- 05000315/LER-1983-021-03, /03L-0:on 830304,612-ft Elevation Containment Air Lock Interlock Found Inoperable.Caused by out-of-adjustment Cable.Cable Adjusted (← links)
- 05000315/LER-1983-020-03, /03L-0:on 830306,control Room Access Fire Door 412 Would Not Operate Properly.Caused by Extension Rod Pulling Loose from Door Frame Shoe.Shoe Setscrews & Rod Replaced (← links)
- 05000315/LER-1983-019-03, /03L-0:on 830313,612-ft Elevation Containment Air Lock Interlock Found Inoperable.Caused by out-of-adjustment Cable.Cable Adjusted (← links)
- 05000315/LER-1983-018-03, /03L-0:on 830303,upper Containment Personnel Air Lock Door Leakage Rate Found Excessive.Caused by Dirt & Tape Affixed to Outer Door Seals During Equipment Installation. Dirt & Tape Removed (← links)
- 05000315/LER-1983-017-03, /03L-0:on 830303,excessive Leakage Rates Noted at Upper & Lower Containment Personnel Air Lock Doors.Caused by Personnel Not Removing Grease Fittings After Lubrication. Fittings Replaced (← links)
- 05000315/LER-1983-016-03, /03L-0:on 830314,control Room Air Cleanup Charcoal Filter (1-HV-ACRF) Detection Sys Found Inoperable.Caused by Failed Electronic Detection Circuit Board.Circuit Board Replaced (← links)