Pages that link to "Duffy B"
← Duffy B
Jump to navigation
Jump to search
The following pages link to Duffy B:
Displayed 11 items.
- 05000336/LER-1985-005, :on 850401,retest of Control Switch Caused Loss of Normal Power Signal to Be Generated to 4.16 Kv Emergency Bus 24D.Caused by Personnel Error.Personnel Instructed to Use Increased Caution in Researching Circuits (← links)
- 05000336/LER-1982-053-03, /03L-0:on 821228,while Placing C Reactor Bldg Closed Cooling Water (RBCCW) Back in Svc,Operator Failed to Align B RBCCW W/Svc Water Header.Caused by Personnel Error. Use of Procedures re-emphasized W/Dept Personnel (← links)
- 05000336/LER-1983-032-03, /03L-0:on 831214,during Loss of Normal Power Test on Facility Z1,diesel Generator 12U Started But Failed to Sequence on Emergency Loads.Caused by Lack of Breaker Permissive Inputs.Connection Resoldered (← links)
- 05000336/LER-1983-001-04, /04T-0:on 830302,recorder Associated W/Liquid Radwaste Discharge Path Rjr 9129 Failed While in Mode 3 at 532 F.Caused by Stripped Gear on Drive Motor.Defective Gear & Motor Replaced (← links)
- 05000336/LER-1982-040-03, /03L-0:on 820918,acceptance Criteria Not Met When Containment Personnel Airlock Test Performed.Caused by Leaking Gasket on Inner Airlock Door.Gasket Replaced & Successful Leak Test Performed (← links)
- 05000336/LER-1982-025-03, /03L-0:on 820618,control Element Assembly 44 Inserted Into Step 174 & Could Not Be Withdrawn.Caused by Inoperable Pull Down Power Circuit Due to Loose Connection Between Timer Module & Power Switch.Connection Tightened (← links)
- 05000336/LER-1982-010-03, /03L-0:on 820401,while at 100% Power,Svc Water Header a Removed from Svc to Repair Leak in Pipe Downstream to Reactor Bldg Closed Cooling Water HX Isolation Valve. Caused by Coating Failure.Leak Repaired (← links)
- 05000336/LER-1981-031-03, /03L-0:on 810825,during Testing,Diesel Generator 12U Failed to Start on Signal.Apparently Caused by Loose Amphenol Connector Between Emergency Generator Control & Woodward Governor.Connector Cleaned & Tightened (← links)
- 05000336/LER-1982-003-03, /03L-0:on 820104,fan F394 Tripped on Overload, Rendering Radiation Monitors 8123A & B Inoperable.Caused by Seized Bearings Due to Lack of Lubricaton.Blower Replaced. Proper Drainplug Installation Will Be Verified (← links)
- 05000336/LER-1981-044-03, /03L-0:on 811229,while in Mode 6,radiation Monitors 8262A,8262B & 8123B Were inoperable.De-energizing of Channel C Caused 8123B to Become Inoperable.Monitors 8262A & 8262B Removed from Svc for Repair (← links)
- 05000336/LER-1981-042-03, /03L-0:on 811207,while Performing Type C Leak Rate Test,Excessive Leakage Was Noticed on Containment Hydrogen Purge Line.Caused by Slippage of Isolation Valve 2-EB-92 Set Screw.Indentation Made in Valve Stem Set Screw (← links)