TXX-6795, Interim Deficiency Rept CP-87-94 Re Station Uninterruptible Power Supply Sys Inverter IV 1PC3.Initially Reported on 870903.Mfg Requested to Verify That Inverter Will Function Correctly at Reduced Load.Next Rept Expected by 880108

From kanterella
(Redirected from TXX-6795)
Jump to navigation Jump to search
Interim Deficiency Rept CP-87-94 Re Station Uninterruptible Power Supply Sys Inverter IV 1PC3.Initially Reported on 870903.Mfg Requested to Verify That Inverter Will Function Correctly at Reduced Load.Next Rept Expected by 880108
ML20235V295
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 10/05/1987
From: Counsil W
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CP-87-94, TXX-6795, NUDOCS 8710150079
Download: ML20235V295 (1)


Text

..

M==

Log # TXX-6795 b

L 5

File # 10110 908.3 Ref # 10CFR50.55(e)

M1 ELECTRIC October 5, 1987 Willia,n G. Coun.sil Luccutive %ce Pinient U. S. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, D. C. 20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446 UNINTERRUPTIBLE POWER SDAR:

CP-87-94 (INTERIM REPORT)

Gentlemen:

On September 3,1987, we verbally notified your Mr. H. S. Phillips of a deficiency involving the Station Uninterruptible Power Supply (SUPS) inverter IV IPC3.

Specifically, this SUPS inverter is designed to maintain the proper output current when loaded between 2/3 and full designed load.

However, we have determined that this inverter will be loaded to only approximately 56% of full capacity, thus not ensuring that proper output will be maintained.

This is an interim report of a potentially reportable item under the provisions of 10CFR50.55(e).

Our evaluation of this issue is continuing. We have requested the manufacturer verify, by calculation, that the inverter will function correctly at the reduced load. We expect to submit our next report on this issue by January 8,1988.

Very truly yours, W. G. Counsil WJH:tgj c-Mr. R. D. Martin, Region IV Resident Inspectors, CPSES (3) 8710150079 871005 PDR ADOCK 0500o445 s

PDR

[hY

40) Nonh Olive Street LB 81 Dallas, Tetas 75201

/