- 05000348/LER-1983-004-03, /03L-0:on 830114,main Steam Safety Valves Q1N11V010A,Q1N11V010C,Q1N11V011C & Q1N11V012B Declared Inoperable Due to Relief Setpoint Being Out of Tolerance. Caused by Setpoint Drift.Valves Readjusted (← links)
- 05000348/LER-1983-003-03, /03L-0:on 830114,during Calibr & Functional Test, B Train Chlorine Detector Declared Inoperable Due to Failure of Tape Advance Mechanism.Caused by Paper Drive Motor Gear Failure.Paper Drive Replaced (← links)