- 05000440/LER-1994-005-01, :on 940209,loss of Both Trains of Control Room Emergency Recirculation Occurred Due to Low Emergency Closed Cooling Temp.Appropriate Sys Operating Procedures Revised (← links)
- 05000341/LER-1993-014, :on 931225,automatic Reactor Shutdown Occurred Following Failure of Main Turbine.Caused by Loss of Material from Turbine Rotor in Low Pressure Section Number 3.Turbine/ Generator Repairs Will Be Determined (← links)
- 05000331/LER-1993-005, :on 930801,unacceptable MSIV Leak Rate Results Due to Excess Leakage Msiv.Replaced Integral Valve Seat & re-machined Valve Bore (← links)