- 05000348/LER-1983-065-03, /03L-0:on 831227,instrumentation Channel Associated W/Temp Indicator TI-432D Declared Inoperable. Caused by Drift of Lead/Lag Card Gain.Card Replaced & Channel Declared Operable (← links)
- 05000348/LER-1983-092-03, /03L-0:on 831225,instrumentation Channel Associated W/Pressure Transmitter PT-494 Declared Inoperable.Caused by Localized Freezing in Sensing Lines Due to Cold Weather.Lines Thawed Out (← links)
- 05000348/LER-1983-091-03, /03L-0:on 831226,radiation Monitor R-5 Declared Inoperable Due to Erroneous Indication.Caused by Faulty Connection.Connection Repaired & Monitor Declared Operable (← links)
- 05000348/LER-1983-090-03, /03L-0:on 831224,radiation Monitors R-11 & R12 Declared Inoperable When Vacuum Pump Tripped.Caused by Flow Rate Set Too High.Method for Adjusting Flow Rate Revised & Monitors Returned to Svc (← links)