05000275/LER-1984-005, :on 840116,diesel Generator 1-2 Automatically Started Due to 4 Kv Startup Power Bus Undervoltage.Caused by Operator Inadvertently Isolating Startup Transformer 12 from 4 Kv Vital Bus Feeder1984-02-15015 February 1984
- on 840116,diesel Generator 1-2 Automatically Started Due to 4 Kv Startup Power Bus Undervoltage.Caused by Operator Inadvertently Isolating Startup Transformer 12 from 4 Kv Vital Bus Feeder
05000275/LER-1984-011, :on 840330,diesel Generator 1-3 Automatically Started When 4 Kv Bus F Potential Transformer Fuse Drawer Pulled Out During Wire Trace.Caused by Personnel Error. Labels Placed on Fuse Drawers1984-03-30030 March 1984
- on 840330,diesel Generator 1-3 Automatically Started When 4 Kv Bus F Potential Transformer Fuse Drawer Pulled Out During Wire Trace.Caused by Personnel Error. Labels Placed on Fuse Drawers
05000275/LER-1984-020, :on 840719,diesel Generator 103 Automatically Started Due to Undervoltage on Unit 2 Bus F.Caused by Const Workers Inadvertently Jarring Relay Panel & Actuating Undervoltage Relay1984-08-20020 August 1984
- on 840719,diesel Generator 103 Automatically Started Due to Undervoltage on Unit 2 Bus F.Caused by Const Workers Inadvertently Jarring Relay Panel & Actuating Undervoltage Relay
05000275/LER-1984-023, :on 840730,diesel Generators 1-1,1-2 & 1-3 Started Automatically in Response to Loss of Startup Bus Voltage.Caused by Personnel Isolating Plant from 230 Kv Offsite Startup Power.Personnel Counseled1984-08-29029 August 1984
- on 840730,diesel Generators 1-1,1-2 & 1-3 Started Automatically in Response to Loss of Startup Bus Voltage.Caused by Personnel Isolating Plant from 230 Kv Offsite Startup Power.Personnel Counseled
05000275/LER-1984-028, :on 841029,diesel Generator 1-2 Started Automatically in Response to Loss of Power to 4-kV Bus G. Caused by Failure of Breaker 52-HG-14 to Close During Performance of Surveillance Test1984-11-28028 November 1984
- on 841029,diesel Generator 1-2 Started Automatically in Response to Loss of Power to 4-kV Bus G. Caused by Failure of Breaker 52-HG-14 to Close During Performance of Surveillance Test
05000275/LER-1984-034, :on 841215,diesel Generator Started Automatically.Caused by Personnel Error.Memo Issued Instructing All Operators to Verify New Source Before Opening Original Source Breaker1985-01-0909 January 1985
- on 841215,diesel Generator Started Automatically.Caused by Personnel Error.Memo Issued Instructing All Operators to Verify New Source Before Opening Original Source Breaker
05000275/LER-1985-013-01, :on 850430,Mode 4 Entered W/Two ESF Timers Out of Tech Spec Limits.Caused by Personnel Failure to Verify Timer Settings.Personnel Given Addl Training on Importance of Verifying Data1985-06-0707 June 1985
- on 850430,Mode 4 Entered W/Two ESF Timers Out of Tech Spec Limits.Caused by Personnel Failure to Verify Timer Settings.Personnel Given Addl Training on Importance of Verifying Data
05000275/LER-1985-013, :on 850430,Mode 4 Entered W/Timer Settings Outside Acceptable Tech Spec Limits.Caused by Personnel Error.Personnel Received Addl Training & Procedure Revised1985-07-12012 July 1985
- on 850430,Mode 4 Entered W/Timer Settings Outside Acceptable Tech Spec Limits.Caused by Personnel Error.Personnel Received Addl Training & Procedure Revised