TAC:43514
From kanterella
Jump to navigation
Jump to search
Request for: Approved, Closed | |
Initiation
Questions Answers | |
| From | |
MONTHYEARML20062K0171980-09-30030 September 1980
[table view]Notifies That NRC Review of Licensee Safety Analysis for Postulated Uncontrolled Boron Dilution Events Indicates Nonconservative Plant Conditions.Recalculation of Boron Dilution & Tech Spec Mod Recommended.W/Supporting Info ML19343B8091980-12-23023 December 1980 Submits Info Re Postulated Uncontrolled Boron Dilution at Cold Shutdown,In Response to NRC .Boron Dilution Event for Cold Shutdown Recalculated Based on Return to Criticality 15 Minutes After Wave Front Reaches Core Inlet ML20003E6271981-03-31031 March 1981 Submits Info for Clarification of Re Uncontrolled Boron Dilution During Cold Shutdown.Charging Flow Should Be Limited to 60 Gpm & Alarm Provided to Alert Operator That Potential Dilution Event Is in Progress ML19343D5101981-04-29029 April 1981 Advises of Acceptability of Analysis & Proposed Administrative Controls Submitted 810331 Re Postulated Uncontrolled Boron Dilution Events.Lockout Procedure Changes Should Be Effective Prior to Next Cold Shutdown 1980-09-30 | |