Instr Range: 1.OOOE-07 Maximum Instr Range: 1.OOOE+05 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: DOWNSTREAM OF EXHAUST FILTER AND FANS Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MONITORS GASEOUS RADIOACTIVITY IN THE EFFLUENT RADWASTE BUILDING DUCT.

ISOLATES WASTE GAS DECAY TANK DISCHARGE LINE ON HIGH ALARM.

FLOW IS 12000 SCFM.

ALERT/HIGH ALARMS PER ODCM ON RMS RM-11.

MAY FAIL HIGH.

47

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: '7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: EFFS GAS RAD Point ID: FCR0385 Plant Spec Point Desc: AFW PUMP TURBINE DISCH RAD MON Generic/Cond Desc: RADIOACTIVITY OF RELEASES GASSES Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units Conversion: N/A Minimum Instr Range: 1.OOOE-02 Maximum Instr Range: 1.OOOE+05 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: VIEWS PLUME FROM TURBINE EXHAUST Alarm/Trip Set Points: HIHI / HI /LO /LOLO 8.5OE2 /1.5E2 /NA /NA NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MULTIPLY VALUE BY 5.51E-02 TO CONVERT UNITS TO UCI/ML. THIS CONVERSION FACTOR TAKES INTO CONDIDERATION PLUME SIZE AND DISTANCE FACTORS.

MAY FAIL HIGH.

48

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 04/09/92 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: EFF LIQ.RAD Point ID: HBROO18 Plant Spec Point Desc: RADWASTE LIQUID DIS RAD MON Generic/Cond Desc: RADIOACTIVITY OF RELEASED LIQUID Analog/Digital: A Engr Units/Dig States: UCI/ML Engr Units Conversion: MAX 2.082E+06 ML/MIN Minimum Instr Range: 1.OOOE-07 Maximum Instr Range: 9.990E-02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: UPSTREAM OF DISCHARGE VALVE Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: HIGH RADIOACTIVITY ALARM CLOSES THE LIQUID RADWASTE SYSTEM DISCHARGE VALVE.

FLOW IS 0-550 GPM.

ALERT/HIGH ALARMS PER ODCM ON RMS RM-lI.

MAY FAIL HIGH.

49

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: COND A/E PAD Point ID: GER0092 Plant Spec Point Desc: CONDENSER DISCHARGE RAD MONITOR Generic/Cond Desc: CONDESER AIR EJECTOR RAD Analog/Digital: A Engr Units/Dig States: UCI/ML Engr Units Conversion: 1.699E+09 ML/HR Minimum Instr Range: 1.OOOE-07 Maximum Instr Range: 1.OOOE-02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: UPSTREAM OF COND AIR REMOVAL SYS FILTERS Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: THIS MONITOR CLOSES STEAM GENERATOR BLOWDOWN ISOLATION VALVE ON HIGH ALARMS. DISCHARGES THROUGH UNIT VENT.

FLOW IS 1000 SCFM.

ALERT/HIGH = 2.OE-06/2.OE-05 UCI/ML ON RMS RM-11.

MAY FAIL HIGH.

50

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: CNTMNT RAD Point ID: SPDSC254 Plant Spec Point Desc: CTMT HI RNG AREA RAD MON Generic/Cond Desc: RADIATION LEVEL IN CONTAINMENT Analog/Digital: A Engr Units/Dig States: R/HR Engr Units Conversion: N/A Minimum Instr Range: 1.OOOE-01 Maximum Instr Range: 1.OOOE+08 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: MAXIMUM Sensor Locations: INSIDE SURFACE OF CONTAINMENT WALL Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

51

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 04/09/92 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: RCS LTDN RAD Point ID: SJR0001 Plant Spec Point Desc: CVCS LETDOWN RAD MON Generic/Cond Desc: RAD LVL OF RCS LETDOWN LINE Analog/Digital: A Engr Units/Dig States: UCI/ML Engr Units Conversion: MAX 640 ML/MIN Minimum Instr Range: 1.OOOE-03 Maximum Instr Range: 1.700E+03 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: UPSTREAM OF CVCS LETDOWN DEMINERALIZERS Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: VARIABLE ALERT/HIGH ALARMS ON RMS RM-II.

MAY FAIL HIGH.

52

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/31/2005 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: NL Point ID: ABRO111 Plant Spec Point Desc: STM LINE A PORV DISCH RAD MON Generic/Cond Desc: STM LINE A PORV DISCH RAD MON Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units Conversion: N/A Minimum Instr Range: 1.OOOE-02 Maximum Instr Range: 1.OOOE+05 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: VIEWS PLUME FROM SG A PORV Alarm/Trip Set Points: HIHI /HI/LO/LOLO 1.46E2/27/NA/NA NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MULTIPLY VALUE BY 4.06E-02 TO CONVERT UNITS TO UCI/ML. THIS CONVERSION FACTOR TAKES INTO CONSIDERATION PLUME SIZE AND DISTANCE FACTORS.

