MONTHYEARML20099B4141992-07-23023 July 1992
[table view]Proposes to Redemonstrate Gas Turbine Generator Reliability After Overhaul & Upgrade of Gas Turbine by May 1993 by Completing 20 Countable Starts & load-runs W/Two or Fewer Failures.Status Update for SBO Implementation Encl ML20044B8621993-03-0505 March 1993 Responds to NRC Transmitting SER of Util Response to Station Blackout Rule (10CFR50.63) Re Recommendation for Using Gas Turbine Generator as Alternate Ac Power Source. Gas Turbine Generator Reliability Assessment Encl ML20044D7721993-05-14014 May 1993 Updates Info in Re post-overhaul Testing of Turbine Generator to Assess Reliability of Gas Turbine.Table Listing Gas Turbine G-05 Start & Load Reliability Data Base (pre-1992 Overhaul) Encl NPL-94-0353, Forwards Evaluation of How Installation of Addl EDGs Affects SBO Rule Response for Pbnp & Rept Concluding That on-site Gas Turbine Generator (G-05) Can Continue as Alternate Ac Power Source for Pbnp1994-09-22022 September 1994 Forwards Evaluation of How Installation of Addl EDGs Affects SBO Rule Response for Pbnp & Rept Concluding That on-site Gas Turbine Generator (G-05) Can Continue as Alternate Ac Power Source for Pbnp 1993-03-05 | |