Displaying 50 items.
- ML18045A470 (redirect page) (← links)
- 05000255/LER-1980-043-01, /01T-0:on 801106,measured Leakage Through Containment Penetration 14 Exceeded Tech Spec Limit.Cause Under Evaluation.Check Valve & Butterfly Valve Seat Replaced (← links)
- 05000255/LER-1980-030-03, /03L-0:on 800811,during Normal Operation, Discovered Indicating Lamps for CV-0437B & CV-0438B (Iodine Removal Sys Tanks Outlet Valves) Were Not Lit.Caused by Moisture in Junction Box Resulting in Blown Fuses (← links)
- 05000255/LER-1980-040-01, /01T-0:on 801023,while Sluicing Resins from T-50 to T-69,waste Gas Monitor RIA-1113 Alarmed,Indicating Airborne Release.Caused by Leakage in T-50 Air Supply. Waste Gas Surge Tank Was Pumped Down (← links)
- 05000255/LER-1980-042-01, /01T-0:on 801031,during Plant Cooldown,Steam Generator Dp Exceeded 1,380 Psid Limit for Approx 85 Minutes.Caused by Operator Misplotting of Power Conversion Sys Vs Pressure.Operator Counseled (← links)
- 05000255/LER-1980-041-01, /01T-0:on 801030,during Routine Surveillance Testing of Diesel Generator 1-2,emergency Diesel Generator Charging Was Inoperable for Tests While Pump P-55C Was Inoperable for Repairs.Caused by Deficient Test Procedure (← links)
- 05000255/LER-1980-039-03, /03L-0:on 801023,during Review of Testing Requirements for CV-3027 & CV-3056 It Was Determined That Valves Must Be Stroked Quarterly.Caused by Testing Requirements Not Addresing Potential for Degraded Equipment (← links)
- 05000255/LER-1980-017, Forwards Updated LER 80-017/03X-1 (← links)
- 05000255/LER-1980-019, Forwards LER 80-019/01T-0 (← links)
- 05000255/LER-1980-011, Forwards LER 80-011/03L-0 (← links)
- 05000255/LER-1980-004, Forwards LER 80-004/01T-0 (← links)
- 05000255/LER-1980-012, Licensee Event Report 80-012 Regarding Bottom Half of the Barrier for Fire Penetration HO-12 Was Missing During Inspection of Fire Barriers (← links)
- 05000255/LER-1980-014, Licensee Event Reports 80-014, 80-015, and 80-016 Regarding Oil Level in Snubbers No. 5, 9, and 7 Were Found to Be Less than Zero During Routine Testing of Hydraulic Snubbers (← links)
- 05000255/LER-1980-018, Licensee Event Report 80-018 Regarding Oil Level in Snubber No. 2 Found to Be Less than Zero During Routine Testing of Hydraulic Snubbers (← links)
- 05000255/LER-1980-033, Forwards LER 80-033/01T-0 (← links)
- 05000255/LER-1980-003, Forwards Revised Page 3-36 to Basis of Tech Spec Section 3.4 Re Containment Cooling,Submitted in 861020 Change Request.Error in Original Submittal Resulted from LER 80-003 Re Description of Main Steam Line Break Results (← links)
- 05000255/LER-1980-044-03, /03L-0:on 801125,closure Head Fasteners on Return Head Flange of Letdown Heat Exchanger Found Corroded.Caused by Contact W/Borated Water Leaking from Flange Due to Improper Assembly of Closure Head.Damaged Studs Replaced (← links)
- 05000255/LER-1980-044, Forwards LER 80-044/03L-0 (← links)
- 05000255/LER-1980-021, Forwards Corrected App C, Calculations of Radiological Effects as Results of Hypothetical Accident W/CV-3030 Open, to 800820 LER 80-021,Revision 1.Corrected Apps E & F Also Encl (← links)
- 05000255/LER-1980-043, Forwards LER 80-043/01T-0 (← links)
- 05000255/LER-1980-040, Forwards LER 80-040/01T-0 (← links)
- 05000255/LER-1980-042, Forwards LER 80-042/01T-0 (← links)
- 05000255/LER-1980-041, Forwards LER 80-041/01T-0 (← links)
- 05000255/LER-1980-039, Forwards LER 80-039/03L-0 (← links)
- 05000255/LER-1980-038-03, /03L-0:on 801016,level in Concentrated Boric Acid Tank Fell Below Limit.Caused by Increase in Safety Injection/Refueling Water Tank Level.Proposed Change in Reporting Requirement Submitted to NRC (← links)
- 05000255/LER-1980-038, Forwards LER 80-038/03L-0 (← links)
