- ML20217A631 (← links)
- 05000213/LER-1982-005-03, /03L-0:on 820603,during Test of Containment Air Recirculation Fan Dampers,Some Louvers of Bypass Damper on One Fan Would Not Respond to Control Signals.Caused by Disconnected Control Linkage.Linkage Reconnected (← links)
- 05000213/LER-1982-004-01, /01T-0:on 820606,during Shutdown,Main Steam Trip Isolation Valve 1 Disassembled to Determine Why Valve Would Not Cycle When Cooled Down.Caused by Misaligned Valve Disc Due to Warped Tail Link (← links)
- 05000213/LER-1981-020-03, /03L-0:on 811122,steam Flow Instrument for Steam Line 1 Observed to Have Decreased 15% of Rated Steam Flow W/O Power Reduction Taking Place.Caused by Leaking Drain Valve from Differential Pressure Transmitter (← links)
- 05000213/LER-1981-020, Forwards LER 81-020/03L-0 (← links)
- 05000213/LER-1981-019-03, /03L-0:on 811119,radial Vibration on Charging Pump Bearing Increased Above Ref Level.Caused by Worn Key & Worn Parts of Thrust Bearing Elements.Parts Replaced (← links)
- 05000213/LER-1981-008-03, /03L-0:on 810616,discovered That Pump Recirculation Valves a & B Were Reversed.Cause Not Stated. Procedure Corrected Immediately (← links)
- 05000213/LER-1991-004, :on 910301,four Containment Air Recirculation (CAR) Fans Declared Inoperable Due to Use of Inadequate Test Method for Measuring CAR Fan Air Flow.Fans Flow Vanes Adjusted & Test Reperformed Satisfactorily (← links)
- 05000213/LER-1981-009-01, /01T-0:on 810723,during Assessment of SEP Topic II-1.B,determined That Low Population Zone Distance Not in Conformance w/10CFR100.11.Caused by Error in Interpretation. Design Basis Events Being re-evaluated (← links)
- 05000213/LER-1980-017-03, /03L-0:on 800909,reactor Thermal Power Limit Was Exceeded.Caused by Abnormal Increase in Oil Pressure Due to Sticking Control Valve or Governor.Governor Adjusted & Load Brought Down (← links)
- 05000213/LER-1981-004-03, /03L-0:on 810407,MOV-35 Motor Breaker Was Discovered Open.Cause Unknown.Breaker Closed.Operators & Mechanics Counseled to Maintain Breaker Lineups (← links)