- ML19209C617 (← links)
- 05000338/LER-1979-119-03, /03L-0:on 790914,high Steam Line Differential Pressure Loop 2 Channel II Bistable Failed to Trip During Surveillance Test.Caused by Loose Lead on Signal Comparator Card.Card Replaced & New One Calibr (← links)
- 05000338/LER-1979-118-03, /03L-0:on 790914,temp of Steam Generator B Support Fell Below Tech Spec Limit.Caused by Personnel Error While Operating Support Heaters Manually.Heaters Energized to Increase Temp (← links)
- 05000338/LER-1979-117-03, /03L-0:on 790913,excessive Steam Observed Leaking Past Seat of Trip Valve TV-MS111A.Caused by Valve Not Fully Seating.Seating Surfaces Were Cleaned & Gaskets Replaced (← links)
- 05000338/LER-1979-115-03, /03L-0:on 790913,loop B Steam Indicator Read Lower than Redundant Indicator.Caused by Leaking of Transmitter Root Valves Resulting in Loss of Ref Leg Level.Steam Flow Channel Tripped & Loop Calibr (← links)