Pages that link to "ML19290E175"
Jump to navigation
Jump to search
The following pages link to ML19290E175:
Displaying 8 items.
- ML19290E176 (← links)
- 05000348/LER-1980-014-03, /03L-0:on 800214,while Testing Control Grade Auto Start Feature,A & B Mdaf Pumps Failed to Auto Start on Loss of Main Feedwater Pump Test Signal.Caused by Inadequate Design Change Control.Design Review Strengthened (← links)
- 05000348/LER-1980-013-03, /03L-0:on 800202,during Safety Injection W/Loss of Sys Pressure Test W/Bubble in Pressurizer,Containment Isolation Valve 1-CCW-HV-3095 Did Not Fully Close.Caused by Handwheel Outside Neutral Position.Handwheel Adjusted (← links)
- 05000348/LER-1980-012-03, /03L-0:on 800201,during a Train Loss of Offsite Power test,1B Component Cooling Water Pump Failed to Auto Start.Caused by Improper Positioning of 1C CCW Pump Handswitch.Switch Correctly Positioned & Test Completed (← links)
- 05000348/LER-1980-011-03, /03L-0:on 800202,during Safety Injection W/Loss of Sys Pressure Test W/Bubble in Pressurizer,Containment Isolation Valve 1-SW-MOV-3134 Failed to Close Fully.Caused by Motor Control Ctr Breaker Thermal Overload Trip (← links)
- 05000348/LER-1980-010-03, /03L-0:on 800201,during Train a Diesel Generator Loss of Sys Pressure Test,Flow Control Valves Failed to Open Automatically on Pump Auto Start.Caused by Misaligned Mechanism Operated Contact Switch.Switch Realigned (← links)
- 05000348/LER-1980-009-03, /03L-0:on 800201,during Loss of Offsite Power Surveillance Test,Output Breaker for Diesel Generator 1B Failed to Auto Close.Caused by Misaligned Mechanism Operated Contact Switch.Switch Realigned (← links)
- 05000348/LER-1980-007-03, /03L-0:on 800202,during Train B Diesel Generator Loss of Sys Pressure Test,Svc Water Pump 1D Failed to Auto Start & Would Not Manually Start.Caused by Test Equipment Short Circuiting Sequencer Relay Contacts.Equipment Remove (← links)