MAY FAIL HIGH.

53

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/31/2005 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: N/A Point ID: ABR0112 Plant Spec Point Desc: STM LINE B PORV DISCH RAD MON Generic/Cond Desc: STM LINE B PORV DISCH RAD MON Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units Conversion: N/A Minimum Instr Range: 1.OOOE-02 Maximum Instr Range: 1.OOOE+05 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: VIEWS PLUME FROM SG B PORV Alarm/Trip Set Points: HIHI /HI/LO/LOLO 1.46E2/27/NA/NA NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MULTIPLY VALUE BY 4.06E-02 TO CONVERT UNITS TO UCI/ML. THIS CONVERSION FACTOR TAKES INTO CONSIDERATION PLUME SIZE AND DISTANCE FACTORS.

MAY FAIL HIGH.

54

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/31/2005 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: NL Point ID: ABRO113 Plant Spec Point Desc: STM LINE C PORV DISCH RAD MON Generic/Cond Desc: STM LINE C PORV DISCH RAD MON Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units Conversion: N/A Minimum Instr Range: 1.OOOE-02 Maximum Instr Range: 1.OOOE+05 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: VIEWS PLUME FROM SG C PORV Alarm/Trip Set Points: HIHI /HI/LO/LOLO 1.46E2/27/NA/NA NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MULTIPLY VALUE BY 4.06E-02 TO CONVERT UNITS TO UCI/ML. THIS CONVERSION FACTOR TAKES INTO CONSIDERATION PLUME SIZE AND DISTANCE FACTORS.

MAY FAIL HIGH.

55

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/31/2005 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: NL Point ID: ABR0114 Plant Spec Point Desc: STM LINE D PORV DISCH RAD MON

  • Generic/Cond Desc: STM LINE D PORV DISCH RAD MON Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units Conversion: N/A Minimum Instr Range: 1.OOOE-02 Maximum Instr Range: 1.OOOE+05 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: VIEWS PLUME FROM SG D PORV Alarm/Trip Set Points: HIHI /HI/LO/LOLO 1.46E2/27/NA/NA N1 Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MULTIPLY VALUE BY 4.06E-02 TO CONVERT UNITS TO UCI/ML. THIS CONVERSION FACTOR TAKES INTO CONSIDERATION PLUME SIZE AND DISTANCE FACTORS.

MAY FAIL HIGH.

56

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: SG BD PAD 1A Point ID: BMR0025 Plant Spec Point Desc: SG BLOWDWN PROCESS RAD MON Generic/Cond Desc: STM GEN BLOWDOWN RADIATION LEVEL Analog/Digital: A Engr Units/Dig States: UCI/ML Engr Units Conversion: MAX 640 ML/MIN Minimum Instr Range: 1.000E-07 Maximum Instr Range: 1.000E-02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: DOWNSTREAM OF SAMPLE SYS HEAT EXCHANGER Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MONITOR CLOSES STEAM GENERATOR BLOWDOWN ISOLATION TO PREVENT THE DISCHARGE OF RADIOACIVE FLUID AND TO LIMIT RADIAOCTIVE CONTAMINATION OF THE BLOWDOWN DEMINERALIZERS.

MONITORS DOWNSTREAM COMB OF 4 LOOPS.

RMS RM-11 ALERT/HIGH ALARMS =

1.0E-05/1.OE-04 UCI/ML.

MAY FAIL HIGH.

57

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CWI Data Feeder: N/A NRC ERDS Parameter: CTMNT PRESS Point ID: SPDSC253 Plant Spec Point Desc: CTMT AVG PRESSURE Generic/Cond Desc: CONTAINMENT PRESSURE Analog/Digital: A Engr Units/Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 6.900E+01 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 3 How Processed: AVERAGE Sensor Locations: CONTAINMENT BLDG 2026' ELEVATION Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

58

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CWI Data Feeder: N/A NRC ERDS Parameter: CTMNT TEMP Point ID: GNT0701 Plant Spec Point Desc: CTMT TEMP AVG Generic/Cond Desc: CONTAINMENT TEMPERATURE Analog/Digital: A Engr Units/Dig States: F Engr Units Conversion: N/A Minimum Instr Range: 0.000E+00 Maximum Instr Range: 4.000E+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 4 How Processed: AVERAGE Sensor Locations: CONTAINMENT BLDG 2047' ELEVATION Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

59

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: H2 CONC Point ID: SPDSCH2A Plant Spec Point Desc: CTMT H2 AVG Generic/Cond Desc: CONTAINMENT HYDROGEN CONC Analog/Digital: A0 Engr Units/Dig States:

Engr Units Conversion: CONTAINMENT VOLUME = 2.5E+06 CUBIC FEET Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 1.OOOE+01 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: CONTAINMENT BLDG 2047' ELEVATION Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MAY FAIL HIGH.

