- 05000280/LER-1983-005-03, /03L-0:on 830204,10 & 11 W/Unit at 85% & Effluent Release in Progress,Radiation Recorder RR-100 Began Printing Erratically.Caused by Poor Electrical Connection on Erratic Recorder.Recorder Swapped W/Properly Functioning Unit (← links)
- 05000280/LER-1983-004-03, /03L-0:on 830202,w/Units 1 & 2 at 88% & 100% Respectively,Emergency Diesel Generator 3 Declared Inoperable Due to Leaking Cooling Water Pump.Caused by Worn Shaft Seal.Seal Replaced & Generator Tested Satisfactorily (← links)