TXX-6925, Interim Deficiency Rept CP-87-54 Re Electrical Design Drawings Which Do Not Apparently Implement FSAR Requirements for Class 1E motor-operated Valve Motor Starters.Initially Reported on 870731.Next Rept Will Be Submitted by 880122
| ML20236N256 | |
| Person / Time | |
|---|---|
| Site: | Comanche Peak |
| Issue date: | 11/06/1987 |
| From: | Counsil W, Woodlan D TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC) |
| To: | NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM) |
| References | |
| CP-87-54, TXX-6925, NUDOCS 8711160087 | |
| Download: ML20236N256 (1) | |
Text
. _ _ - - _ __ - __
)
E
' Log # TXX-6925' Fi1e # 10110
)
=
=
-908.3 l
l Ref: 10CFR50.55(e)
M# ELECTRIC l
November 6,.1987 warmm c. counsu Escrutive Vks hesi&nt l
V.'.S. Nuclear Regulatory' Commission.
. Attn:
Document Control Desk-q Washington, D.C. 20555
SUBJECT:
COMANC'HE PEAK STEAM ELECTRIC. STATION (CPSES)
DOCKET NOS. 50-445 AND 50-446 1
. CLASS 1E MOV MOTOR STARTERS SDAR: CP-87-54 (INTERIM REPORT) i; Gentlemen:
On' July 31, 1987, we verbally notified your Mr. H. S. Phillips of a deficiency involving electrical. design drawings which do not apparently implement FSAR requirements for Class 1E motor-operated valve motor starters.
The drawings do not provide the motor starter with thermal. overloads connected only to alarms or thermal' magnetic breakers to trip the starter for sustained locked motor conditions'.- This is an interim report of a potentially reportable item under,the provisions of 10CFR50.55(e). Our most recent interim report was logged TXX-6684, dated. August 31, 1987.
We are continuing our' evaluation of the impact of this issue upon the safety of plant operations.
We anticipate submitting our next report by January 22, 1988.
Very truly yours, hCo.
W.'G. Counsil 8711160087 871106 gDR ADOCK 050 5