60

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 04/09/92 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: BWST LEVEL Point ID: REU0511 Plant Spec Point Desc: RWST LEVEL Generic/Cond Desc: BORATED WATER STORAGE TANK LEVEL Analog/Digital: A%

Engr Units/Dig States:

Engr Units Conversion: 100% = 419445 GALLONS Minimum Instr Range: 0.000E+00 Maximum Instr Range: 1.000E+02 Zero Point

Reference:

COMPLX Reference Point Notes: 0% = 18722 GALLONS PROC or SENS: P Number of Sensors: 4 How Processed: AVERAGE Sensor Locations: REFUELING WATER STORAGE TANK Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: Y Level Reference Leg: WET Unique System Desc: MAY FAIL HIGH.

61

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/08/2007 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: WIND SPEED Point ID: RDS5010A Plant Spec Point Desc: MET TWR 10M A WIND SPEED Generic/Cond Desc: WIND SPEED AT REACTOR SITE Analog/Digital: A Engr Units/Dig States: MPH Engr Units Conversion: N/A Minimum Instr Range: 0, OOOE+00 Maximum Instr Range: 1.OOOE+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: MET TOWER AT 10 METERS ELEVATION Alarm/Trip Set Points: HIHI/HI/LO/LOLO 40 /NA/NA/NA NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc:

62

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 10/08/2007 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: WIND SPEED Point ID: RDS5060A Plant Spec Point Desc: MET TOWER 60M A WIND SPEED Generic/Cond Desc: WIND SPEED AT REACTOR SITE Analog/Digital: A Engr Units/Dig States: MPH Engr Units Conversion: N/A Minimum Instr Range: 0.000E+00 Maximum Instr Range: 1.000E+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: MET TOWER AT 60 METERS ELEVATION Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector. Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc:

63

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: WIND DIR Point ID: RDZ5010A Plant Spec Point Desc: MET TOWER 10M A WIND DIRECTION Generic/Cond Desc: WIND DIRECTION AT REACTOR SITE Analog/Digital: A Engr Units/Dig States: DEG Engr Units Conversion: N/A Minimum Instr Range: 0.000E+00 Maximum Instr Range: 3.600E+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: MET TOWER AT 10 METERS ELEVATION Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MEASURED IN THE "FROM" DIRECTION.

0 DEG = NORTH.

MAY FAIL IN ANY MODE.

64

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CW1 Data Feeder: N/A NRC ERDS Parameter: WIND DIR Point ID: RDZ5060A Plant Spec Point Desc: MET TOWER 60M A WIND DIRECTION Generic/Cond Desc: WIND DIRECTION AT REACTOR SITE Analog/Digital: A Engr Units/Dig States: DEG Engr Units Conversion: N/A Minimum Instr Range: 0.OOOE+00 Maximum Instr Range: 3.600E+02 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: MET TOWER AT 60 METERS ELEVATION Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: MEASURED IN THE "FROM" DIRECTION.

0 DEG = NORTH.

MAY FAIL IN ANY MODE.

65

Enclosure to ULNRC-05537 J-26060A Rev. 5 DATA POINT LIBRARY REFERENCE FILE Date: 7/21/2008 Reactor Unit: CWl Data Feeder: N/A NRC ERDS Parameter: STAB CLASS Point ID: RDU0701A Plant Spec Point Desc: MET TWR A STABILITY (1-7=A-G)

Generic/Cond Desc: AIR STABILITY AT REACTOR SITE Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: N/A Minimum Instr Range: 1.OOOE+00 Maximum Instr Range: 7.OOOE+00 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 7 How Processed: N/A Sensor Locations: MET TOWER Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc: STABILITY PRIMARILY BASED ON RATE OF VERTICAL TEMPERATURE CHANGE. IF NOT VALIDATED GOOD, STABILITY IS BASED ON STANDARD DEVIATION OF WIND DIRECTION WHEN WIND SPEEDS ARE ABOVE 1 M/S.

1 = EXTREMELY UNSTABLE 2 = MODERATELY UNSTABLE 3 = SLIGHTLY UNSTABLE 4 = NEUTRAL 5 = SLIGHTLY STABLE 6 = MODERATELY STABLE 7 = EXTREMELY STABLE