- 05000281/LER-1983-023-03, /03L-0:on 830511,PT 27B Revealed Amp Readings for Heat Tracing Panel 9,circuit 28A,below Acceptance Criteria. Caused by Boric Acid Buildup on Heat Tape,Corroding Terminals & Resulting in Open Circuit.Heat Tracing Replaced (← links)
- 05000281/LER-1983-022-03, /03L-0:on 830430,PT-27 Revealed Amp Readings for Heat Tracing Panel 8,circuits 5A & 22A,below Acceptance Criteria.Caused by Excessive Heat.Defective Heat Tracing Replaced & Tested.Design Change Prepared (← links)