Log # TXX-6249 File # 10110 903.7 Re: 10CFR50.55(e)

MM r7 filELECTRIC U""jdN3a.,,,

January 30, 1987 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446 STATIC COMPUTER MODEL FOR THE SAFEGUARDS BUILDING SDAR: CP-87-01 (INTERIM REPORT)

Gentlemen:

On January 14, 1987, we verbally notified your Mr. Ian Barnes of a deficiency l

involving an error in the finite element computer model for the Safeguards Building. The error involves a fixed support point at the roof elevation where no such support exists. This condition produces an incorrect load distribution in the computer model, which will require a reevaluation of the structural members in the building.

We are continuing our evaluation as a part of the Design Basis Consolidation Program and anticipate submitting our next report by July 29, 1987.

Very truly yours, ha W. G. Counsil By: I, G. S. Keeley G /_,

Manager, Nuclear Licphsing MCP/mlh c - Mr. E. H. Johnson, Regiori IV Mr. D. L. Kelley, RI - Region IV Mr. H. S. Phillips, RI - Region IV i

l 8702040132 870130 PDR ADOCK 05000445 S

PDR 1

f I O 400 North Olhe Start Lit 81 Dallaw leus 75201