TXX-6620, Final Deficiency Rept CP-87-31 Re Diesel Generator Control Air Regulator.Initially Reported on 870706.No Deficiency Existed at Plant,Per Imo Delaval Part 21 Rept.Deficiency Not Reportable Under 10CFR50.55(e)

From kanterella
(Redirected from TXX-6620)
Jump to navigation Jump to search
Final Deficiency Rept CP-87-31 Re Diesel Generator Control Air Regulator.Initially Reported on 870706.No Deficiency Existed at Plant,Per Imo Delaval Part 21 Rept.Deficiency Not Reportable Under 10CFR50.55(e)
ML20236L071
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 08/05/1987
From: Counsil W, John Marshall
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
REF-PT21-87 CP-87-31, TXX-6620, NUDOCS 8708100115
Download: ML20236L071 (1)


Text

_-

l mh" Log # TXX-6620

==

File # 10110 2

909.5 l

Ref # 10CFR50.55(e)

TUELECTRIC I

August 5, 1987 William G. Coumil Ewuthe %cr Preudent U. S. Nuclear Regulatory Commission Attn: Document Control Desk l

Washington, D. C.

20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446 DIESEL GENERATOR CONTROL AIR REGULATOR SDAR:

CP-87-31 (FINAL REPORT) l Gentlemen:

On July 6,1987, we verbally notified your Mr. H. S. Phillips of a potential deficiency involving the air pressure regulator on the IMO Delaval Diesel l

Generators which may contain manufacturing defects in the dripwell gasket

{

seating surfaces.

These defects could cause a loss of control air which in

]

turn could cause a loss of starting air pressure.

The 10 CFR Part 21 report submitted by IMO Delaval indicates the defective regulators are identifiable by the date of manufacture stamped on the bottom of the regulator.

It has been confirmed that none of the defective regulators (including four installed regulators and three spares) are in use at Comanche Peak Steam Electric Station.

4 As discussed above, no deficiency existed at Comanche Peak Steam Electric Station, therefore no report pursuant to 10CFR50.55(e) is required.

Very truly yours, k). h.( % w )1 1

W. G. Counsil 2"

By:

O. S. Marshall Supervisor, Generic Licensing MCP/gj c - Mr. R. D. Martin, Region IV Resident Inspectors, CPSES (3) h[k DO 50 5

Yk

-- s-l