- 05000324/LER-1981-051-03, /03L-0:on 810608,during Operability Testing,When Manual Start Was Initiated,Diesel Generator 4 Started & Then Stopped.Caused by Moisture in Run Control Solenoid Valve, Model X53-HM-2150.Moisture Removed (← links)