- 05000255/LER-1980-036-01, /01T-0:on 800929,while Testing C-51A Vacuum Degasifier Pump,Radioactive Gaseous Release Occurred Prior to Required 15-day Holdup.Cause Not Determined.Release Terminated by Stopping Vacuum Pump (← links)
- 05000255/LER-1980-036, Forwards LER 80-036/01T-0 (← links)
- 05000255/LER-1980-037-01, /01X-0:on 801009,found Pipe Support Sway Strut Bushings Furnished by Corner & Lada,Inc May Become Loose or Disengaged from Clamp End.Caused by Mfg Defect.Bechtel Is Reviewing Issue for Corrective Actions (← links)
- 05000255/LER-1980-037, Forwards LER 80-037/01X-0 (← links)
- 05000255/LER-1980-035-03, /03L-0:on 800830,during Return to Svc After Shutdown,Leakage Discovered Through Pressure Relief Valve. Caused by Loose Spring Guide within Solenoid Assembly Valve Due to Failed Brazed Joint.Guide Brazed Back Onto Plate (← links)
- 05000255/LER-1980-035, Forwards LER 80-035/03L-0 (← links)
- 05000255/LER-1980-034-03, /03L-0:on 800826,during Pretest Review of Check Valve:Inservice Insp Surveillance,Procedures Required Closing & Reopening of Sirw Tank Outlet Valves.Caused by Inadequate Procedures.Procedures Revised (← links)
- 05000255/LER-1980-034, Forwards LER 80-034/03L-0 (← links)
- 05000255/LER-1980-033-01, /01T-0:on 800911 During Control Rod Exercising,Rod 31 Was Misaligned.Caused by Rod Insertion Length.Procedures Revised to Lessen Insertion & Remain within Tech Spec Requirements (← links)
- 05000255/LER-1980-032-03, /03L-0:on 800826,primary Data Logger Ceased Performing Control Rod Scans & Secondary Data Logger Typer Became Stuck.Cause Unknown.Failure Corrected by Resetting (← links)
- 05000255/LER-1980-031-01, /01T-0:on 800826,group 1 Control Rods Withdrew 121 Inches Which Resulted in Unplanned Reactivity Insertion. Caused by Loss of Both Primary & Secondary Data Loggers. Loggers Restored & Control Rods Reinserted (← links)
- 05000255/LER-1980-027-01, During Venting of Quench Tank to Waste Gas Surge Tank,Gaseous Release Occurred W/O 15 Day Min Holdup.Caused by Leaking Isolation Valve & Valve Pin Disassembly.Pin Replaced (← links)
- 05000255/LER-1980-027, Forwards Updated LER 80-027/01X-1 (← links)
- 05000255/LER-1980-030, Forwards LER 80-030/03L-0 (← links)
- 05000255/LER-1980-023-03, Containment High Radiation Detectors Re 1805 & 1807 Determined Inoperable.No Apparent Cause for Failure.Detectors Disassembled,Cleaned & Recoated & Are Now Functional (← links)
- 05000255/LER-1980-023, Forwards Updated LER 80-023/03X-1 (← links)
- 05000255/LER-1980-028-03, /03L-0:on 800807,during Normal Power Operations, Low Level Alarm Received from Switch on SI Tank a (T 82 A). Apparently Caused by Slow Leakage from Tank.Inaccuracy of Analog Channel Attributed to Liquid Loss in Ref Leg (← links)
- 05000255/LER-1980-028, Forwards LER 80-028/03L-0 (← links)
- 05000255/LER-1980-029-01, /01T-0:on 800819,during Normal operation,CV-3031 Was Stroked Closed & Immediately Reopened.Caused by Failure to Follow Procedural Requirements Related to Plant Conditions Needed to Perform Test (← links)
- 05000255/LER-1980-029, Forwards LER 80-029/01T-0 (← links)
- 05000255/LER-1980-021-01, /01X-1:on 800725,during Valve Inservice Insp, Operator Opened Containment Sump Valve CV-3030.Valve Stayed Open 36-h.Caused by Operator Error.Valve Closed,Operator Counseled & Shift Turnover Checklist Revised (← links)
- 05000255/LER-1980-026-03, /03L-0:on 800719,during Refilling of Safety Injection tanks,FT-0313 Found Inoperable.Caused by Failure to Close Instrument Equalizing Valve During Recent Calibr (← links)
- 05000255/LER-1980-026, Forwards LER 80-026/03L-0 (← links)
- 05000255/LER-1980-025-01, /01T-0:on 800801,during Vol Control Tank Venting, Unplanned Gaseous Release Occurred W/O 15-day Min Holdup. Caused by Either Dirt Trapped in Head Plate & Diaphragm or Uneven Tightening of Compressor Head Bolts (← links)