- a
{
h M==
Log # TXX-7055 5
File # 10110
__,=
=
910.3
" # 'UC' 0'
('}
nlELECTRIC wimam c. counsu December 23, 1987 Emntive Ykr Punkknt U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C.
20555
SUBJECT:
COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)
DOCKET 40. 50-446 HOT SilVTDOWN PANEL SEISMIC ANALYSIS SDAR: CP-87-112 (FINAL REPORT)
Gentlemen:
On October 12, 1987, we verbally notified your Mr. 11. 5. Phillips of a deficiency identified by third party inspections which indicate the Unit 2 hot shutdown panel and main control board may not be seismically qualified.
The conditions addressed in this issue are documented in Nonconformance Reports (NCRs) CC-87-10859-X, CE-87-8714, and CE-87-8834. Our latest report on this issue, logged TXX-6941, was submitted November 11, 1987.
NCR CC-87-10859-X reported deviations involving undersized or missing structural steel members on the Unit 2 main control board. NCRs CE-87-8714 and CE-87-8834 reported deviations involving undersized members, missing members, and other structural detail items on the Unit 2 hot shutdown panel.
Calculation IMT-CA-EQ-0332-MS-605 was prelared to verify the structural integrity of the main control board and t1e hot shutdown panel prior to rework.
The results of this calculation indicate the structural integrity of the main control board and the hot shutdown panel would not be impaired had these deficiencies gone uncorrected.
I J
l 8712290144 871223 0.
PDR ADOCK 05000446 1
s DCD e, n,,,,, oi,,, sa,a, u, si va,. rcn, un
- f,
- Q
^
..g,
c
.TXX-7055..
December 23.1987.
Page 2 of:2 We have concluded that in the event these deficiencies had remained uncorrected,Lno condition adverse to safety would have existed; therefore, this issue is not-reportable under the provisions of 10CFR50.55(e).
Records supporting this conclusion are available for your inspectors to review at the CPSES Project. site.-
Very truly yours, k).G. Gu sd W. G. Counsil By:
J.~S. Marshall Supervisor, en c
censing CBC/grr.
c'- Mr. R. D. Martin, Region IV ResidentInspectors,CPSES(3)
_.-_. _ -_-___________,__ -____ -