Pages that link to "05000324/LER-1983-026, Forwards LER 83-026/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000324/LER-1983-026, Forwards LER 83-026/03L-0:
Displayed 36 items.
- 05000325/LER-1983-003, Forwards LER 83-003/03L-0 (← links)
- 05000324/LER-1983-083, Updated LER 83-083/01T-1:on 830905,supply Valve 2-FP-V39 to Deluge Sys of Both Standby Gas Treatment Sys Discovered Shut.Caused by Operator Error.Valves Tagged for Identification.Auxiliary Operator Disciplined (← links)
- 05000324/LER-1983-097, Updated LER 83-097/01T-1:on 831212,during Testing,Per IE Bulletin 83-02,crack Indications Discovered in 19 of 131 Welds in Reactor Recirculation & Reactor Water Cleanup Sys. Caused by Stress Corrosion Cracking (← links)
- 05000324/LER-1983-015, Forwards LER 83-015/03L-0 (← links)
- 05000324/LER-1983-007, Forwards LER 83-007/03L-0 (← links)
- 05000324/LER-1983-044, Forwards LER 83-044/03L-0 (← links)
- 05000324/LER-1983-045, Forwards LER 83-045/03L-0 (← links)
- 05000325/LER-1983-014, Forwards LER 83-014/03L-0 (← links)
- 05000324/LER-1983-037, Forwards LER 83-037/03L-0 (← links)
- 05000324/LER-1983-016, Forwards LER 83-016/03L-0 (← links)
- 05000324/LER-1983-024, Forwards LER 83-024/03L-0 (← links)
- 05000325/LER-1983-012, Forwards LER 83-012/03L-0 (← links)
- 05000325/LER-1983-013, Forwards LER 83-013/03L-0 (← links)
- 05000325/LER-1983-011, Forwards LER 83-011/03L-0 (← links)
- 05000324/LER-1983-032, Forwards LER 83-032/03L-0 (← links)
- 05000325/LER-1983-015, Forwards LER 83-015/01T-0 (← links)
- ML20072N159 (redirect page) (← links)
- 05000325/LER-1983-006, Forwards Updated LER 83-006/03L-1 (← links)
- 05000324/LER-1983-056-03, /03L-0:on 830605,while Withdrawing Control Rods to Increase Reactor Power Level,Control Rod 26-19 Did Not Have RTGB Position Indication as Required.Caused by Faulty Position Indication Probe (← links)
- 05000324/LER-1983-026-03, /03L-0:on 830313,suppression Pool Level Indicator/ Recorder 2-CAC-LR-2602 Showed out-of-spec Low Level While Redundant Level Indicators Showed Normal Level.Caused by out-of-calibr Instrument Transmitter.Device Recalibr (← links)
- 05000325/LER-1983-025-03, /03L-0:on 830606,supervisory Review Determined That Standby Liquid Control Sys Unknowingly Rendered Inoperable for 1 H 20 Minutes on 830604.Caused by Personnel Failure to Update Log Index (← links)
- 05000324/LER-1983-058-03, /03L-0:on 830606,HPCI Sys Steamline Area Differential Temp High Logic a Isolation Signal Occurred, Causing Automatic Closure of HPCI Sys Steam Supply Outboard Valve PCIV 2-E41-F003 (← links)
- 05000325/LER-1983-020-03, /03L-0:on 830524,intermediate Range Monitor a Indicated Instrument Upscale.Caused by Moisture Accumulation in Monitor Detector Cable Undervessel Connector.Connector Replaced (← links)
- 05000324/LER-1983-052-03, /03L-0:on 830526,smoke Observed Emanating Briefly from RHR Sys Flow Transmitter Signal Converters 2-E11-FY-3338 & Indicator Did Not Show Expected Indication. Caused by Test Leads Shorting to Ground (← links)
- 05000324/LER-1983-029-03, /03L-0:on 830220,routine Surveillance During Plant Operation Revealed Audible Evidence of Airflow Through Both Doors of Reactor Bldg 50-ft Elevation.Caused by 1 1/2 Inch Diameter Hole in Outer Door.Hole in Door Sealed (← links)
- 05000324/LER-1983-035-03, /03L-0:on 830520,reactor Water Cleanup Differential Flow Indicator 2-G31-R615 Indicated High. Caused by Low Output Signal from Flow Transmitter FT-N012. Transmitter Calibr & Returned to Svc (← links)
- 05000324/LER-1983-048-03, /03L-0:on 830520,surveillance Revealed Primary Containment Atmosphere Oxygen Analyzer 2-CAC-AT-1259-2 Drywell Oxygen Concentration 1% Higher than Redundant Analyzer.Caused by Calibr Drift (← links)
- 05000325/LER-1983-007-03, During Extended Refueling Outage,One Fuel Bundle Located Around Control Rods 22-15, 34-23,34-27 & 26-43.Caused by Procedual Inadequacy.Rods Inserted & Procedure Revised (← links)
- 05000324/LER-1983-017-03, /03L-0:on 830126,during Standby Gas Treatment Sys Heater Check,One Heater Element in Treatment Sys a Found Inoperable.Caused by Damaged Power Supply Cable Terminal Lug Ring.Lugs Checked for Proper Tightness (← links)
- 05000325/LER-1983-006-03, Insert/Withdrawal Position & Drive Power Indication for Source Range & Immediate Range Monitors Discovered Inoperable.Caused by Blown Control Power Supply Fuse F13.Fuse Replaced (← links)
- 05000324/LER-1983-019-01, /01T-0:on 830210,while Performing Drywell Insp, Instrument Air Tubing to Safety Relief & ADS Valve Accumulators Inadequately Supported.Caused by Inadequate Controls to Ensure Support Design Compliance (← links)
- 05000324/LER-1983-020-03, /03L-0:on 830129,primary Containment Atmosphere Oxygen Analyzer 2-CAC-AT-1263-2 Indicated 0.5% Step Decrease in Drywell Oxygen Concentration.Caused by Zero Shift in Instrument Magnetic Analyzer 1263-2.Analyzer Replaced (← links)
- 05000325/LER-1983-022-03, /03L-0:on 830513,during Routine Surveillance,Fire Hose Station 2-AOG-58 Declared Inoperable Due to Bent Hose Reel.Caused by Opening Valve W/Hose on Reel.Hose Replaced (← links)
- 05000325/LER-1983-018-03, /03L-0:on 830503 & 14 Average Power Range Monitor D Inoperable Due to Failed Power Supply.First Failure Caused by Defective Diode CR1:thyrister SCR1 & Capacitor C1.Cause of 830514 Failure Undetermined (← links)
- 05000324/LER-1983-040-03, /03L-0:on 830426,while Performing Operability Test of Remote Shutdown RHR Sys Flow Monitoring Instrumentation PT-55.8PC,determined RHR Sys Flow Transmitter 2-E11-FT-3338 Had No Output Response to Applied Test Signal (← links)
- 05000325/LER-1983-023-03, /03L-0:on 830426,loss of Offsite Power Occurred When 230 Kv Bus Tripped.Fire Reported in 4160/480 Transformer Between Emergency Bus E-2 & E-6.Caused by Personnel Error.Trip Signal Cleared (← links)