- 05000311/LER-1982-050, Forwards LER 82-050/03L-0.Detailed Event Analysis Encl (← links)
- 05000000/LER-1983-034-03, /03L-0:on 830419,Fire Door S71-18,between Emergency Diesel Room 2H & Turbine Bldg,Would Not Latch. Caused by Latch Sticking.Latch Lubricated (← links)
- 05000373/LER-1983-122-03, /03L-0:on 831007,during Startup,Rcic Sys Isolated by High Steam Flow Switch 1E31-N013B.Switch Performed Function But Failed to Reset.Caused by Switch Stuck in Set Position.Switch Lightly Tapped & Reset (← links)
- 05000373/LER-1983-045-03, /03L-0:on 830506,during Reactor Vessel High Water Level HPCS Injection Valve Closure Calibr & Functional Test, Level Indicating Switch 1B21-N100A Found Out of Tolerance. Caused by Instrument Drift (← links)
- 05000373/LER-1983-034-03, /03L-0:on 830408,during LIS-HP-10,level Indicating Switch 1B21-N100A as-found Setpoint Exceeded Tech Spec Value.Caused by Setpoint Drift.Switch Setpoint Recalibr (← links)
- PLA-2016, Forwards 10CFR50.59 Rept Summarizing Safety Evaluations Approved from 820717-1231.Rept Format for Responding to SER Items Described (← links)