Pages that link to "05000302/LER-1977-158, Forwards LER 77-158/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000302/LER-1977-158, Forwards LER 77-158/03L-0:
Displaying 13 items.
- ML19308D382 (redirect page) (← links)
- 05000302/LER-1977-104, Forwards Rev 1 to LER 77-104 Re Four RCS Flow Instruments Exceeding Calibr Tolerances.Util Revising Commitment to Agree W/Tech Specs to Calibr Transmitters Every 18 Months (← links)
- 05000302/LER-1977-099, :on 770810,during Mode 1,primary Containment Average Temp Exceeded 130 F,Violating Tech Specs.Caused by Procedural Inadequacy Re Closed Industrial Cooling Water Supply Valve.Procedure SP-344 Revised (← links)
- 05000302/LER-1977-104-01, /01t-1:on 770902,four RCS Flow Instruments Discovered Out of Calibr.Caused by Calibr Drift of Differential Pressure Transmitters.Transmitters Replaced. Instruments Will Be Calibr Every 18 Months (← links)
- 05000302/LER-1977-161, E/04X-0:on 771229-30,biomass of Fish & Shellfish Impinged on Intake Screens,Exceeding ETS Limits.Partially Caused by Oil Barge Entering Intake Canal During Sampling. Entire Scaled Sardine School May Have Been Trapped (← links)
- 05000302/LER-1977-163, Forwards LER 77-163/03L-0 (← links)
- 05000302/LER-1977-164, E/04X-0:on 771231 (Discovered 780111),correct Procedure Not Used for Environ Sample Analysis.Seawater, Small Terrestrial Animals & Vegetables Had LLDs Greater than ETS Requirements.Caused by Inadequate Sample Size (← links)
- 05000302/LER-1977-158-03, /03L-0:on 771227,3B Emergency Diesel Generator Failed to Start During Monthly Surveillance Test SP-354. Caused by Foriegn Matter Preventing Governor to Function Properly.Servo Booster Cleaned & Tested (← links)
- 05000302/LER-1977-160, E/04X-0:on 771221-22,biomass of Fish & Shellfish Impinged on Intake Screens Exceeding 50 kg/24-h ETS Levels. Partially Caused by Oil Barge Entering Intake Canal During Sampling (← links)
- 05000302/LER-1977-158 (redirect page) (← links)
- 05000302/LER-1977-159-03, /03L-0:on 771228,reactor Bldg Purge Exhaust Valve AHV-1B Did Not Auto Close Upon Reactor Bldg Purge Initiation.Caused by Purge Exhaust Valve AHV-1B Not Being Open Enough to Activate Automatic Closure Matrix (← links)
- 05000302/LER-1977-159, Forwards LER 77-159/03L-0 (← links)
- ML19296D595 (← links)