- 05000325/LER-1982-016-03, /03L-0:on 820123,containment Atmosphere Oxygen Monitor CAC-AT-1263-2 Would Not Calibr.Caused by burned-out Monitor Exciter Lamp.Lamp Replaced & Monitor Returned to Svc (← links)
- 05000324/LER-1982-031-03, /03L-0:on 820209,water Leak Dripping on Primary Containment Atmospheric Monitor 2-CAC-ATH-1263,came in Contact W/Monitor Power Supply Transformer Resulting in Loss of Power.Transformer Replaced (← links)
- 05000325/LER-1981-087-03, /03L-0:on 811127,primary Containment Atmospheric Monitoring Oxygen Analyzer 1-CAC-AT-1263-2,Model F3M3-1AX Was Exhibiting Downscale Indications.Caused by Sample Point Shift.Electromagnetic Unit Readjusted (← links)
- IR 05000324/1981012 (← links)
- 05000324/LER-1981-043-03, /03L-0:on 810411,primary Containment Atmospheric Monitor Oxygen Analyzer Tripped & Would Not Remain Running When Restarted.Caused by Failure of Photocell Light Due to Moisture Buildup in Monitor Photohelic Unit (← links)